Schischek InMax SF3 Series User manual

EXPLOSIONPROOF
InMax - ... - F3
InMax - ... - SF3
InMax - ... - BF3
InMax - ... - CTM
InMax - ... - VAM
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-F3_en
V05 – 19-Oct-2021
Subject to change!
Compact. Easy installation. Universal. Cost effective. Safe.
Product views and applications
Description Highlights
Fire/air damper Ball valve Throttle valve
Electrical rotary actuators with integrated thermal circuit limiter (optional) for use in safe areas
On-off / 3-pos. control mode, 24…240 VAC/DC, 95° angle of rotation incl. 5° pretension
30 – 50 Nm with safety operation (spring return), optional with auxiliary switches
InMax ¼ turn actuators – size M
►Industrial use
►Universal supply unit from 24…240 VAC/DC
►Motor running times 40– 60– 90–120–150 s/90° adjustable on site
►On-off control with spring return function
►Circuit for direct connection of the ...Pro-TT-... safety temperature trigger (type ...-BF3)
►2 integrated auxiliary switches, switching at 5° and 85° angle of rotation
►30– 50 Nm actuators in the same housing size
►100 % overload protected
►Compact design and small dimension (L × W × H ~ 288 × 149 × 116 mm)
►Direct coupling to the damper shaft with double square connection 16 × 16 mm
►95° angle of rotation inclusive 5° pretension
►Robust aluminium housing (optional with seawater resistant coating)
or in stainless steel
►IP67 protection
►Simple manual override included + preparation for comfortable manual override
►Gear made of stainless steel and sinter metal
►Weight only ~ 9,5 kg
►Integrated heater for ambient temperatures down to −40 °C
►Integrated safety temperature sensor
►Integrated equipment for manual adjustment (push button, lamp, switch)
►Preparation for adaptable and adjustable auxiliary switches type ...Switch
►Wide range of accessories
The InMax actuators are a revolution for safety, fire and shut-off dampers,
VAV systems, ball valves, throttle valves and other motorized applications
for HVAC systems in chemical, pharmaceutical, industrial and offshore/onshore
plants.
IP67 protection, small dimensions, only 9,5 kg weight, universal functions
and technical data, an integrated heater and an optional stainless steel
housing guarantee safe operation even under difficult environmental
conditions. High quality brushless motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times are selectable or
adjustable on site. The integrated universal power supply is self adaptable
to input voltages in the range of 24...240 VAC/DC. The actuators are
100 % overload protected.
...Max-...-F3 actuators are equipped with spring return fail safe function.
Additionally the ...Max-...-SF3 and ...-BF3 actuators are equipped with
2 integrated, potential free auxiliary switches each and ...Max-...-BF3
comes with a tripping circuit for connecting the ...Pro-TT-... safety
temperature trigger. Standard shaft connection is a double square direct
coupling with 16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
Type Torque Supply Motor running time Spring return* Control mode Feedback Wiring diagram
InMax- 30 - F3 30 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 3 s/90° On-off – SB 2.4/2.5
InMax- 50 - F3 50 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 3 s/90° On-off – SB 2.4/2.5
InMax- 30 - SF3 30 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 3 s/90° On-off 2 × aux. switches SB 2.4/2.5 + 3.2
InMax- 50 - SF3 50 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 3 s/90° On-off 2 × aux. switches SB 2.4/2.5 + 3.2
InMax- 30 - BF3 30 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s / 90° ~ 3 s / 90° On-off 2 × aux. switches + tripping circuit SB 2.4/2.5 + 7.4
InMax- 50 - BF3 50 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s / 90° ~ 3 s / 90° On-off 2 × aux. switches + tripping circuit SB 2.4/2.5 + 7.4
InMax- ... - CTM Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
InMax- ... - VAM Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)
*at temperatures below −20 °C, depending on the load, the spring return period can be up to 20 sec. If fast spring return below −20 °C is required, please contact our sales support.
Please note that nominal values are also subject to tolerances.
1 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-F3_en
