Schischek InMax-8-F1 User manual

ENTWURF
EXPLOSIONPROOF
InMax - ... - F1
InMax - ... - SF1
InMax - ... - BF1
InMax - ... - CTS
InMax - ... - VAS
InMax-...-F1
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-S-F1_en
V07 – 19-Oct-2021
Subject to change!
Compact. Easy installation. Universal. Cost effective. Safe.
Product views and applications
Description Highlights
Safety damper Ball valve Throttle valve
Electrical rotary actuators
for use in safe areas
On-off control mode, 24…240 VAC/ DC, 95° angle of rotation incl. 5° pretension
8 Nm, 15 Nm with safety operation: fast spring return ~ 1 s*
Type Torque Supply Motor running time Spring return* Control mode Feedback Wiring diagram
InMax- 8 - F1 8 Nm 24...240 VAC/DC 3 / 15 / 30 / 60 / 120 s/90° ~ 1 s/90° On-off – SB 2.4/2.5
InMax- 15 - F1 15 Nm 24...240 VAC/DC 3 / 15 / 30 / 60 / 120 s/90° ~ 1 s/90° On-off – SB 2.4/2.5
InMax- 8 - SF1 8 Nm 24...240 VAC/DC 3 / 15 / 30 / 60 / 120 s/90° ~ 1 s/90° On-off 2 × aux. switches SB 2.4/2.5 + 3.2
InMax- 15 - SF1 15 Nm 24...240 VAC/DC 3 / 15 / 30 / 60 / 120 s/90° ~ 1 s/90° On-off 2 × aux. switches SB 2.4/2.5 + 3.2
InMax- 8 - BF1 8 Nm 24...240 VAC/DC 3 / 15 / 30 / 60 / 120 s/90° ~ 1 s/90° On-off 2 × aux. switches + tripping circuit SB 2.4/2.5 + 7.4
InMax- 15 - BF1 15 Nm 24...240 VAC / DC 3 / 15 / 30 / 60 / 120 s / 90° ~ 1 s/ 90° On-off 2 × aux. switches + tripping circuit SB 2.4 / 2.5 + 7.4
InMax- ... - CTS Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
InMax- ... - VAS Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)
InMax ¼ turn actuators – size S
►Industrial use
►Universal supply unit from 24…240 VAC/DC
►5 different motor running times 3–15–30 –60–120 s/90°, adjustable on site
►On-off control with fast spring return function
►Circuit for direct connection of the ...Pro-TT-... safety temperature trigger
(type ...-BF1)
►2 integrated auxiliary switches, switching at 5° und 85° (type ...-SF1 and ...-BF1)
►100 % overload protected
►Compact design and small dimension (L × W × H = 210 × 95 × 80 mm)
►Direct coupling to the damper shaft with double square connection 12 × 12 mm
►95° angle of rotation inclusive 5° pretension
►Robust aluminium housing (optional with seawater resistant coating) or in stainless steel
►IP66 protection
►Simple manual override included + preparation for comfortable manual override
►Gear made of stainless steel and sinter metal
►Weight only ~ 3,5 kg
►Integrated heater for ambient temperatures down to −40 °C
►Integrated safety temperature sensor
►Integrated equipment for manual adjustment (push button, lamp, switch)
►Preparation for adaptable and adjustable auxiliary switches type ...Switch
The InMax actuators are a revolution for safety, control and shut-off
dampers and other motorized applications for HVAC systems in chemical,
pharmaceutical, industrial and offshore/onshore plants.
IP66 protection, small dimensions, only 3,5 kg weight, universal functions
and technical data, an integrated heater and an optional stainless steel
housing guarantee safe operation even under difficult environmental
conditions. High quality brushless motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times are selectable on site.
The integrated universal power supply is self adaptable to input voltages
in the range of 24...240 VAC/DC. The actuators are 100% overload
protected and self locking.
...Max-...-F1 actuators are equipped with spring return fail safe function.
Additionally the ...Max-...-SF1 and ...-BF1 actuators are equipped with
2 integrated, potential free auxiliary switches each and ...Max-...-BF1
comes with a tripping circuit for connecting the ...Pro-TT-... safety
temperature trigger. Standard shaft connection is a double square direct
coupling with 12 × 12 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
*at temperatures below −20 °C, depending on the load, the spring return period can be up to 20 sec. If fast spring return below −20 °C is required, please contact our sales support.
Please note that nominal values are also subject to tolerances.
1 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-S-F1_en
V07 – 19-Oct-2021
InMax-...-F1 InMax-...-SF1 InMax-...-BF1
Special options ... -CTS ... -VAS
Approbations
Torque motor (min.) 8 Nm 15 Nm 8 resp. 15 Nm 8 resp. 15 Nm
Torque spring (F) min. 8 Nm min. 15 Nm min. 8 resp. 15 Nm min. 8 resp. 15 Nm
Torque blockade In blockade and end positions torques are higher than above specified torques for motor and spring.
