The ES24V controls a ventilator to meet fresh air supply requirements
while limiting operation during periods of extreme temperature and/or
humidity.
INSTALLATION & OPERATION MANUAL
CAUTION:
1. READ AND SAVE THESE INSTRUCTIONS.
2. Before installation or maintenance, disconnect the power supply.
3. This control is for 24 VAC applications only.
4. All wiring must be done by qualified person(s) in accordance with
all applicable codes & standards.
5. Indoor Use Only
WIRING
Use Copper Conductors Only
Terminal
Type
Description
R
24Vac
Input: 24Vac input (50/60 Hz)
C
24Vac
Input: 24Vac common
G
24Vac
Input: Furnace Blower (Optional)
B
24Vac
Output: Furnace Blower (2A max) (Optional)
F+
24Vac
Output: Fresh Air Fan output + (2A max)
F-
24Vac
Output: Fresh Air Fan output - (2A max)
D+
24Vac
Output: Motorized Damper + (2A max) (Optional)
D-
24Vac
Output: Motorized Damper - (2A max) (Optional)
H+
24Vac
Output: Duct Heater output + (2A max) (Optional)
H-
24Vac
Output: Duct Heater output - (2A max) (Optional)
MOUNTING
Front Cover Removal
Insert a flathead screwdriver into the slot
on the right side of the controller and
apply gentle pressure inward and up so
that the front cover disengages from the
back cover. Pull the front cover up and to
the left.
Back Cover Mounting
Locate the control on the mounting surface being sure to allow clearance
for the necessary wiring connections. Mark the mounting hole locations and
remove the back cover from the work space. Make the stripped/labelled
wiring connections now. CAUTION: Be sure that no exposed portions of
wires are touching.
If installing onto wood, mount the back cover with the provided screws. If
installing onto drywall, drill pilot holes using a 7/32”drill bit (not provided)
and tap the provided drywall anchors into place. Mount with provided
screws. NOTE: Velcro can be used to mount the control instead of screws
if necessary.
Verify that wiring connections are correct and secure.
Align the front cover with the
back cover starting on the left
side. Push the front cover
towards the back cover in a
“hinging” motion from the left to
the right. CAUTION: Make sure
the front cover is aligned properly
with the back cover to avoid
damaging the control. Press
down until the front cover snaps
securely into place.
Sensor Mounting
The ES24V comes with a temperature sensor (26AWG, 2 wire) and
humidity sensor (6P6C, telephone wire), both 10” long. Install the sensors
at a location so that they will be exposed to the fresh air intake (ex: the
fresh air ductwork). Drill 2, 3/4" diameter holes, spaced appropriately and
install the sensors with the provided hardware. NOTE: the sensor wires can
be extended up to 300 feet without deviation. Use appropriate duct tape to
seal joints/openings as necessary.
DIMENSIONS (in)
SCREEN DIAGRAM
OPERATING MODES
OFF Mode: All outputs are off.
ON Mode: The Fresh Air Fan, Motorized Damper (if enabled), and
Furnace Blower (if enabled) are on continuously. The Duct Heater
will follow the user settings (see FUNCTION SETTINGS below).
Eco Mode: Eco Mode limits the Fresh Air Fan operation during
periods of extreme temperature and/or humidity. The Fresh Air
Fan, Motorized Damper (when enabled), Furnace Blower (when
enabled), and Duct Heater (when enabled) will follow the user
settings when the outside air temperature/humidity is within the
user set limits (see FUNCTION SETTINGS below).
The Fresh Air Fan will run for the user set amount of time/hour
while the temperature/humidity limits are within range. The
temperature/humidity sensors evaluate the fresh air conditions
every 10 seconds. While the fresh air temperature/humidity is
within the user set limits, the Fresh Air Fan/accessories will run
per the user settings. When the fresh air temperature/humidity
exceeds the user set limits, the Fresh Air Fan/accessories will turn
off and engage a timer. The timer will run the fan for 5 minutes
every 15 minutes in order to meet code requirements. NOTE: the
Furnace Blower (if enabled) will not run during this check
procedure to prevent cycling. The fan will continue this check