V05 – 19-Oct-2021
InMax-...-F3 InMax-...-SF3 InMax-...-BF3
Special option ... -CTM ... -VAM
Technical data InMax- 30 - F3 InMax- 50 - F3 InMax- ... - SF3 InMax- ... - BF3
Approbations Special solutions and accessories
...-CTM Types in aluminium housing with seawater resistant coating,
parts nickel-plated
...-VAM Types in stainless steel housing, parts nickel-plated
InBox-... Terminal boxes
MKK-M Mounting bracket for boxes type ...Box-... directly on actuator
InPro-TT-... Safety temperature trigger for fire dampers
InSwitch 2 external aux. switches, adjustable
AR-16-xx Reduction part for 16 mm square connection to 14 or 12 mm shafts
Kit-S8 Cable glands nickel-plated
Adaptions for dampers and valves on request
InMax-...-S3 Ambient temperature up to +60 °C, 110...240 VAC/DC, 25 % ED
Torque motor (min.) 30 Nm 50 Nm 30 resp. 50 Nm 30 resp. 50 Nm
Torque spring (F) min. 30 Nm min. 50 Nm min. 30 resp. 50 Nm min. 30 resp. 50 Nm
Torque blockade In blockade and end positions torques are higher than above specified torques for motor and spring.
Dimensioning of external load Upon spring return the external load should be max. 80 % of torque spring (F), but
min. 8 Nm min. 15 Nm min. 8 resp. 15 Nm min. 8 resp. 15 Nm
Supply voltage / frequency 24...240 VAC/DC ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %
Power consumption max. starting currents see Extra information (in acc. with voltage, I start >> I rated ), approx. 5 W holding power, approx. 16 W for heater
Protection class Class I (grounded)
Angle of rotation and indication 95° incl. ~ 5° pretension, mechanical value indication
Working direction Selectable by left/right mounting to the damper/valve shaft
Motor running times 40 / 60 / 90 / 120 / 150 s/90° selectable on site
Motor Brushless DC motor
Control mode On-off
Spring return (F) spring return upon voltage interruption or opening of line 3, response time up to 1 sec. after voltage interruption
Spring return running time (F) ~ 3 s/90° (at temperatures below -20 °C, depending on the load, the spring return period can be up to 20 s.)
Safety operations at 3 sec. (F) min. 1,000 acc. to construction of damper and ambient. Consider minimum external load!
Tripping circuit ...-BF3 Circuit to connect the InPro-TT-... safety temperature trigger directly to the actuator with M12 quick connection
Aux. switches ...-SF3, ...-BF3 2 integrated auxiliary switches, switching at 5° and 85° angle of rotation, potential free. Grid fuse-protection is recommended!
Umax/ Imax AC = 250 V/5 A; Umin AC/DC = 5 V; After one-time operation with U > 24 V AC/DC or I > 100 mA: Umin AC/DC = 12 V
Umax/ Imax DC = 48 V/1 A; Imin AC/DC = 5 mA; Imin AC/DC = 100 mA
Axle of the actuator Double square 16 × 16 mm, direct coupling, 100 % overload protected
Electrical connection Cable ~ 1 m, wire cross section 0.5 mm², equipotential bonding 4 mm². Connections require a terminal box!
Diameter of cable ~ Ø 7.0 mm ~ Ø 7.0 mm ~ Ø 7.0 + 7.6 mm ~ Ø 9.6 mm
2 cables in version ...-SF3
Cable gland M16 × 1.5 mm
Manual override Use delivered socket wrench, max. 4 Nm
Heater Integrated, controlled heater for ambient temperature down to −40 °C
Housing material Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CTM) or stainless steel housing,
№1.4581 / UNS-J92900 / similar AISI 316Nb (...-VAM)
Dimensions (L × W × H) ~ 288 × 149 × 116 mm, for diagrams see Extra information
Weight ~ 9.5 kg aluminium housing, stainless steel ~ 15 kg
Ambients Storage temperature −40…+70 °C, working temperature −40…+50 °C
Humidity 0...90 % rH, non condensing
Operation mode 80 % ED are permitted (ED = duty cycle)
Maintenance Maintenance free relative to function, maintenance must comply with regional standards, rules and regulations
Wiring diagrams SB 2.4 / 2.5 SB 2.4 / 2.5 SB 2.4 / 2.5 + 3.2 SB 2.4 / 2.5 + 7.4
Scope of delivery Actuator, 4 screws M8 × 140 mm, 4 nuts M8, Allen key for simple manual override
Parameter at delivery 30 Nm, 90 s/90° 50 Nm, 90 s/90° 30 resp. 50 Nm, 90 s/90° 30 resp. 50 Nm, 90 s/90°
CE identification CE
EMC directive 2014/30/EU
Low voltage directive 2014/35/EU
Enclosure protection IP67 in acc. with EN 60529
2 / 4
EXPLOSIONPROOF
InMax- 30 -BF3 ►
InMax- 50 -BF3 ►
30 Nm
50 Nm
▼
40 s/ 90° ►
60 s/ 90° ►
90 s/ 90° ►
120 s /90° ►
