Seneca R-8AI-8DIDO User manual

MI00606-1-EN INSTALLATION MANUAL 1/6
INSTALLATION MANUAL
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user's safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions that could damage the
instrument or connected equipment.
The warranty shall become null and void in the event of improper use or tampering with the module or devices
supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual
are not followed.
WARNING: The full content of this manual must be read before any operation. The module must only be used by
qualied electricians. Specic documentation is available using the QR-CODE shown on page 1.
Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The
symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to
recycle electrical and electronic waste.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electro-
static discharges. Take appropriate measures during any operation.
CONTACT INFORMATION
This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised.
The content of this document corresponds to the described products and technologies.
Stated data may be modied or supplemented for technical and/or sales purposes.
R-8AI-8DIDO
DOCUMENTATION
R-8AI-8DIDO

MI00606-1-EN INSTALLATION MANUAL 2/6
MODULE LAYOUT
Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.
FRONT SIDE BACK
LED STATUS LED meaning
IO1/IO8 On Digital input/output active
Off Digital input/output not active
OUT
SUP
On Digital inputs/outputs powered
Off Digital inputs/outputs not powered
STS
(Status only version R-8AI-8DIDO)
On IP address set
Flashing Waiting for the IP address from the DHCP
STS
(Status only version R-8AI-8DIDO-P)
On IP address set
Flashing No congured IP address
COM
(only version R-8AI-8DIDO-P)
Off No Pronet communication
Flashing Pronet communication present
FAIL On Digital output in FAIL / TC in Burn or out of range
RX
(only version R-8AI-8DIDO)
On RS485 port wiring error
Flashing Reception of data packet completed on RS485
TX
(only version R-8AI-8DIDO) Flashing Reception of data packet completed on RS485
ETH TRF (Yellow) Flashing Packet transit on Ethernet port
ETH LNK (Green) Flashing Ethernet port connected
SIGNALS VIA LED ON FRONT PANEL
SW2 SW3
32.2 mm
mm0.09
106.6 mm

MI00606-1-EN INSTALLATION MANUAL 3/6
CERTIFICATIONS
INSULATION
POWER SUPPLY Voltage: 10 ÷ 40 Vdc; 19 ÷ 28 Vac; 50 ÷ 65 Hz; Absorption: 3 W
ENVIRONMENTAL
CONDITIONS
Operating temperature:
from -25°C to +65°C
Humidity: 10%
÷
90% non condensing.
Storage temperature: from -30°C to +85°C
Protection rating: IP20
ASSEMBLY 35mm DIN rail IEC EN60715
CONFIGURATION With built-in WEB server (only version R-8AI-8DIDO)
CONNECTIONS /
COMMUNICATION
PORTS
3.5 mm pitch terminal block, 1.5 mm2 max cable section
2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45
1 RS485 port on terminals (only version R8AI--8DIDO)
DIGITAL INPUTS
Number of channels: 8; Voltage: Threshold ON: > 11 V; Threshold OFF:< 4 V; Vmax: 28 V; Impedance 9 kΩ
Compliant with IEC61131-2 type 3.
DIGITAL OUTPUTS Number of channels: 8, MOSFET, PNP; Max voltage/current: 0.2A; 9÷ 28 V
ANALOG INPUT
Number of channels: 8; Type: voltage, current, thermocouple, Max. 1 PT100 resistance thermometer.
Measuring range: Voltage: -30 V ÷ +30 V; -150 mV ÷ +150 mV
Current: -24 mA ÷ +24 mA (maximum loop power: 24 Vdc)
Thermocouple: J, K, T, E, N, R, S, B, L
Resistance thermometer: PT100: -200 °C ÷ +650 °C
(only for cold junction or
measurement compensation)
TECHNICAL SPECIFICATIONS

MI00606-1-EN INSTALLATION MANUAL 4/6
ELECTRICAL CONNECTIONS
The upper power supply limits must not be exceeded, as this could cause serious damage to the module.
Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc...).
CAUTION
23 B(-)
24 A(+)
25 GND
POWER SUPPLY RS485 SERIAL PORT
Connection to the RS485 port.
Polarity is not standardised and
in some devices may be inverted.
ANALOG INPUTS: The device has 8 analog inputs that can be congured via DIP-SDWITCH:
CURRENT (mA)
Active transmitter (SOURCE)
VOLTAGE (V) THERMOCOUPLE (Tc / mV)
B
A
C
+
mA (40, 43,...60, 63)
CURRENT (mA)
Passive transmitter, with external power
supply (SINK)
DIGITAL INPUTS (PNP)
With external power
DIGITAL OUTPUTS (PNP)
With external power
The relative dip-switch goes to the ON position The relative dip-switch goes to the OFF position The relative dip-switch goes to the OFF position
The relative dip-switch goes to the ON position
B
A( 40, 43,...60, 63)
C
+
TC/mV
B
A
C
+
(40, 43,...60, 63)
V
The digital outputs must be powered
externally to function properly.
Digital inputs must be externally powe-
red to function properly.
DIP-SWITCHES SW2 and SW3 are located on the back of the device. DIP-SWITCH SW1 is located on the front of the device.
DIP-SWITCH SW2 AND SW3:
ANALOG INPUT CONFIGURATION
SW1 DIP-SWITCH:
DEFAULT SETTINGS
SW2 SW3
12341234
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
SW1
DIP1 OFF DEFAULT
SETTINGS
DIP2 OFF
SETTING THE DIP-SWITCHES
For use and settings via DIP-SWITCH, see the user manual available on the website on the web page dedicated to the product.
The DIP-switch settings are read only at boot time. At each change, perform a restart.
WARNING
21
22
20
–/
+ /
.......
B
A
C
mA (40, 43...57, 60)
+
V EXT
S
+
10
11
12
....
17
18+
19-
V EXT
+
10
11
12
....
17
18+
19-
LOAD
LOAD
LOAD
LOAD
LOAD
V EXT
+