Dimensioning of external load Upon spring return the external load should be max. 80 % of torque spring (F), but
min. 2 Nm min. 5 Nm min. 2 resp. 5 Nm min. 2 resp. 5 Nm
Supply voltage / frequency 24...240 VAC/DC ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %
Power consumption max. starting currents see Extra information (in acc. with voltage, I start >> I rated ), approx. 5 W holding power, approx. 16 W for heater
Protection class Class I (grounded)
Angle of rotation and indication 95° incl. ~ 5° pretension, mechanical value indication
Working direction Selectable by left/right mounting to the damper/valve shaft
Motor running times 3 / 15 / 30 / 60 / 120 s/90° selectable on site
3 sec. mode – motor In acc. with the supply voltage and external torque 3 to 4 s/90° angle of rotation
Motor Brushless DC motor
Control mode On-off
Spring return (F) spring return upon voltage interruption or opening of line 3, response time up to 1 sec. after voltage interruption
Spring return running time (F) ~ 1 s/90° (at temperatures below -20 °C, depending on the load, the spring return period can be up to 20 s.)
Safety operations at 1 sec. (F) min. 1,000 acc. to construction of damper and ambient. Consider minimum external load!
Tripping circuit ...-BF1 Circuit to connect the InPro-TT-... safety temperature trigger directly to the actuator with M12 quick connection
Aux. switches ...-SF1, ...-BF1 2 integrated auxiliary switches, switching at 5° and 85° angle of rotation, potential free. Grid fuse-protection is recommended!
Umax/ Imax AC = 250 V/5 A; Umin AC/DC = 5 V; After one-time operation with U > 24 V AC/DC or I > 100 mA: Umin AC/DC = 12 V
Umax/ Imax DC = 48 V/1 A; Imin AC/DC = 5 mA; Imin AC/DC = 100 mA
Axle of the actuator Double square 12 × 12 mm, direct coupling, 100 % overload protected
Electrical connection Cable ~ 1 m, wire cross section 0.5 mm², equipotential bonding 4 mm². Connections require a terminal box!
Diameter of cable ~ Ø 6.2 mm ~ Ø 6.2 mm ~ Ø 6.2 + 7.4 mm ~ Ø 9.3 mm
2 cables in version ...-SF1
Cable gland M16 × 1.5 mm
Manual override Use delivered socket wrench, max. 4 Nm
Heater Integrated, controlled heater for ambient temperature down to −40 °C
Housing material Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CTS) or stainless steel housing,
№1.4581 / UNS-J92900 / similar AISI 316Nb (...-VAS)
Dimensions (L × W × H) 210 × 95 × 80 mm, for diagrams see Extra information
Weight ~ 3,5 kg aluminium housing, stainless steel ~ 7 kg
Ambients Storage temperature −40…+70 °C, working temperature −40…+50 °C
Humidity 0...90 % rH, non condensing
Operating 3 sec. motor run time In 3 s mode the motor will work only after 1 minute of voltage supply. While open/close operation (open voltage supply and shut it down)
motor works only with speed of 15 s/90°
≥15 sec. motor run time at 15 / 30 / 60 / 120 s 100 % of ED is permitted (ED = duty cycle)
Maintenance Maintenance free relative to function, maintenance must comply with regional standards, rules and regulations
Wiring diagrams SB 2.4 / 2.5 SB 2.4 / 2.5 SB 2.4 / 2.5 + 3.2 SB 2.4 / 2.5 + 7.4
Scope of delivery Actuator, 4 screws M4 × 100 mm, 4 nuts M4, Allen key for simple manual override
Parameter at delivery 8 Nm, 30 s/90° 15 Nm, 30 s/90° 8 resp. 15 Nm, 30 s/90° 8 resp. 15 Nm, 30 s/90°
Technical data InMax- 8 - F1 InMax- 15 - F1 InMax-... - SF1 InMax-... - BF1
CE identification CE
EMC directive 2014/30/EU
Low voltage directive 2014/35/EU
Enclosure protection IP66 in acc. with EN 60529
2 / 4
EXPLOSIONPROOF
InMax- 8 -...F1 ►
InMax- 15 -...F1 ►
8 Nm
15 Nm
▼
3 s/90° ►
15 s/90° ►
30 s/90° ►
60 s/90° ►
120 s /90° ►
00
01
02
03
04
05
06
07
08
09
InBox
S
T
a
a
a
+
~
+
~
+
~
+
~
−
~
−
~
−
~
−
~
PE
PE
PE
PE
1
1
1
1
2
2
2
2
3
3
3
3
PA
PA
PA PA
4
1
7
4
5
2
6
3
8
5
9
6
< 5°
< 5°
> 85°
> 85°
1 2
°C
InPro-TT
U < 90 V AC/DC 2 AT 10 AT
U > 90 V AC/DC 5 AT 10 AT
U < 90 V AC/DC 2 AT 10 AT
U > 90 V AC/DC 5 AT 10 AT
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-S-F1_en
V07 – 19-Oct-2021
InMax-...-F1 InMax-...-SF1 InMax-...-BF1
Special options ... -CTS ... -VAS
Electrical connection Parameters, adjustments and failure indication
Parameter selection
Functions, adjustments and parameters
Type
Running times Position of switch S
Torques
Example:
InMax-15-BF1
Requested parameter:
Torque 15 Nm
Motor running time 30 s/90°
Result:
Switch position 02
Installation
Supply *
24...240 VAC/DC ± 10 %
* electrical wiring see diagrams
Switch – Push button – Lamp
for adjustment
(behind the blanking plug)
10-position switch (S)