150 s /90° ►
00
01
02
03
04
05
06
07
08
09
InBox
a
a
a
+
~
+
~
+
~
+
~
−
~
−
~
−
~
−
~
PE
PE
PE
PE
1
1
1
1
2
2
2
2
3
3
3
3
PA
PA
PA PA
4
1
7
4
5
2
6
3
8
5
9
6
< 5°
< 5°
> 85°
> 85°
1 2
°C
InPro-TT
U < 90 V AC/DC 2 AT 10 AT
U > 90 V AC/DC 5 AT 10 AT
U < 90 V AC/DC 2 AT 10 AT
U > 90 V AC/DC 5 AT 10 AT
S
T
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-F3_en
V05 – 19-Oct-2021
InMax-...-F3 InMax-...-SF3 InMax-...-BF3
Special option ... -CTM ... -VAM
Electrical connection Parameters, adjustments and failure indication
Parameter selection
Functions, adjustments and parameters
Type
Running times Position of switch (S)
Torques
Example:
InMax-30-BF
Requested parameter:
Torque 30 Nm
Motor running time 90 s/ 90°
Result:
Switch position 02
Installation
supply *
24...240 VAC/DC ± 10 %
* electrical wiring see diagrams
All actuators are equipped with a universal supply unit working at a voltage range from
24...240 VAC/DC. The supply unit is self adjusting to the connected voltage!
The safety operation of the spring return function works if the supply voltage is cut or line 3 opened.
For electrical connection a terminal box is required (e.g. InBox).
An over-current protection fuse < 10 A has to be provided by installer.
Note: The initial current is appr. 2 A for 1 second.
Integrated auxiliary switches signal the rotation angle’s position. Umin and Imin change once
the switches were operated with higher voltage or current.
Attention
During commissioning apply a self adjustment drive.
Regard duty cycle at motor running times!
Never use spring return actuators without external load.
Auxiliary switches *
see Technical data
On-off SB 2.4 On-off (1 wire) SB 2.5
Wiring of integrated auxiliary switches SB 3.2
On-off – spring return + tripping circuit SB 7.4
Tripping circuit for In-
Pro-TT-... safety
temperature trigger
Test
button
Attention!
At 1-wire control
mode the heater
does not work in
case of open contact.
24...240 VAC/DC
24...240 VAC/DC
24...240 VAC/DC
24...240 VAC/DC Integrated auxiliary switches,
Grid fuse-protection recommended.
min. max.
Integrated auxiliary switches,
Grid fuse-protection recommended.
min. max.
A) Self adjustment of angle of rotation
ATTENTION: To adjust the angle of rotation connect only wire 1 and 2.
Do not connect wire 3.
Apply supply voltage to wire 1 and 2. Turn switch (S) to position 02. Press
button (T) for a minimum of 3 seconds. The actuator drives to the first end posi-
tion, detects the blocking position and performs a spring return to the starting posi-
tion. The LED flashes GREEN during adjustment. After that disconnect from the
mains and connect wire 3.
The adjustment takes about 93 seconds (90 sec. “On”, 3 sec. “Off”).
B) Selecting motor running time
Adjust parameters only if actuator is in idle state or without applied potential.
Turn switch (S) to the position required for the intended operation acc. to table
above. The selected parameters will be carried out at the actuator’s next opera-
tion.
C) Function of the InPro-TT-... in the tripping circuit
When the ...Pro-TT’s tripping circuit is opened the actuator runs into its end posi-
tion with spring return.
D) Additional information for control in On-off operation
a closed = actuator opens
a open = spring return
The rotation direction (clockwise/counter clockwise) depends on left/right
mounting of the actuator to the damper.
Switch – Push button – Lamp
for adjustment
(behind the blanking plug)
10-position switch (S)
3-colour LED
Push button (T)
3 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-F3_en
V05 – 19-Oct-2021
InMax-...-F3 InMax-...-SF3 InMax-...-BF3
Special option ... -CTM ... -VAM
Important information for installation and operation
Accessory InBox – terminal boxAccessory InSwitch – auxiliary switch
Extra information (see additional data sheet)
Additional technical information, dimensions, installation instruction, illustration
and failure indication
A. Installation, commissioning, maintenance
All national and international standards, rules and regulations must be complied with. Apparatus
must be installed in accordance with manufacturer instructions. If the equipment is used in a manner
not specified by the manufacturer, the safety protection provided by the equipment may be impaired.