procedure until the temperature/humidity limits are within the user
set limits.
If Enabled (in SETUP):
The Furnace Blower will be on: any time there is a call from “G”
Input or any time the Fresh Air Fan is on (excluding the check
procedure above).
The Motorized Damper will be on anytime the Fresh Air Fan is on.
The Duct Heater will be on any time the Fresh Air Fan is on and
the set point > room temperature +2°F.
(Motorized Damper, Furnace Blower, and Duct Heater are
required to be enabled in SETUP)
BUTTONS
Keys
Description
Mode
Select the operating mode
Set
Confirm settings
▲
Increase settings
▼
Decrease settings
S&P USA Ventilation Systems, LLC
6393 Powers Ave
Jacksonville, FL 32217
ES24V
Envirosense Ventilation Controller
Operating Modes: OFF, ON, or Eco
Motorized Damper indicator
Relative Humidity %
Temperature (F or C)
Thermostat integration indicator
Fresh Air Fan indicator
Duct Heater indicator
SETUP
Press and hold [MODE] for 3 seconds to enter setup mode.
OR
01 Optional Duct Heater (Default: heater disabled)
Press [▲]/[▼] to enable or disable duct heater.
Press [SET] to confirm settings.
OR
02 Temperature Unit (Default: degrees F)
Press [▲]/[▼] to select degrees C or degrees F.
Press [SET] to confirm settings.
OR OR
03 Humidity/Temperature (Default: temperature and humidity)
Press [▲]/[▼] to evaluate temperature only, humidity only or both
temperature and humidity.
Press [SET] to confirm settings.
OR
04 Optional Motorized Damper (Default: motorized damper disabled)
Press [▲]/[▼] to enable or disable motorized damper.
Press [SET] to confirm settings.
OR
05 Optional Thermostat Integration (Default: standalone system)
Press [▲]/[▼] to enable or disable thermostat integration.
Press [SET] to confirm settings.
06 Fan Run Time per Hour (Default: 15 minutes)
Press [▲]/[▼] to adjust 5-60 Minutes/Hour (Increments of 5).
Press [SET] to confirm settings and return to normal mode.
All setting screens will return to the normal mode screen automatically after
20 seconds.
FUNCTION SETTINGS
Press <Set> key to set the temperature/humidity limits and duct heater set
point.
FACTORY RESET
Press and hold [▲]&[▼] buttons in OFF mode for ~5 seconds to
reset the control to factory settings. will be displayed on the
screen when complete.
FEATURES
◆Voltage supply: 24VAC +/- 15% 50/60Hz
◆System mode: Off / On / Eco
◆Temperature unit mode: F or C
◆Temperature measurement range: 15F - 130F (-10C to
55C)
◆High Limit Temperature settings range: 65 -105°F (18C to
40C)
◆Low Limit Temperature settings range: 20 - 60°F ( -6C to
16C)
◆Heater Temperature settings range: 32°F - 62°F (0°C -
16°C)
◆Temperature resolution: 1 °F or 0.5C
◆Temperature Accuracy: +/-1 °F or 0.5C
◆Humidity measurement range: 10-95%
◆High Limit Humidity settings range: 55-90%
◆Low Limit Humidity settings range: 10-50%
◆Humidity resolution: 1 %
◆Humidity Accuracy: +/- 5 %
◆10 inch RJ11 (6 wires) phone cable for humidity sensor
◆10 inch 26AWG (2 wires) cable for temperature sensor
◆Max Sensor Wire Length: 300 feet (100m)
◆Motorized Damper relay output (Maximum 2A)
◆Fan relay output (Maximum 2A)
◆Duct Heater relay output (Maximum 2A)
◆Furnace Blower Output (Maximum 2A)
◆Non-volatile memory to store settings, configuration
parameters
◆Operating temperature: 15F to 130F (-10 C to 55C)
◆Storage temperature: -20F to 158F (-29 C to 70C)
◆Temperature limit of mounting surface: 130F (55C)
◆Terminals: 2.5mm2cable
◆Pollution Degree: 2
◆Degree of protection: IP20
◆Electronic control: Type 2.B
◆Class II Control
◆cULus listed: UL60730-1
◆Housing Material: Lexan 943(f1), 1.6mm thick, V-0 (UL94
Rating)
◆Time Setting Rage: 5-60 Minutes
◆Power: 1.5W (Max)
200103
Press [▲]/[▼] to change the high limit
temperature setting.
Press [SET] to confirm settings.
Press [▲]/[▼] to change the high limit
humidity setting.
Press [SET] to confirm settings.
Press [▲]/[▼] to change the low limit
temperature setting.
Press [SET] to confirm settings.
Press [▲]/[▼] to change the duct heater
activation temperature setting.
Press [SET] to confirm settings and return to
normal mode.
Press [▲]/[▼] to change the low limit
humidity setting.
Press [SET] to confirm settings.