Push button (T)
3-colour LED
All actuators are equipped with a universal supply unit working at a voltage range from
24...240 VAC/DC. The supply unit is self adjusting to the connected voltage!
The safety operation of the spring return function works if the supply voltage is cut or line 3
opened. For electrical connection a terminal box is required (e.g. InBox).
An over-current protection fuse < 10 A has to be provided by installer.
Note: the initial current is appr. 2 A for 1 second.
Integrated auxiliary switches signal the rotation angle’s position. U
min
and I
min
change once
the switches were operated with higher voltage or current.
Attention
During commissioning apply a self adjustment drive.
Regard duty cycle at motor running times!
Never use spring return actuators without external load.
Auxiliary switches *
see Technical data
On-off SB 2.4 On-off (1 wire) SB 2.5
Wiring of integrated auxiliary switches SB 3.2
On-off – spring return + tripping circuit SB 7.4
Tripping circuit for In-
Pro-TT-... safety
temperature trigger
Test
button
Attention!
At 1-wire control
mode the heater
does not work in
case of open contact.
24...240 VAC/DC
24...240 VAC/DC
24...240 VAC/DC
24...240 VAC/DC Integrated auxiliary switches,
Grid fuse-protection recommended.
min. max.
Integrated auxiliary switches,
Grid fuse-protection recommended.
min. max.
A) Self adjustment of angle of rotation
ATTENTION: To adjust the angle of rotation connect only wire 1 and 2.
Do not connect wire 3.
Apply supply voltage to wire 1 and 2. Turn switch (S) to position 02. Press
button (T) for a minimum of 3 seconds. The actuator drives to the first end posi-
tion, detects the blocking position and performs a spring return to the starting posi-
tion. The LED flashes GREEN during adjustment. After that disconnect from the
mains and connect wire 3.
The adjustment takes about 31 seconds (30 sec. “On”, 1 sec. “Off”).
B) Selecting motor running time
Adjust parameters only if actuator is in idle state or without applied potential.
Turn switch (S) to the position required for the intended operation acc. to table
above. The selected parameters will be carried out at the actuator’s next opera-
tion.
C) Function of the InPro-TT-... in the tripping circuit
When the ...Pro-TT’s tripping circuit is opened the actuator runs into its end posi-
tion with spring return.
D) Additional information for control in On-off operation
a closed = actuator opens
a open = spring return
The rotation direction (clockwise/counter clockwise) depends on left/right
mounting of the actuator to the damper.
3 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-S-F1_en
V07 – 19-Oct-2021
InMax-...-F1 InMax-...-SF1 InMax-...-BF1
Special options ... -CTS ... -VAS
Important information for installation and operation
Extra information (see additional data sheet)
Additional technical information, dimensions, installation intruction, illustration
and failure indication
A. Installation, commissioning, maintenance
All national and international standards, rules and regulations must be complied with.
Apparatus must be installed in accordance with manufacturer instructions. If the equip-
ment is used in a manner not specified by the manufacturer, the safety protection pro-
vided by the equipment may be impaired.
For electrical connection a terminal box is requested (e.g. InBox-...).
Attention: If the actuator is put out of operation all rules and regulations must be
applied. You have to cut the supply voltage before opening a terminal box!
The cable of the actuator must be installed in a fixed position and protected against
mechanical and thermical damage. Connect potential earth. Avoid temperature
transfer from armature to actuator ! Close all openings with min. IP66.
For outdoor installation a protective housing against sun, rain and snow should be
applied to the actuator as well as a constant supply at terminal 1 and 2 for the inte-
grated heater. During commissioning apply a self adjustment drive.
Actuators are maintenance free. An annual inspection is recommended. Actuators
must not be opened by the customer.
B. Manual override
Manual override only if supply voltage is cut. Use delivered socket wrench with slow
motions, usage can be tight.
Attention: Releasing or letting go the Allen key too fast at manual operating actuators
with spring return causes risk of injury!
C. Shaft connection, selection of running time
Actuators are equipped with a direct coupling double square shaft connection of