For electrical connection a terminal box is required (e.g. InBox-...).
Attention: If the actuator is put out of operation all rules and regulations must be applied.
You have to cut the supply voltage before opening the terminal box!
The cables of the actuator must be installed in a fixed position and protected
against mechanical and thermical damage. Connect potential earth. Avoid tem-
perature transfer from armature to actuator! Close all openings with min. IP67.
For outdoor installation a protective weather shield against sun, rain and snow
should be applied to the actuator as well as a constant supply at terminal 1 and
2 for the integrated heater. During commissioning apply a self adjustment drive.
Actuators are maintenance free. An annual inspection is recommended. Actuators must
not be opened by the customer.
B. Manual override
Manual override only if supply voltage is cut. Use delivered socket wrench with slow
motions, usage can be tight.
Attention: Releasing or letting go the Allen key too fast at manual operating actuators
with spring return causes risk of injury!
C. Shaft connection, selection of running time
Actuators are equipped with a direct coupling double square shaft connection of 16 × 16 mm.
The housing of the actuator is axially symmetrically built to select Open-close direction of
the spring return function by left-right mounting. Using the 10-position switch different mo-
tor running times and spring return running times can be selected on site in acc. to the actu-
ator type.
D. Temperature trigger ...Pro-TT-...
The actuator ...Max-...-BF3 will work only with the temperature trigger InPro-TT-...
E. Spring return
Spring return function works only if the supply voltage for terminal 1 or 2 is cut. In the
event of an electrical interruption, the spring returns to its end position even if supply
voltage is available again during return function. Thereafter operation will continue.
F. Operation at ambient temperatures below −20 °C
All actuators are equipped with a regulated integrated heating device designed for
employments down to −40 °C ambient temperature. The heater will be supplied automatically
by connecting the constant voltage supply on the clamps 1 and 2.
1. After mounting the actuator must bei immediately electrically connected.
2. The heater switches on automatically when actuator reaches internally −20 °C. It
heats up the actuator to a proper working temperature, then heater switches off au-
tomatically. Actuator will not run during heating process.
3. The adjustment options are only ensured after this heating up period.
G. Excess temperatures
All actuators are protected against excess temperature. The internal thermostat works
as a maximum limiter and, in the event of failure at incorrect temperatures, shuts off the
actuator irreversible. An upstream connected temperature sensor stops the actuator
before reaching its max. temperature. This safety feature is reversible, after cooling down
the actuator is completely functional again. In this case the failure must be eliminated
immediately on site!
H. Synchron mode
Do not connect several actuators to one shaft or link mechanically together.
I. Mechanical protection
Actuators must be operated with a minimum external load.
After installing the actuator to the damper/armature a self adjustment drive has to be
performed in order to protect the damper/armature against mechanical overload.
During operation the actuator reduces briefly its speed (motor power) before reaching
the end position for a “gentle” blockade/stop.
J. Routine tests of fire dampers
For periodic inspection of fire dampers cut off the supply line (current of actuator).
The test button at InPro-TT-... is only for test aims of actuator’s function.
For an end or inclined position indication it is possible to
retrofit external, adjustable auxiliary switches type
InSwitch.
The ...Switch is mounted directly to the actuator. The
switches deliver a potential free output and can be adjusted
separately. They are connected by cable.
For electrical connection of the ...Max actuator a terminal
box is required.
To adapt the ...Box directly to the actuator housing a mounting
bracket is required.
InBox- 3P for ...Max-...-F3
InBox- Y/S for ...Max-...-SF3
InBox- BF for ...Max-...-BF3
4 / 4

