Percentage Timer Control with Furnace Interlock (SFM)
Installation and Operation Manual: TR90/TR130/TR200/TR300/TRe200/TRe300/
TRLPe100/TRLPe100c
SFM-Submittal_v1_012022
All specications are subject to change without notice unless approved in submittal by S&P USA.
OPERATION
The Percentage Timer Control with indicator lights and furnace interlock (SFM) is the
primary control for S&P USA Energy Recovery Ventilator (ERV) models TR90, TR130,
TR200, TR300, TRe200, TRe300, and TRLPe100/TRLPe100c when Furnace Interlock is
needed and no Push Button Lighted (SPBL) controls are used. This proportional runtime
control will operate your ERV an adjustable amount of time each hour as well as tell your
furnace or air-conditioner to circulate air throughout your home at the same time, if not
already doing so. When the “Runtime %” light is on, the SFM control is telling your ERV
and furnace/air-conditioning blower to operate. Additionally, the SFM can be set to turn
your ERV o or to operate constantly. ERV operation time will vary from application to
application as well as time of year, lifestyle, indoor air quality concerns, and other factors.
Discuss any questions with your HVAC professional or contact S&P USA directly.
FOR CONSTANT OPERATION: Press the S&P logo until the light next to “100” is lit.
OPERATION EACH HOUR: Run time of your ERV and furnace/air-conditioning blower
can be adjusted from 10%, or 6 minutes each hour, up to 100% operation in 10%
increments. Simply press the S&P logo until the light next to the desired percentage
amount is lit. You can increase or decrease the run time based upon daily, weekly, or
monthly variations in occupancy levels, indoor odors, cold weather winter humidity, or other
indoor air quality concerns as needed.
NO OPERATION: Press the logo until all lights are o. The control is o. When set to o,
your furnace/air-conditioning blower will run based upon your thermostat or other controls.
INSTALLATION
1. Install control in a standard 2" x 4" electrical box, with a minimum depth of 1.5", with
the two screws provided.
2. Wire Size: 18–22 gauge, no more than 500 feet. Wiring is non-polar.
3. See the wiring schematics for your specic installation.
4. Use Lutron Decora™ cover plate to complete installation (single cover plate included).
Runtime %
Setting
Minutes of
operation
(PER HOUR)
EQUIVALENT CONTINUOUS OPERATION CFM
TRLPe100/
TRLPe100c TR90 TR130 TR200 TR300 TRe200 TRe300
10 679 13 18 30 21 24
20 12 14 18 26 36 59 42 48
30 18 21 27 39 54 89 63 72
40 24 28 36 52 72 119 84 96
50 30 35 45 65 91 149 105 120
60 36 42 54 78 109 178 126 144
70 42 49 63 91 127 208 147 168
80 48 56 72 104 145 238 168 192
90 54 63 81 117 163 267 189 216
100 60 70 90 130 181 297 210 240
PERCENTAGE RUN TIME TABLES
"ASHRAE 62.2 2013/16
RESIDENTIAL VENTILATION AIR ReQUIRE-
MENTS CONTINUOUS CFM"
FLOOR
AREA
(FT2)
BEDROOMS
123 4 5
<500 30 38 45 53 60
501-
1000 45 53 60 68 75
1001-
1500 60 68 75 83 90
1501-
2000 75 83 90 98 105
2001-
2500 90 98 105 113 120
2501-
3000 105 113 120 128 135
3001-
3500 120 128 135 143 150
3501-
4000 135 143 150 158 165
4001-
4500 150 158 165 173 180
4501-
5000 165 173 180 188 195