Schischek ExMax CTM Series User manual

EXPLOSIONPROOF
ExMax - ... - Y
ExMax - ... - YF
ExMax - ... - CTM
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
ExMax-M-Y_en
V01 – 20-Apr-2016
Subject to change!
Compact. Easy installation. Universal. Cost effective. Safe.
Product views and applications
Description Highlights
Safety damper Ball valve Throttle valve
Electrical, explosion proof rotary actuators
3-pos. / 0...10 VDC / 4...20 mA control mode, with feedback, 24...240 VAC/DC, 95° angle of rotation
50/75 Nm, 100 Nm without and 30 Nm, 50 Nm with safety operation (spring return)
ATEX tested in acc. with directive 2014/34/EU for zone 1, 2, 21, 22
Type Torque Supply Motor running time Spring return Control mode Feedback Wiring diagram
ExMax- 50.75 - Y 50 / 75 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° – 3-pos., 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA SB 4.0+4.1
ExMax-100 - Y 100 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° – 3-pos., 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA SB 4.0+4.1
ExMax- 30 - YF 30 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 20 s/90° 3-pos., 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA SB 4.0+4.1
ExMax- 50 - YF 50 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 20 s/90° 3-pos., 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA SB 4.0+4.1
ExMax- ... - CTM Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
ExMax ¼ turn actuators – size M
►For all types of gas, mists, vapours and dust for use in zone 1, 2, 21 and 22
►Universal supply unit from 24…240 VAC/DC
►5 different motor running times 40–60–90 –120–150 s/90°, adjustable on site
►2 different spring return running times ~ 20 s/90°, selectable on site
►3-pos. and 0...10 VDC, 4...20 mA control mode with or without spring return function
► Feedback signals 0...10 VDC and 4...20 mA
► Reverse function
►30– 50–75–100 Nm actuators in the same housing size
►100 % overload protected
►Compact design and small dimension (L × W × H = 288 × 149 × 116 mm)
►Direct coupling to the damper shaft with double square connection 16 × 16 mm
►95° angle of rotation inclusive 5° pretension
►Robust aluminium housing (optional with seawater resistant coating)
►IP66 protection
►Simple manual override included + preparation for comfortable manual override
►Gear made of stainless steel and sinter metal
►Weight only ~ 9,5 kg
►Integral heater for ambient temperatures down to −40 °C
►Integral safety temperature sensor
►Integral equipment for manual adjustment (push button, lamp, switch)
►Preparation for adaptable and adjustable auxiliary switches type ...Switch
►Wide range of accessories
The ExMax actuators are a revolution for safety, control and shut-off
dampers, VAV systems, ball valves, throttle valves and other motorized
applications for HVAC systems in chemical, pharmaceutical, industrial
and offshore/onshore plants, for use in Ex-areas zone 1, 2 (gas) and
zone 21, 22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimensions,
only 9,5 kg weight, universal functions and technical data, an integrated
heater and an optional stainless steel housing guarantee safe operation
even under difficult environmental conditions. High quality brushless
motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times and torques as well as
spring return times, according to the actuator type, are selectable or
adjustable on site. The integrated universal power supply is self adaptable
to input voltages in the range of 24...240 VAC/DC. Furthermore it is
possible to perform control signal inverting and compulsion control by
certain connections. The actuators are 100 % overload protected.
...Max-...-YF actuators are equipped with spring return fail safe function.
Standard shaft connection is a double square direct coupling with
16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
1 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
ExMax-M-Y_en
V01 – 20-Apr-2016
ExMax-...-Y ExMax-...-YF
Special option ... -CTM
Technical data ExMax- 50.75 -Y ExMax- 100 -Y ExMax- 30 -YF ExMax- 50 -YF
Approbations Special solutions and accessories
...-CTM Types in aluminium housing with seawater resistant coating,
parts nickel-plated
VAMHCasing in VA for ...Max actuators size M
ExBox-Y/S... Ex-e terminal boxes for zone 1, 2, 21, 22
MKK-M Mounting bracket for boxes type ...Box-... directly on actuator
ExSwitch 2 external aux. switches, adjustable for zone 1, 2, 21, 22
HV-MK Comfortable manual override for ...Max actuators size M
AR-16-xx Reduction part for 16 mm square connection to 14 or 12 mm shafts
Kit-S8 Cable glands nickel-plated
Adaptions for dampers and valves on request