This manual suits for next models

10

Other Schischek Controllers manuals

Schischek ExMax CTM Series User manual

Schischek

Schischek ExMax CTM Series User manual

Schischek InMax CTM Series User manual

Schischek

Schischek InMax CTM Series User manual

Schischek RedMax User manual

Schischek

Schischek RedMax User manual

Schischek ExMax CY Series User manual

Schischek

Schischek ExMax CY Series User manual

Schischek InMax-100 User manual

Schischek

Schischek InMax-100 User manual

Schischek InMax Series User manual

Schischek

Schischek InMax Series User manual

Schischek ExMax CTS Series User manual

Schischek

Schischek ExMax CTS Series User manual

Schischek RedMax BF Series User manual

Schischek

Schischek RedMax BF Series User manual

Schischek RedMax-30-BF User manual

Schischek

Schischek RedMax-30-BF User manual

Schischek ExMax Series Quick start guide

Schischek

Schischek ExMax Series Quick start guide

Schischek RedMax F Series User manual

Schischek

Schischek RedMax F Series User manual

Schischek RedMax BF-VA Series User manual

Schischek

Schischek RedMax BF-VA Series User manual

Schischek ExMax BF User manual

Schischek

Schischek ExMax BF User manual

Schischek ExMax F3 Series User manual

Schischek

Schischek ExMax F3 Series User manual

Schischek RedMax S Series User manual

Schischek

Schischek RedMax S Series User manual

Schischek ExMax User manual

Schischek

Schischek ExMax User manual

Schischek InMax-8-F1 User manual

Schischek

Schischek InMax-8-F1 User manual

Schischek RedMax CTM Series User manual

Schischek

Schischek RedMax CTM Series User manual

Schischek RedMax-8-F1 User manual

Schischek

Schischek RedMax-8-F1 User manual

Schischek InMax CTM Series User manual

Schischek

Schischek InMax CTM Series User manual

Schischek EXV-8 Series User manual

Schischek

Schischek EXV-8 Series User manual

Schischek Redmax Series Quick start guide

Schischek

Schischek Redmax Series Quick start guide

Schischek ExMax-50.75 Owner's manual

Schischek

Schischek ExMax-50.75 Owner's manual

Schischek ExRun Y Series User manual

Schischek

Schischek ExRun Y Series User manual

Popular Controllers manuals by other brands

Linak Homeline LA10 user manual

Linak

Linak Homeline LA10 user manual

Uponor Smatrix Wave PLUS quick guide

Uponor

Uponor Smatrix Wave PLUS quick guide

Aruba 200 Series installation guide

Aruba

Aruba 200 Series installation guide

Extron electronics MLC 226 IP Series installation manual

Extron electronics

Extron electronics MLC 226 IP Series installation manual

Zetlight ZN1001 Quick start manual

Zetlight

Zetlight ZN1001 Quick start manual

WIKA CPC3000 operating instructions

WIKA

WIKA CPC3000 operating instructions

Zamel exta SRM-11 instruction manual

Zamel

Zamel exta SRM-11 instruction manual

Allen-Bradley Bulletin 900-TC Series Selection guide

Allen-Bradley

Allen-Bradley Bulletin 900-TC Series Selection guide

JB Systems LED 1CH DIM-CONTROL Operation manual

JB Systems

JB Systems LED 1CH DIM-CONTROL Operation manual

Baker Hughes Masoneilan 525 Seris instruction manual

Baker Hughes

Baker Hughes Masoneilan 525 Seris instruction manual

HORNER XLE Firmware update manual

HORNER

HORNER XLE Firmware update manual

Endress+Hauser Liquiline CM442 operating instructions

Endress+Hauser

Endress+Hauser Liquiline CM442 operating instructions

EUCHIPS DALI-P03 user manual

EUCHIPS

EUCHIPS DALI-P03 user manual

Data Technology 5150X installation guide

Data Technology

Data Technology 5150X installation guide

dooch Q-Drive NQ-0400-S user guide

dooch

dooch Q-Drive NQ-0400-S user guide

Tyro Fornax Basic manual

Tyro

Tyro Fornax Basic manual

Johnson Controls VA-7700 Series manual

Johnson Controls

Johnson Controls VA-7700 Series manual

Linak TECHLINE LA36 Connection diagram

Linak

Linak TECHLINE LA36 Connection diagram

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.