Seneca Z203-1 User manual

ENGLISH - 1/16MI00117 -E8
Z203-1
Input/Retransmitted output
Voltage Input :
Current Input :
Class/Base Precision :
upto500Vac;frequency:35to75Hz.
Current inputrated range: 5Arms, Max peak factor: 3,
MaxCurrent:15A,Frequency:35to75Hz.
Voltmeter:0,5%.
Amperometer:0,5%.
Wattmeter:0,5%.(activepower)
Advanced Single-phase Network Analyser
Model Z203-1 is a complete single-phase network analyser suited for use with up to 500
Vacvoltagerangeand 5A(35to75Hz)current.
The instrument provides all the following electrical measurable quantities , ,: Vrms Irms
Watt Var Frequency,Energy,Cos, , .
Measurements are read through serial communication and both floating point and
normalisedformat(exceptforenergy).The DIP-switches (orModbusregisters)canbeset
for the analogue retransmission of any Vrms, Irms, Watt, Var, Frequency, and Cos
quantity. Themoduleisalsodistinguishedby:
GeneralDescription
Analog Output
Output Voltage :
Output Current :
Transmission error :
0..10Vdc,0..5Vdc,minimumloadresistance:2k .
0..20mA,4..20mA,maximumloadresistance:500
0,1%(max.range).
EN
FacilitatedpowersupplyandserialbuswiringbymeansofthebushousedintheDINrail.
CommunicationconfigurabilitythroughDIP-switchorsoftware.
s485serialcommunicationwithMODBUS-RTUprotocol,maximum32nodes.R
Powerinputisolation:3750Vacrespecttoalltheothercircuits.
Isolationbetweencommunicationandpowersupply:1500Vac.
Isolationbetweenretransmittedoutputandpowersupply:1500Vac.
Analogueoutputsignalsettableinvoltageorcurrent.
Possibility for connection and management by an external CT (only if Z203-1 is configurated
by a configuration software).
Energy counter: pulse digital output, reading on Modbus register (the count is saved into
retentive memory).
EasyconfigurationwiththesoftwareEasy,downloadablefromwww.seneca.it
Technical Specifications
Power Supply: 10–40 Vo19–28V (50–60Hz)
Consumption: max2.5W
Communication Ports: -RS485,1200..115200Baud.
-RS232, 2400 Baud, Address: 01, Parity: NO, Data: 8
bits;Stopbits:1.
Protocol: MODBUS-RTU
Installation category: II (Up to 300 V)

MI00117 E8 ENGLISH - 2/16
Insulation voltage :
Protection :
Environmental conditions :
Storage temperature :
Signalling by LED :
Connections :
Reference standards :
Dimensions and weight :
3750 Vac between the measurement input and all the
other circuits.1500 Vac between power supply and
communication. 1500 Vac between power supply and
outputs.
IP20.
Temperature -10..+65°C.
Humidity 30..90%non-condensing.
Altitude:upto2000ma.s.l.
-20..+85°C
Powersupply,Fail,RS485communication.
-Removable3-wayscrewterminals,5.08mmpitch.
-RearIDC10connectorforDINrail.
-3.5 mm stereophonic front jack for RS232 (COM)
connection.
EN61000-6-4 (electromagnetic emission, industrial environment)
EN61000-6-2(electromagneticimmunity,industrialenvironment)
EN61010-1 (safety). All circuits must be insulated from the other
circuits under dangerousvoltagewith double insulation.The power
supply transformer must comply with EN60742: “Insulated
transformersandsafetytransformers”.
Notes:
-Usewithcopperconductor.
-UseinPollutionDegree2Environment.
-PowerSupplymustbeClass2.
-WhensuppliedbyanIsolatedLimitedVoltageand/orLimited
CurrentPowerSupply,afuseratedmax2,5Ashallbeinstalledin
thefield.
100 x 112 x 17,5 mm, 140 g.
Box : PA6, black
Operatinglogic
The module measures the electrical measurable quantities: Vrms, Irms, Watt, Var,
Frequency, Energy, Cos and provides the values in the corresponding MODBUS
registers. Except for energy, these measurements are rendered in both floating point and
normalized format between 0..+10000 (0 ..+10000 for absolute value of VAR and Cos
350..750 for frequency from 35.0 Hz to 75.0 Hz). The module output transmits one of the
previous quantities selected (excluding energy) as either a current or voltage value. The
range of the retransmitted output is proportional to the full scale value of the quantity
measured:ifthesignal isa4..20mAcurrentsignalandthequantitytobetransmittedisthe
Vrms voltage, for example, 4 mAwill equal 0 V and 20 mAwill equal 500 V because these
arethetopandbottomfullscalevaluesforrmsvoltage.
Digital Output for pulses (energy counter)
Type : Passive(itmustbepowered),R>480
Range : 50mA
Insulation : 1500Vpeak
Screw terminal : 1and6(commonwithGNDanalogueoutput)