12 × 12 mm. For round shafts adaptors/clamping connection (accessories, e.g. KB-S)
are available. The housing of the actuator is axially symmetrically built to select
Open-close direction of the spring return function by left-right mounting. Using the
10-position switch different motor running times and spring return running times can be
selected on site in acc. to the actuator type.
D. Temperature trigger ...Pro-TT-...
The actuator ...Max-...-BF1 will work only with the temperature trigger InPro-TT-...
E. Operation with 3 sec. motor running time
Note following:
1. The 3 sec. motor running time mode is only available in switch position 0 and 5 and
at a constant supply voltage applied for a minimum of 1 minute on terminal 1 and 2.
2. The actuator opens at voltage on terminal 3 (resp. closes) and closes at voltage on
terminal 4 (resp. opens) – depending on mounting position of the actuator.
3. The max. duty ratio is 10 % resp. 1 cycle / minute. Between two fully 3 sec. cycles in
the same direction there must be a minimum intermission of 1 minute. Trying to run
the actuator in the same direction in less than the required minimum of 1 minute
the function will be blocked for the rest of the idle period. Later the release for the
next cycle is made automatically by an internal timing relay.
4. Same function is applied on spring return actuators, fail safe operation is regarded
same as a motor running cycle.
5. Trying to use the 1 wire On-off methode in switch position 0 and 5, software
changes the motor running time temporarily and automatically to 15 s/90° to pro-
tect the actuator for overheating due to uncontrolled duty ratio.
F. Spring return
Spring return function works only if the supply voltage for terminal 1 or 2 is cut. In the
event of an electrical interruption, the spring returns to its end position even if supply
voltage is available again during return function. Thereafter operation will continue.
G. Operation at ambient temperatures below −20 °C
All actuators are equipped with a regulated integrated heating device designed for em-
ployments down to −40 °C ambient temperature. The heater will be supplied automati-
cally by connecting the constant voltage supply on the clamps 1 and 2.
1. After mounting the actuator must bei immediately electrically connected.
2. The heater switches on automatically when actuator reaches internally −20 °C. It
heats up the actuator to a proper working temperature, then heater switches off au-
tomatically. Actuator will not run during heating process.
3. The adjustment options are only ensured after this heating up period.
H. Excess temperatures
All actuators are protected against excess temperature. The internal thermostat works
as a maximum limiter and, in the event of failure at incorrect temperatures, shuts off
the actuator irreversible. An upstream connected temperature sensor stops the actua-
tor before reaching its max. temperature. This safety feature is reversible, after cooling
down the actuator is completely functional again. In this case the failure must be elimi-
nated immediately on site!
I. Synchron mode
Do not connect several actuators to one shaft or link mechanically together.
J. Mechanical protection
Actuators must be operated with a minimum external load.
After installing the actuator to the damper/armature a self adjustment drive has to be
performed in order to protect the damper/armature against mechanical overload.
During operation the actuator reduces briefly its speed (motor power) before reaching
the end position for a “gentle” blockade/stop.
K. Routine tests of fire dampers
For periodic inspection of fire dampers cut off the supply line (current of actuator).
The test button at InPro-TT-... is only for test aims of actuator’s function.
Special solutions and accessories
...-CTS Types in aluminium housing with seawater resistant coating,
parts nickel-plated
...-VAS Types in stainless steel housing, parts nickel-plated
Adaptions for dampers and valves on request
InMax-...-S3 Ambient temperature up to +60 °C, 110...240 VAC/ DC, 25 % ED
InPro-TT-... Safety temperature trigger for fire dampers
InBox-... Terminal boxes
MKK-S Mounting bracket for boxes type ...Box-... directly on actuator
InSwitch 2 external aux. switches, adjustable
KB-S Clamp for damper shafts Ø 10...20 mm and □10...16 mm
AR-12-xx Reduction part for 12 mm square connection to 11, 10, 9 or 8 mm shafts
BSH-S Mounting holder for actuators in fire danger areas
Kit-S8 Cable glands nickel-plated
4 / 4

