InMax-...-F1 InMax-...-SF1 InMax-...-BF1
Special options ... -CTS ... -VAS
Important information for installation and operation
Extra information (see additional data sheet)
Additional technical information, dimensions, installation intruction, illustration
and failure indication
A. Installation, commissioning, maintenance
All national and international standards, rules and regulations must be complied with.
Apparatus must be installed in accordance with manufacturer instructions. If the equip-
ment is used in a manner not specified by the manufacturer, the safety protection pro-
vided by the equipment may be impaired.
For electrical connection a terminal box is requested (e.g. InBox-...).
Attention: If the actuator is put out of operation all rules and regulations must be
applied. You have to cut the supply voltage before opening a terminal box!
The cable of the actuator must be installed in a fixed position and protected against
mechanical and thermical damage. Connect potential earth. Avoid temperature
transfer from armature to actuator ! Close all openings with min. IP66.
For outdoor installation a protective housing against sun, rain and snow should be
applied to the actuator as well as a constant supply at terminal 1 and 2 for the inte-
grated heater. During commissioning apply a self adjustment drive.
Actuators are maintenance free. An annual inspection is recommended. Actuators
must not be opened by the customer.
B. Manual override
Manual override only if supply voltage is cut. Use delivered socket wrench with slow
motions, usage can be tight.
Attention: Releasing or letting go the Allen key too fast at manual operating actuators
with spring return causes risk of injury!
C. Shaft connection, selection of running time
Actuators are equipped with a direct coupling double square shaft connection of
12 × 12 mm. For round shafts adaptors/clamping connection (accessories, e.g. KB-S)
are available. The housing of the actuator is axially symmetrically built to select
Open-close direction of the spring return function by left-right mounting. Using the
10-position switch different motor running times and spring return running times can be
selected on site in acc. to the actuator type.
D. Temperature trigger ...Pro-TT-...
The actuator ...Max-...-BF1 will work only with the temperature trigger InPro-TT-...
E. Operation with 3 sec. motor running time
Note following:
1. The 3 sec. motor running time mode is only available in switch position 0 and 5 and
at a constant supply voltage applied for a minimum of 1 minute on terminal 1 and 2.
2. The actuator opens at voltage on terminal 3 (resp. closes) and closes at voltage on
terminal 4 (resp. opens) – depending on mounting position of the actuator.
3. The max. duty ratio is 10 % resp. 1 cycle / minute. Between two fully 3 sec. cycles in
the same direction there must be a minimum intermission of 1 minute. Trying to run
the actuator in the same direction in less than the required minimum of 1 minute
the function will be blocked for the rest of the idle period. Later the release for the
next cycle is made automatically by an internal timing relay.
4. Same function is applied on spring return actuators, fail safe operation is regarded
same as a motor running cycle.
5. Trying to use the 1 wire On-off methode in switch position 0 and 5, software
changes the motor running time temporarily and automatically to 15 s/90° to pro-
tect the actuator for overheating due to uncontrolled duty ratio.
F. Spring return
Spring return function works only if the supply voltage for terminal 1 or 2 is cut. In the
event of an electrical interruption, the spring returns to its end position even if supply
voltage is available again during return function. Thereafter operation will continue.
G. Operation at ambient temperatures below −20 °C
All actuators are equipped with a regulated integrated heating device designed for em-
ployments down to −40 °C ambient temperature. The heater will be supplied automati-
cally by connecting the constant voltage supply on the clamps 1 and 2.
1. After mounting the actuator must bei immediately electrically connected.
2. The heater switches on automatically when actuator reaches internally −20 °C. It
heats up the actuator to a proper working temperature, then heater switches off au-
tomatically. Actuator will not run during heating process.
3. The adjustment options are only ensured after this heating up period.
H. Excess temperatures
All actuators are protected against excess temperature. The internal thermostat works
as a maximum limiter and, in the event of failure at incorrect temperatures, shuts off
the actuator irreversible. An upstream connected temperature sensor stops the actua-
tor before reaching its max. temperature. This safety feature is reversible, after cooling
down the actuator is completely functional again. In this case the failure must be elimi-
nated immediately on site!
I. Synchron mode
Do not connect several actuators to one shaft or link mechanically together.
J. Mechanical protection
Actuators must be operated with a minimum external load.
After installing the actuator to the damper/armature a self adjustment drive has to be
performed in order to protect the damper/armature against mechanical overload.
During operation the actuator reduces briefly its speed (motor power) before reaching
the end position for a “gentle” blockade/stop.
K. Routine tests of fire dampers
For periodic inspection of fire dampers cut off the supply line (current of actuator).
The test button at InPro-TT-... is only for test aims of actuator’s function.
Special solutions and accessories
...-CTS Types in aluminium housing with seawater resistant coating,
parts nickel-plated
...-VAS Types in stainless steel housing, parts nickel-plated
Adaptions for dampers and valves on request
InMax-...-S3 Ambient temperature up to +60 °C, 110...240 VAC/ DC, 25 % ED
InPro-TT-... Safety temperature trigger for fire dampers
InBox-... Terminal boxes
MKK-S Mounting bracket for boxes type ...Box-... directly on actuator
InSwitch 2 external aux. switches, adjustable
KB-S Clamp for damper shafts Ø 10...20 mm and □10...16 mm
AR-12-xx Reduction part for 12 mm square connection to 11, 10, 9 or 8 mm shafts
BSH-S Mounting holder for actuators in fire danger areas
Kit-S8 Cable glands nickel-plated