Torque motor (min.) 50 / 75 Nm selectable on site 100 Nm 30 Nm 50 Nm
Torque spring (F) without F without F min. 30 Nm min. 50 Nm
Dimension of external torque Above mentioned torques are min. torques in blocked position, external torque should be max. 80 % of max. actuator torque but min. 10 Nm
Supply voltage / frequency 24...240 VAC/DC, ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %
Power consumption max. starting currents see Extra information (in acc. with voltage, I start >> I rated ), approx. 5 W holding power, approx. 16 W for heater
Protection class Class I (grounded)
Angle of rotation and indication 95° incl. ~ 5° pretension, mechanical value indication
Working direction Selectable by left/right mounting to the damper/valve shaft
Motor running times 40 / 60 / 90 / 120 / 150 s/90° selectable on site
Motor Brushless DC motor
Spring return (F) without F without F spring return in the event of loss of power
Spring return running time (F) without F without F spring return ~ 20 s/90°
Safety operations min. 10,000 in acc. with construction of damper and ambient
Response time spring return up to 1 sec. after power failure
Control mode Y 3-pos., 0…10 VDC, 4…20 mA in acc. with wiring, selectable on site. Galvanic separation between supply and Y-signal
Feedback signal U 0…10 VDC, 4…20 mA in acc. with wiring, selectable on site, both signals are available at the same time
Resistance of Y and U signals Input signal: YU0...10 VDC at 10 kΩ, YI4...20 mA at 100 Ω. Feedback signal: UU 0...10 VDC at 2.000...∞ Ω, UI4...20 mA at 0...800 Ω
Reverse function Bridge between wiring 3 and 4 (signal wise) gets a reverse function of Y and U
Compulsion control In modulation mode an On-off compulsion control can be performed by external connection/wiring independently from the modulating signal
Adjustment of Y and U In case of external mechanical limitation of the angle of rotation, it is possible to perform an adjustment drive started by touching the button
Axle of the actuator Double square 16 × 16 mm, direct coupling, 100 % overload protected
Electrical connection 2 cable glands each ~ 1 m, wire cross section 0.5 mm², equipotential bonding 4 mm².
Connections in hazardous areas require an Ex-e terminal box!
Diameter of cable ~ Ø 7.1 + 7.4 mm ~ Ø 7.1 + 7.4 mm ~ Ø 7.1 + 7.4 mm ~ Ø 7.1 + 7.4 mm
Cable gland M16 × 1.5 mm
Manual override Use delivered socket wrench, max. 4 Nm
Integral heater Integral, controlled heater for ambient temperature down to −40 °C
Housing material Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CTM)
Dimensions (L × W × H) 288 × 149 × 116 mm, for diagrams see Extra information
Weight ~ 9,5 kg
Ambients Storage temperature −40…+70 °C, working temperature −40…+40 °C at T6 and −40…+50 °C at T5
Humidity 0...90 % rH, non condensing
Operation mode 100 % of ED are permitted (ED = duty cycle)
Accuracy electrically ~ 100 steps
Self adjustment If you select 40 sec. or 60 sec. mode for motor running time or rotation angle < 90° you need to start the self adjustment mode
Maintenance Maintenance free relative to function, maintenance must comply with regional standards, rules and regulations
Wiring diagrams SB 4.0 / 4.1 SB 4.0 / 4.1 SB 4.0 / 4.1 SB 4.0 / 4.1
Scope of delivery Actuator with 2 × 1 m cable, 4 screws M8 × 140 mm, 4 nuts M8, Allen key for simple manual override
Parameter at delivery 50 Nm, 90 s/90° 100 Nm, 90 s/90° 30 Nm, 90 s/90° 50 Nm, 90 s/90°
ATEX directive 2014/34/EU
EC type-approved PTB 04 ATEX 1028 X
IECEx certified IECEx PTB 07.0057X
Approval for gas II 2 (1) G Ex d [ia] IIC T6, T5
Approval for dust II 2 (1) D Ex tD [iaD] A21 IP66 T80, T95°C
CE identification CE №0158
EMC directive 2014/30/EU
Low voltage directive 2014/35/EU
Enclosure protection IP66 in acc. with EN 60529
2 / 4
EXPLOSIONPROOF
! !
ExMax- 50.75-Y ►
ExMax- 100-Y ►
ExMax- 30-YF ►
ExMax- 50-YF ►
50 N
100 N
30 N
50 N
▼
75 N
▼
40 s / 90° ►
60 s / 90° ►
90 s / 90° ►
120 s/ 90° ►
150 s/ 90° ►
00
01
02
03
04
05
06
07
08
09
S
T
ExBox
a b
+
~
+
~
−
~
−
~
PE
PE
1
1
2
2
3
3
4
4
6
6
1
1
2
2
3
3
5
5
4
4
PA
PA
YmA
YmA
YVDC
YVDC
T
VDC/mA
T
VDC/mA
UmA
UmA
UVDC
UVDC
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
ExMax-M-Y_en
V01 – 20-Apr-2016
ExMax-...-Y ExMax-...-YF
Special option ... -CTM
Electrical connection Parameters, adjustments and failure indication
Parameter selection
Functions, adjustments and parameters
Type
Running times Position of switch (S)
Torques
Example:
ExMax-50.75-Y
Requested parameter:
Torque 75 N
Motor running time 90 s/90°
Result:
Switch position 07
All actuators are equipped with a universal supply unit working at a voltage range from
24...240 VAC/DC. The supply unit is self adjusting to the connected voltage!
