Operating instructions
Safety-monitoring module SRB 324ST/R V.3
EN
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages resulting
from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modications to the device are strictly forbidden;
the manufacturer shall accept no liability for damages resulting from
such invasive work, arbitrary repairs, conversions and/or modications
to the device.
2 Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
SRB 324ST/R V.3
Only if the information described in this operating instructions
manual are realised correctly, the safety function and therefore
the compliance with the Machinery Directive is maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specications apply accordingly, provided that they correspond to
the standard version.
2.3 Destination and use
The safety-monitoring modules for integration in safety circuits are
designed for tting in control cabinets. They are used for the safe
evaluation of the signals of positive break position switches for safety
functions or magnetic safety sensors on sliding, hinged and removable
safety guards as well as emergency stop control devices and AOPD's
(safety light barriers).
The safety function is dened as the opening of the enabling circuits
13-14, 23-24 and 33-34 and the delayed opening of the enabling
circuits 57-58 and 67-68 when the inputs S11-S12 and/or S21-S22
are opened. The safety-relevant current paths with the output contacts
13-14, 23-24 and 33-34 meet the following requirements under
observation of a B10d value assessment (also refer to "Requirements
to DIN EN ISO 13849-1"):
– control category 4 – PL e to DIN EN ISO 13849-1
– corresponds to SIL 3 to DIN EN 61508-2
– corresponds to SILCL 3 to DIN EN 62061
(corresponds to control category 4 to DIN EN 954-1)
The safety-relevant current path with the output contacts 57-58 and
67-68 meets the following requirements under observation of a B10d
value assessment (also refer to "Requirements to DIN EN ISO 13849-1"):
– control category 3 – PL d to DIN EN ISO 13849-1
– corresponds to SIL 2 to DIN EN 61508-2
– corresponds to SILCL 2 to DIN EN 62061
(corresponds to control category 3 to DIN EN 954-1)
To determine the Performance Level (PL) of the entire safety function
(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all
relevant components is required.
2.4 Technical data
General data:
Standards: IEC/EN 60204-1, EN 60947-5-1,
EN ISO 13849-1, IEC/EN 61508
Climate resistance: EN 60068-2-78
Fixing: Snaps onto standard DIN rails
to DIN EN 60715
Terminal designations: EN 60947-1
Material of the enclosure: glass-bre reinforced thermoplastic,
ventilated
Material of the contacts: AgSnO, AgNi, self-cleaning,
positive drive
Weight: 420 g
Start conditions automatic or start button (monitored)
Feedback circuit available: Yes
Pull-in delay for automatic
start:
typ. 400 ms
Pull-in delay with reset
button:
typ. 30 ms
Drop-out delay in case
of emergency stop:
typ. 30 ms
Drop-out delay on
"supply failure":
typ. 80 ms
Mechanical data:
Connection type: Screw terminals
Cable section: min. 2 mm2/ max. 2 mm2
Connecting cable: rigid or exible
Tightening torque for
the terminals:
0.6 Nm
With removable terminals: Yes
Mechanical life: 10 million operations
Resistance to shock: 10 g / 11 ms
Resistance to vibrations
to EN 60068-2-6:
10 … 55 Hz, amplitude 0.35 mm
Ambient temperature: –25°C … +60°C
Storage and transport
temperature:
–40°C … +85°C
Protection class: Enclosure: IP 40,
Terminals: IP 20,
Wiring compartment: IP 54
Air clearances and creepage
distances to IEC/EN 60664-1:
4 kV/2 (basic insulation)
EMC rating: to EMC Directive
Electrical data:
Contact resistance in new state: max. 100 mΩ
Power consumption: max. 3.2 W / 7.1 VA 3 W,
plus signalling outputs
Rated operating voltage Ue: 24 VDC –15% / +20%,
residual ripple max. 10%
24 VAC –15% / +10%
Frequency range: 50 Hz / 60 Hz
Max. fuse rating of the
operating voltage:
internal electronic fuse,
tripping current F1: > 2.5 A;
tripping current F2: > 50 mA
(S11-S31) / 800 mA (X4)
Current and voltage at
the control circuits:
S11, S12, S21, S22, S31, B1:
24 VDC, 10 mA S33,
Y2:
24 VDC, start impulse 130 mA / 80 ms
Y2, X5:
24 VDC, start impulse 140 mA / 15 ms
Monitored inputs:
Cross-wire detection: optional
Wire breakage detection: Yes
Earth leakage detection: Yes
Number of NO contacts: 0
Number of NC contacts: 2
Conduction resistance: max. 40 Ω
Outputs:
Number of safety contacts: 5
Number of auxiliary contacts: 0
Number of signalling outputs: 1