MI00606-1-EN INSTALLATION MANUAL 5/6
INSTRUCTIONS FOR ANALOG INPUTS:
The analog inputs of this device are designed to measure
voltages/currents on oating circuits that is not electrically
connected to each other.
In the case of measurement with thermocouples it is
possible to obtain correct measurements even if they are
applied to common metal parts.
The temperature measurement using thermocouples can be
affected by measurement errors due to the determination of
the cold junction temperature carried out near the terminal.
To eliminate any measurement errors it is necessary to wire
the thermocouples on an isothermal terminal board separate
from the device as shown in the diagram on the side.
Input No.1 set as Pt100 (see the DIP- SWITCH table) will
then be used to measure the cold junction temperature of
said terminal block.
PT100 A 40
B 41 AI1
C 42
A 43
B 44
C 45
A ...
B ...
C ...
A 63
B 64
C 65
AI2
AI...
AI8
+
+
RAME
MORSETTIERA
ISOTERMA
RAME
RAME
RAME
TC
TC
ANALOG INPUTS
Range Effective resolution
(at 400 ms)
Impedance Precision Temperature
drift
Ext. current
Voltage (V) -30 ÷ +30 Vdc 0.05 mV > 200 kΩ 0.1% f.s. 50 ppm
Current (mA) 0 ÷ +24 mA 0.07 µA 60 Ω 0.1% f.s. 50 ppm
Voltage (mV) -150 ÷ +150 mV 0.5µV > 10 MΩ 0.1% f.s. 50 ppm
Thermocouple -150 ÷ +150mV 0.5µV > 10 MΩ 0.1% f.s. 50 ppm
PT100 -200 ÷ 650 °C 6 mΩ (0.015°C at 0°C) 0.1°C 50 ppm 250 µA
THERMOCOUPLE TYPE
Range
[°C]
Standard Internal cold junction error
[°C]
J-210..1200 EN 60584 2
K-200..1372 EN 60584 2
T-200..400 EN 60584 2
E-200..1000 EN 60584 2
N-200..1300 EN 60584 2
R-50..1768 EN 60584 2
S-50..1768 EN 60584 2
B250..1820 EN 60584 2
L-200..800 GOST:8.585 2
FEATURE SUMMARY
THERMORESISTANCE
The SW1 Dip-Switch selector 1 goes to the OFF position.
Function valid only for analog input 1.
The product is not suitable for connection to a dangerous voltage conductor.
The maximum allowable voltage is 50 Vac / 75 Vdc with respect to earth.
WARNING
The input for the RTD thermoresistance is available only for the rst channel. For channels 2 to 8 it is not available.
CAUTION
COPPER
COPPER
COPPER
COPPER
ISOTHERMAL
TERMINAL BLOCK

MI00606-1-EN INSTALLATION MANUAL 6/6
DAISY-CHAIN ETHERNET CONNECTION
CAUTION
WARNING
IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES
FUNCTION VALID ONLY FOR THE R-8AI/8DIDO-2 AND R-8AI-8DIDO-2-P MODELS
Using the daisy-chain connection it is not necessary to use switches to connect the devices.
The following examples show the correct connections.
There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches
must be connected eliminating any loops. The following examples show the incorrect connections.
The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the
event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off
one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4.
The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched off module is less
than 100m.
MODULE 1 MODULE 2 MODULE 3
MODULE 1 MODULE 2 MODULE 3
MODULE 1 MODULE 2
LOOP
MODULE 3
MODULE 1
LOOP
ETHERNET CONNECTION RULES
For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.
FACTORY IP ADDRESS (ONLY R-8AI-8DIDO)
The default module IP address is static: 192. 168. 90. 101
WEB SERVER
To access the maintenance Web Server, use the following credentials:
Default user: admin
Default password: admin
CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
Table of contents
Other Seneca Measuring Instrument manuals

Seneca
Seneca S311D L Series User manual

Seneca
Seneca UT-M12 Manual

Seneca
Seneca R203 User manual

Seneca
Seneca S203RC-D User manual

Seneca
Seneca S203TA-D User manual

Seneca
Seneca S311D-XX-H User manual

Seneca
Seneca T203PM100-MU User manual

Seneca
Seneca R203 User manual

Seneca
Seneca R203 Series User manual

Seneca
Seneca S311A-XX-L User manual