MI00117 -E8 ENGLISH - 3/16
Installationrules
The module is designed to be installed in vertical position on a DIN 46277 rail. In order to
ensure optimum performance and the longest working life, the module(s) must be
supplied adequate ventilation and no raceways or other objects that obstruct the
ventilation slots. Never install modules above sources of heat; we recommend installation
inthelowerpartofthecontrolpanel.
Electric connections
RS485 SERIAL PORTAND POWER SUPPLY
Theelectricconnectionsforpower supplycanbemadebyusingeithertheterminalsorthe
bus for the Seneca DIN rail. The RS485 bus connections are available only by using the
busfortheDINrail.
Relay scaling can also be selected from 100%, 50 % or 25 %. In the example above, with
50%retransmissionscaling, a4mAsignalwillequal0Vanda20mAsignalwill equal250
V. The retransmission values saturate at approximately 11 V for voltage outputs and at
around21mAforcurrentoutputs.Whenthemoduleisswitchedon,theappropriatesetting
coefficients are measured (depending on the choice of 50 or 60 Hz frequency). All the
settingsmadewillbeautomaticallyloadedwhenthemoduleisreset.TheFeRAM allowsto
recoverytheenergyifablack-outoccurs.
Note that the Vrms, Irms, Active Power and frequency values are obtained by direct
measurement, whereas the energy, Reactive Power and cos values are calculated.
Active power can be only greater than 0. An example: if reactive power is -2500 VAR or
+2500 VAR (physical value, electric line), corresponding numeric value is +10000 and
analogue output (available at the screw terminals) is +10 V (if SW2-2,3=”00”).If reactive
power is 0 VAR (physical value, electric line), corresponding numeric value is 0 and
analogue output (available at the screw terminals) is 0 V (if SW2-2,3=”00”). Cosfi has the
same behavior of reactive power. See the tables provided in APPENDIX A for the
measurementandretransmissionrangesinthecasesof50%and25%scaling.
Isolations
Power
supply
RS485
GND
AB
AC, DC
IN
OUT
OUT
LINE
OUT
LINE
IN
RS232
RS232
DIG.
OUT

MI00117 -E8 ENGLISH - 4/16
INPUT/RETRANSMITTEDOUTPUT
The module accepts an input voltage of up to a maximum 500 Vac. The input voltage is
connected to Terminals 10 and 12, whereas the load to be analysed is connected to
Terminals7and9.
3.5 mm Stereo Jack
DB9-F
GND Rx
Tx
Rx
Tx
GND
RS232SERIAL PORT
Connection cable DB9 with a 3.5 mm stereo Jack, can be assembled as indicated in the
followingfigure,orcanbeboughtasanaccessory.
1
RS485 B
RS485 A
RS485 GND
Power supply AC -
Power supply AC +
IDC10
Bus connector for DIN rail connections
2.5 W
10 ÷ 40 VDC
19 ÷ 28 VAC
2
3
Power supply from terminals
There is no isolation between RS485 and the retransmitted output.
MAX
5 A rms
MAX
500 VAC
7
9
10
12
LINE IN LINE OUT
Z203-1
2 3
POWER SUPPLY
LINE
LOAD

MI00117 -E8 ENGLISH - 5/16
Indications by LED on the frontal panel
PWR LED (GREEN)
Steady ON Meaning
Power supply is present.
ANALOGUE OUTPUT
The module provides an analog output in voltage (0..10 Vdc, 0..5 Vdc) or current (0..20
mA,4..20mA).Werecommendusingshieldedcablesfortheelectricconnectionsabove.
Voltage Output Current Output
++
5 5
6 4
EXAMPLE OF CONNECTION WITH AN EXTERNALCT (inthiscase,
configuretheZ203-1usingsoftware,NOTdip-switch)
There is no isolation between RS485 and the analog output.
Z203-1
P
230Vac
I I LOAD
N
97 10 12
S1/K S2/L
CT
N.C.
P1/K P2/L
DIGITAL OUTPUT
The module has a digital output: each pulse (200 ms) corresponds to a given number of
increments of the energy counted (see the register Digital Output Ratio).
Imax=V/R=50mA
Digital output
+
6
1
+
-
I
R
V