The safety operation of the spring return function works if the supply voltage is cut.
For electrical connection inside hazardous areas an Ex-e terminal box, certificated in acc.
with ATEX is required (e.g. ExBox).
An over-current protection fuse < 10 A has to be provided by installer.
Note: the initial current is appr. 2 A for 1 second.
Installation
supply *
24...240 VAC/DC ± 10 %
* electrical wiring see diagrams
A) Self adjustment of angle of rotation:
Switch (S) into position 02 (low torque) or 07 (high torque), then push button (T) for
minimum 3 seconds. The actuator will drive into both end positions to be adjusted.
LED indicates GREEN.
Adjustment time needs approx. 180 sec. (90 sec. “On”, 90 sec. “Off”). After that,
switch (S) into the position acc. with your required torque and running time.
B) Selection of running time and torque:
Put switch (S) into the correct selected position in acc. to above table.
The selected parameter will work at next operation of the actuator.
Adjustment can be done even without supply voltage. If supply voltage
is available turn switch only if actuator is not running.
C) Changing modulating mode into 3-pos. operation mode with feedback:
Push button (T) 3 times.
LED changes from permanent GREEN to permanent YELLOW.
Push button within following limits:
▪Push for min. 0,2 sec. each
▪Complete pushing (3 ×) within 5 sec.
LED – Status:
▪GREEN (permanent) – Supply available, actuator is active in modulating mode
▪YELLOW (permanent) – Supply available, actuator is active in 3-pos. (+ U) mode
D) Changing 3-pos. mode with feedback into modulating operation mode:
Push button (T) 3 ×. LED changes from permanent YELLOW to permanent GREEN.
E) Additional information for 3-pos. operation:
a closed, b open = direction I
b closed, a open = direction II
a and b closed = motor doesn’t work
a and b opened = motor doesn’t work
The rotation direction (I and II) depends on left/right mounting of the actuator to the
damper/valve. You can change direction of the motor by changing electrical wiring
of terminal 3 and 4. In this case the Y-inputs are without function.
F) Reverse function:
Bridge between signal wise wiring 3–4 (cable B) gets a reverse function of input Y
and feedback signals U.
10-position switch (S)
Push button (T)
3-colour LED
Switch – Push button – Lamp for adjustment (behind the blanking plug)
Modulating / 3-pos. – with / without spring return SB 4.0
Modulating – with / without spring return (no enforcement) SB 4.1
Function and enforcement control of switch a and b in modulating mode:
▪a closed – Forced-ON (OFF) in acc. to left/ right mounting of actuator
▪b closed – Forced-OFF (ON) in acc. to left/ right mounting of actuator
Reverse function:
Bridge 3– 4 reverses the
input and output signals
Reverse function:
Bridge 3– 4 reverses the
input and output signals
Self adjustment:
To adjust the signal input / output to the angle of
rotation of the damper/ valve the button (T) must
be pushed for a minimum of 3 sec.
Self adjustment:
To adjust the signal input / output to the angle of
rotation of the damper/ valve the button (T) must
be pushed for a minimum of 3 sec.
24...240 VAC / DC
24...240 VAC / DC
Attention
During commissioning apply a self adjustment drive.
Regard duty cycle at motor running times!
Never use spring return actuators without external load.
Ex area –
zone 1, 2, 21, 22 Safe area
3 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
ExMax-M-Y_en
V01 – 20-Apr-2016
ExMax-...-Y ExMax-...-YF
Special option ... -CTM
Important information for installation and operation
Extra information (see additional data sheet)
Additional technical information, dimensions, installation instruction, illustration
and failure indication
A. Installation, commissioning, maintenance
All national and international standards, rules and regulations for hazardous Ex-areas
must be complied. Certified apparatus must be installed in accordance with manufacturer
instructions. If the equipment is used in a manner not specified by the manufacturer, the
safety protection provided by the equipment may be impaired. For electrical installations
design, selection and erection, EN/IEC 60079-14 can be used.
For electrical connection an Ex-e terminal box is required (e.g. ExBox-...).
Attention: If the actuator is put out of operation all Ex rules and regulationsmust be
applied. You have to cut the supply voltage before opening the terminal box!
The cablesof the actuator must be installed in a fixed position and protected against
mechanical and thermical damage. Connect potential earth. Avoid temperature transfer
from armature to actuator! Close all openings with min. IP66.