Other S&P Controllers manuals

S&P TR90 Series User manual

S&P

S&P TR90 Series User manual

S&P REB-1N User manual

S&P

S&P REB-1N User manual

S&P Envirosense ES24V User manual

S&P

S&P Envirosense ES24V User manual

S&P REB 5 User manual

S&P

S&P REB 5 User manual

S&P RMB User manual

S&P

S&P RMB User manual

S&P REB 5 User manual

S&P

S&P REB 5 User manual

S&P REB-1NE User manual

S&P

S&P REB-1NE User manual

S&P REB 5 User manual

S&P

S&P REB 5 User manual

S&P REB-1N User manual

S&P

S&P REB-1N User manual

S&P RMT-1.5 User manual

S&P

S&P RMT-1.5 User manual

S&P RMB Series User manual

S&P

S&P RMB Series User manual

S&P MULTI-REG CONTROL 2841 Series User manual

S&P

S&P MULTI-REG CONTROL 2841 Series User manual

S&P CONTROL ECOWATT User manual

S&P

S&P CONTROL ECOWATT User manual

S&P RMB Series User manual

S&P

S&P RMB Series User manual

S&P CONTROL ECOWATT User manual

S&P

S&P CONTROL ECOWATT User manual

Popular Controllers manuals by other brands

Brewolution Ferminator Connect instruction manual

Brewolution

Brewolution Ferminator Connect instruction manual

SOMFY animeo WM installation guide

SOMFY

SOMFY animeo WM installation guide

Tally metaSETZ TLC-8D manual

Tally

Tally metaSETZ TLC-8D manual

ECKELMANN UA 410 L Case Controller Operating	 instruction

ECKELMANN

ECKELMANN UA 410 L Case Controller Operating instruction

Hydrofarm Autopilot PX2 instructions

Hydrofarm

Hydrofarm Autopilot PX2 instructions

ST STM32F101xx series Reference manual

ST

ST STM32F101xx series Reference manual

ESBE CRC200 Series manual

ESBE

ESBE CRC200 Series manual

Talgil DREAM 2 Guide

Talgil

Talgil DREAM 2 Guide

V-TAC VT-2421 instruction manual

V-TAC

V-TAC VT-2421 instruction manual

Crestron DM-RMC-4K-100-C-1G quick start

Crestron

Crestron DM-RMC-4K-100-C-1G quick start

Extron electronics MLC 62 IR D user guide

Extron electronics

Extron electronics MLC 62 IR D user guide

Imi Heimeier Regulux operating instructions

Imi Heimeier

Imi Heimeier Regulux operating instructions

Parker Compax3S installation manual

Parker

Parker Compax3S installation manual

Desoutter ESP-CA 230 Original instructions

Desoutter

Desoutter ESP-CA 230 Original instructions

Skyrc Leopard v2 instruction manual

Skyrc

Skyrc Leopard v2 instruction manual

Danfoss AME 55 installation guide

Danfoss

Danfoss AME 55 installation guide

EPH Controls DETACH PRO B1PF Installation & operating instructions

EPH Controls

EPH Controls DETACH PRO B1PF Installation & operating instructions

oventrop EnOcean Aktor MH CON B Installation and operating instructions

oventrop

oventrop EnOcean Aktor MH CON B Installation and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.