MI00117 -E8 ENGLISH - 6/16
Serial interface
FordetailedinformationonRS485serialinterface,consultthedocumentationprovidedby
thewebsitewww.seneca.it,inthesection .Prodotti/SerieZ-PC/MODBUS TUTORIAL
ERR LED (YELLOW)
Meaning
Steady ON Communication error between internal peripherals.
RX LED (RED)
TX LED (RED)
Steady ON
Steady ON
Meaning
Meaning
Data are being received through the RS485 communication port
Data are being transmitted through the RS485 communication port
Fixed Address: 03
Fixed Address: 04
Fixed Address, as from binary representation.
Fixed Address: 63
Fixed Address: 02
Communication Parameters from EEPROM (*)
Fixed Address: 01
SW1 43
X
5
X
6
X
7
X
8
X X
ADDRESS
57600 Baud
38400 Baud
19200 Baud
9600 Baud
1SW1 2
BAUD RATE
In all the following tables, the indication corresponds to a DIP-switch set in 1 (ON); no
indicationisprovidedwhentheDIP-switchissetin 0(OFF).
The instrument leaves the factory with all DIP-switches configured in position 0. The
settings of the DIP-switches defines the module's communication parameters: address
andspeed.
Default configuration
DIP-SWITCH SETTING
Flashing Voltage measured at less than 40 Vac and at less than 20 mA.
Network Frequency: 60 Hz
1SW2 Network Frequency: 50 Hz
NOMINAL FREQUENCY (50 or 60 Hz)

MI00117 -E8 ENGLISH - 7/16
(*) The default configuration is the following: Address 1, 38400, no parity, 1 stop bit.
0..5 V
0..20 mA
4..20 mA
SW2 0..10 V
OUTPUT TYPE
For the product's programming and/or configuration tools, consult the website
www.seneca.it.
During initial programming, the EEPROM (SW3 ..8 in OFF position) default setting
valuesoriginallyprogrammedasfollowscanbeused:
Address = 01 SPEED =38400 Baud PARITY= none BIT NUMBER = 8 STOP, , , ,
BIT=1.
The module can also be programmed through the front connector (COM) while paying
attentiontosetthefollowingconnectionparameters:
Address=01,Speed=2400Baud PARITY=none STOP BIT 1, , = .
The Com communication port behaves in the sameway asthe RS485bus port except for
thecommunicationparametersdescribedabove.ItalsohaspriorityovertheRS485serial
portandclosesafter15secondsofinactivity.
Programming
2 3
Retransmission of cos
Retransmission of frequency
Retransmission of VAR
Not allowed ( )configuration by EEPROM if SW2-1..8 are all «0»
Not allowed
Retransmission of Watt
Retransmission of Irms
Retransmission of Vrms
6SW2 7 8
SELECTION OF QUANTITY RETRANSMITTED (RETR. OUTPUT)
25 %
Not allowed
100%
SW2
50 %
RETRANSMISSION SCALING (OUT. RANGE)
4 5
SW2
SW3
TERMINATOR RS485
1 2
x
xTerminator ON, the SW3-2 is not used.
Terminator OFF, the SW3-2 is not used.

MI00117 -E8 ENGLISH - 8/16
Overall Dimensions
17,5 mm
100 mm
1 2 3
4 5 6
7 8 9
10 11 12
PWRERR
RX TX
Z203
COM
Frontal Panel and Led Dip-switch and Modbus register
If all the dip-switch of SW2 are equal to zero, so
“00000000”: the module acquires the configuration from
EEPROM for: nominal frequency, output-type, output-
electric value, retransmitted output, electric start scale,
electricendscale(seethemodbusregisters).
If at least one dip-switch of SW2 is different from zero: the
moduleacquires fromonlytheconfigurationsappliable
dip-switch SW2. For example: if SW2 is equal to “1 | 00 |
00 | 001”, then the nominal frequency is configurated as
“60 Hz” from dip-switch, the output type is configurated as
“0..10 V” from dip-switch, the retransmission scaling is
configurated as “100%” and the retransmitted output is
VRMS. In this case, the content of the registers
40110/40111, 40112/40113 (retransmitted output
range), 40114/40115, 40116/40117 (analogue output
range)arenotacquiredforthescaling.