For outdoor installation a protective weather shield against sun, rain and snow should be
applied to the actuator as well as a constant supply at terminal 1 and 2 for the integral
heater.
Actuators are maintenance free. An annual inspection is recommended. For electrical
installations inspection and maintenance, EN/IEC 60079-17 can be used. Ex-actuators
must not be opened by the customer.
B. Manual override
Manual override only if supply voltage is cut. Use delivered socket wrench with slow
motions, usage can be tight.
Attention: Releasing or letting go the Allen key too fast at manual operating actuators
with spring return causes risk of injury!
C. Shaft connection, selection of running time
Actuators are equipped with a direct coupling double square shaft connection of 16 × 16 mm.
The housing of the actuator is axially symmetrically built to select Open-close direction
of the spring return function by left-right mounting. Using the 10-position switch different
motor running times and spring return running times can be selected on site in acc. to
the actuator type.
D. 3-position control mode
...Max actuators are in the best way suitable for the 3-pos. operation. To protect such
elements as gears and mounting elements against harmful influences like minimum
pulse time, ...Max actuators are protected via internal electronics. It ignores impulses
< 0,5 s, the cyclic duration must be min. 0,5 s. At changing direction the pause is 1 s.
E. Spring return
Spring return function works only if the supply voltage for terminal 1 or 2 is cut. In the
event of an electrical interruption, the spring returns to its end position even if supply
voltage is available again during return function. Thereafter operation will continue.
F. Operation at ambient temperatures below −20 °C
All actuators are equipped with a regulated integrated heating device designed for
employments down to −40 °C ambient temperature. The heater will be supplied automatically
by connecting the constant voltage supply on the clamps 1 and 2.
1. After mounting the actuator must bei immediately electrically connected.
2. The heater switches on automatically when actuator reaches internally −20 °C. It
heats up the actuator to a proper working temperature, then heater switches off
automatically. Actuator will not run during heating process.
3. The adjustment options are only ensured after this heating up period.
G. Excess temperatures
In acc. to the ATEX rules and regulations Ex actuators must be protected against excess
temperature. The internal thermostat works as a maximum limiter and, in the event of
failure at incorrect temperatures, shuts off the actuator irreversible. An upstream connected
temperature sensor stops the actuator before reaching its max. temperature. This safety
feature is reversible, after cooling down the actuator is completely functional again. In
this case the failure must be eliminated immediately on site!
H. Synchron mode
Do not connect several actuators to one shaft or link mechanically together.
I. Mechanical protection
The actuator must be operated with an outside load of at least 10 Nm.
After installing the actuator to the damper/armature an automatic alignment has to be ac-
complished in order to obtain a “gentle” blockade/stop. This function protects the
damper/armature by reducing the end position’s/blockade speed in order to avoid
mechanical overload. The actuator alignes specifically once with 90 s/90° onto each
position and recognizes the blockade position in order to reduce the motor performance
during operation briefly before reaching the end/blockade position.
J. Intrinsically safe circuits
The actuator itself has a flameproof enclosure. The supply of the push button (adjustment
drive), the 10-position switch (adjustment of torque and running time) and the LED
indicator is performed intrinsically safe!
Accessory ExBox – adaptable Ex-e terminal boxAccessory ExSwitch – adaptable Ex-d auxiliary switch
For electrical connection of ...Max actuators inside the
hazardous area an Ex-e terminal box is required.
ExBoxes are appropriate terminal boxes and placed at
the disposal. To adapt the ...Box directly to the actuator
housing a mounting bracket type MKK-M is required.
ExBox- Y/S for ...Max-...-Y and ...-YF with integral
auxiliary switches
For an end or inclined position indication it is possible to
retrofit external, adjustable, explosion proof auxiliary switches
type ExSwitch. The switch housing is mounted directly to
the actuator and the switches are linked to the actuator’s
square connector. The switches deliver a potential free
output and can be adjusted separately. They are connected
by the included cable tail.
4 / 4

