2The actuation of the interlock must be compared externally with the OSSD release. If a shut-down now occurs due to an
unintentional unlocking this is detected by an external diagnostic.
2The safety analysis of the guard locking function refers to the component solenoid interlock AZM as part of the complete
system.
On the customer side further measures such as safe actuation and safe cable installation to prevent faults are to be
implemented.
In the event of a fault resulting in the unlocking of the guard locking, this is detected by the solenoid interlock and the
safety gates Y1/Y2 switch off. When such a fault occurs the protection equipment may open immediately, just once, before
the safe condition of the machine is reached. The system reaction of category 2 allows that a fault can occur between tests
causing the loss of the safety function which is detected by the test.
FCC/IC - Note
This device complies with Part 15 of the FCC Rules and contains licence-exempt transmitter/receivers that are
compliant with ISED (Innovation, Science and Economic Development) Canada licence-exempt RSS standard(s).
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference signals, and
(2) This device must be able to tolerate interference signals. These also include interference signals that could
cause the device to function improperly.
This device complies with the nerve stimulation limits (ISED SPR-002) when operated at a minimum distance of 100
mm. Changes or modifications not expressly approved by K.A. Schmersal GmbH & Co. KG could void the user's
authority to operate the equipment.
The licence-free transmitter/receiver contained in this device satisfies the requirements of the "Radio Standards
Specification" of the Innovation, Science and Economic Development Canada (ISED) authority that apply to licence-
free radio equipment. Operation is permissible under the following two conditions:
(1) The device must not create disturbances.
(2) The device must tolerate received radio frequency interference, even if this could impair its functionality.
This device complies with the nerve stimulation limits (ISED CNR-102) when operated at a minimum distance of 100
mm.
In the event of changes or modifications that have not been expressly approved by K.A. Schmersal GmbH & Co. KG,
the user's authorisation to use the device may become ineffective.
20941-22-1451
Este equipamento nao tem direito àprotecao contra interferência
prejudicial e nao pode causar interferencia em sistemas
devidamente autorizados.
Para maiores informacores consultar: www.gov.br/anatel
3 Mounting
3.1 General mounting instructions
2Please observe the remarks of the standards EN ISO 12100, EN ISO 14119 and EN ISO 14120.
Die Gebrauchslage ist beliebig.
Die Sicherheitszuhaltung darf nicht als Anschlag benutzt werden.
Die Transportsicherung ist zu entfernen.
10-24