Other manuals for InMax-8-F1

1

This manual suits for next models

10

Other Schischek Controllers manuals

Schischek InMax Series User manual

Schischek

Schischek InMax Series User manual

Schischek RedMax-30-BF User manual

Schischek

Schischek RedMax-30-BF User manual

Schischek RedMax S Series User manual

Schischek

Schischek RedMax S Series User manual

Schischek EXV-8 Series User manual

Schischek

Schischek EXV-8 Series User manual

Schischek RedMax-8-F1 User manual

Schischek

Schischek RedMax-8-F1 User manual

Schischek RedMax F Series User manual

Schischek

Schischek RedMax F Series User manual

Schischek RedMax F1 Series User manual

Schischek

Schischek RedMax F1 Series User manual

Schischek RedMax BF Series User manual

Schischek

Schischek RedMax BF Series User manual

Schischek ExMax CTM Series User manual

Schischek

Schischek ExMax CTM Series User manual

Schischek InMax SF3 Series User manual

Schischek

Schischek InMax SF3 Series User manual

Schischek ExReg-V CT Series User manual

Schischek

Schischek ExReg-V CT Series User manual

Schischek RedMax CTM Series User manual

Schischek

Schischek RedMax CTM Series User manual

Schischek ExMax-50.75 Owner's manual

Schischek

Schischek ExMax-50.75 Owner's manual

Schischek ExMax User manual

Schischek

Schischek ExMax User manual

Schischek RedMax User manual

Schischek

Schischek RedMax User manual

Schischek ExMax Series User manual

Schischek

Schischek ExMax Series User manual

Schischek InMax CTM Series User manual

Schischek

Schischek InMax CTM Series User manual

Schischek ExMax CTS Series User manual

Schischek

Schischek ExMax CTS Series User manual

Schischek InMax-8-F1 User manual

Schischek

Schischek InMax-8-F1 User manual

Schischek ExMax CTM Series User manual

Schischek

Schischek ExMax CTM Series User manual

Schischek ExMax Series Quick start guide

Schischek

Schischek ExMax Series Quick start guide

Schischek ExMax CY Series User manual

Schischek

Schischek ExMax CY Series User manual

Schischek ExRun Y Series User manual

Schischek

Schischek ExRun Y Series User manual

Schischek ExMax F3 Series User manual

Schischek

Schischek ExMax F3 Series User manual

Popular Controllers manuals by other brands

YASKAWA SGD7S series product manual

YASKAWA

YASKAWA SGD7S series product manual

Charles E1 installation guide

Charles

Charles E1 installation guide

ST Sitronix ST7038 manual

ST

ST Sitronix ST7038 manual

Newport FSM-CD300B user manual

Newport

Newport FSM-CD300B user manual

KIOUR TOUCH LINE RSP4 Start-up

KIOUR

KIOUR TOUCH LINE RSP4 Start-up

American Standard Gold 824 user guide

American Standard

American Standard Gold 824 user guide

Regulus SRS1 T Installation and operation manual

Regulus

Regulus SRS1 T Installation and operation manual

Oldham MX 43 user manual

Oldham

Oldham MX 43 user manual

Megmeet MC5000 Series User quick reference manual

Megmeet

Megmeet MC5000 Series User quick reference manual

phytron MCC-1 manual

phytron

phytron MCC-1 manual

Copley Controls Xenus XSL-230-36 Regeneration Guide

Copley Controls

Copley Controls Xenus XSL-230-36 Regeneration Guide

Newport Electronics i Series Operator's manual

Newport Electronics

Newport Electronics i Series Operator's manual

EasyIO FT Series User reference

EasyIO

EasyIO FT Series User reference

Siemens simatic ET 200MP manual

Siemens

Siemens simatic ET 200MP manual

Siemens Simatic S7-1500R manual

Siemens

Siemens Simatic S7-1500R manual

Geco GH11NB user manual

Geco

Geco GH11NB user manual

Lennox LXTFF01M manual

Lennox

Lennox LXTFF01M manual

Brama S-A1 user guide

Brama

Brama S-A1 user guide