Other manuals for ExMax CTM Series

1

This manual suits for next models

4

Other Schischek Controllers manuals

Schischek EXV-8 Series User manual

Schischek

Schischek EXV-8 Series User manual

Schischek ExMax CTM Series User manual

Schischek

Schischek ExMax CTM Series User manual

Schischek InMax Series User manual

Schischek

Schischek InMax Series User manual

Schischek ExReg-V CT Series User manual

Schischek

Schischek ExReg-V CT Series User manual

Schischek RedMax User manual

Schischek

Schischek RedMax User manual

Schischek RedMax F1 Series User manual

Schischek

Schischek RedMax F1 Series User manual

Schischek InMax SF3 Series User manual

Schischek

Schischek InMax SF3 Series User manual

Schischek Redmax Series Quick start guide

Schischek

Schischek Redmax Series Quick start guide

Schischek RedMax-Y Series User manual

Schischek

Schischek RedMax-Y Series User manual

Schischek InMax-8-F1 User manual

Schischek

Schischek InMax-8-F1 User manual

Schischek RedMax F Series User manual

Schischek

Schischek RedMax F Series User manual

Schischek InMax CTM Series User manual

Schischek

Schischek InMax CTM Series User manual

Schischek RedMax BF Series User manual

Schischek

Schischek RedMax BF Series User manual

Schischek ExMax User manual

Schischek

Schischek ExMax User manual

Schischek ExMax User manual

Schischek

Schischek ExMax User manual

Schischek ExMax Series User manual

Schischek

Schischek ExMax Series User manual

Schischek RedMax CTM Series User manual

Schischek

Schischek RedMax CTM Series User manual

Schischek RedMax-30-BF User manual

Schischek

Schischek RedMax-30-BF User manual

Schischek InMax-8-F1 User manual

Schischek

Schischek InMax-8-F1 User manual

Schischek ExMax BF User manual

Schischek

Schischek ExMax BF User manual

Schischek RedMax-8-F1 User manual

Schischek

Schischek RedMax-8-F1 User manual

Schischek ExMax-50.75 Owner's manual

Schischek

Schischek ExMax-50.75 Owner's manual

Schischek InMax-100 User manual

Schischek

Schischek InMax-100 User manual

Schischek ExMax CY Series User manual

Schischek

Schischek ExMax CY Series User manual

Popular Controllers manuals by other brands

Samson 430 Series Mounting and operating instructions

Samson

Samson 430 Series Mounting and operating instructions

SEDEA 531610-2210 installation instructions

SEDEA

SEDEA 531610-2210 installation instructions

MAXIMATOR RM350 operating instructions

MAXIMATOR

MAXIMATOR RM350 operating instructions

sauter NRT405F902 Instruction

sauter

sauter NRT405F902 Instruction

FZONE STUDIO FZ-1011 user manual

FZONE STUDIO

FZONE STUDIO FZ-1011 user manual

Rain TBD user manual

Rain

Rain TBD user manual

Lynxspring JENEsys Edge 534 installation guide

Lynxspring

Lynxspring JENEsys Edge 534 installation guide

Leadtek Turbidity manual

Leadtek

Leadtek Turbidity manual

Denali CANsmart KTM Series instructions

Denali

Denali CANsmart KTM Series instructions

Controls MVP-A7302 product manual

Controls

Controls MVP-A7302 product manual

Siemens PS 307 6ES7307-1BA01-0AA0 operating instructions

Siemens

Siemens PS 307 6ES7307-1BA01-0AA0 operating instructions

Belimo PKR Series QUICK MOUNT VISUAL INSTRUCTION MANUAL

Belimo

Belimo PKR Series QUICK MOUNT VISUAL INSTRUCTION MANUAL

Pyle Hydra PLMR440PA owner's manual

Pyle

Pyle Hydra PLMR440PA owner's manual

Danfoss 102 User instructions

Danfoss

Danfoss 102 User instructions

Azbil KFDB user manual

Azbil

Azbil KFDB user manual

Linear Technology LTC2874 Demo Manual

Linear Technology

Linear Technology LTC2874 Demo Manual

Sony HKSP-R80 Operation guide

Sony

Sony HKSP-R80 Operation guide

Kelly KBL24101 user manual

Kelly

Kelly KBL24101 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.