ENGLISH - 9/16
MODBUS REGISTERS
Holding Registers
The 16-bit Holding Registers have the following structure:
The Bit notation [x:y] shown in the table indicates all the bits from x to y. For example, Bit
[2:1] indicates bit 2 and bit 1, and illustrates the meaning of the various linked
combinationsofthevaluesofthetwobits.RememberthattheMODBUS3and6functions
(respectively of multiple reading and single writing) can be executed on the following
registers.Defaultvaluesaremarkedwith*symbol.
Thefollowingindication(onlyreadableoralsowritable)isprovidedforeveryregister:
R:Readable
W:Writeable
Supported MODBUS Commands
Code
03
06
Function
Read Holding Registers
Write Single Register
Description
Reading of registers up to 16 words at a time
withinthesamegroup.
Writing of a word register
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Most
Significant bit Least
Significant bit
Bit Index
Word (16 bits): MODBUS Register
Z203-1 has MODBUS 16 bits (words) registers, accessible by RS485 or RS232 serial
communication. In the next paragraphs, we shall describe the supported MODBUS
commands,andthefunctionsoftheregisters.
MI00117 -E8

MI00117 -E8 ENGLISH- 10/16
REGISTER
MACHINE ID Description
Bit[15:8]:containthemodule'sID
Bit [7:0] contain the firmware's external
revision.
R/W
R
ADD.
40001
ADDR
BAUDR
CT_RATIO
Bit [15:8]
Bit [15:8]
Bit [7:0]
Bit [7:0]
Register for the setting of the module's
addressandparitycontrol.
Register for the setting of the Baud rate and
theresponsedelaytimeincharacters.
Register for the setting of thecoefficient ofthe
CT connectedtotheinstrument.
Set the module's address. Permissible values
from to (decimal values in the interval0x00 OxFF
of0-255).Defaultaddress:1.
Set the serial communication speed value
(Baudrate):
00000000 (0x00): 4800 Baud
00000001 (0x01): 9600 Baud
00000010 (0x02): 19200 Baud
00000011 (0x03): 38400 Baud*(Default).
00000100 (0x04): 57600 Baud
00000101 (0x05):115200 Baud
00000110 (0x06): 1200 Baud
00000111 (0x07): 2400 Baud
Set the response delay time in characters that
represents the number of pauses of 6 characters
each to be entered between the end of the Rx
messageandthestartoftheTxmessage.
Defaultvalue:0(hexadecimal:0x00).
Set the type of parity control:
00000000 : No parity ( NONE )*(Default)
00000001 : Even parity ( EVEN )
00000010 : Odd parity ( ODD )
R/W
R/W
R/W
40002
40003
40004
GROUP 1
Set the coefficient forany CT connected to themodule.
The transformation ratio multiplied by 10 must be
entered.This coefficient will influence the floating point
value of IRMS, Active Power and Reactive Power, but
will not influence the integer (0 - 10000) and
retransmission values. Default: 10 (retransmission is
not influenced by CT value, if configuration from Dip-
switch)
FW_CODE Register containing the firmware's internal
code. R40005
Bit [15:0]

ENGLISH - 11/16
VRMS_FLOAT_L
IRMS_FLOAT_L
VRMS_FLOAT_M
IRMS_FLOAT_M
Bit [15:0]
Bit [15:0]
Bit [15:0]
Bit [15:0]
Vrms voltage measurement in floating point
(leastsignificantword)
Irms current measurement in floating point
(leastsignificantword .)
Vrms voltage measurement in floating point
(most significantword)
Irms current measurement in floating point
(mostsignificantword .)
VrmsvoltagemeasurementinV(LSW).
IrmscurrentmeasurementinmA(LSW).
VrmsvoltagemeasurementinV(MSW).
IrmscurrentmeasurementinmA(MSW).
R
R
R
R
40082
40084
40081
40083
GROUP 2
MI00117 -E8
FREQUENCY Registertosetthenetworkfrequency R/W40007
If the dip switch Sw2 are configurated as
«00000000»:0=50Hz;1=60Hz
Bit [15:0]
OUT TYPE Registertosettherangeoftheanalogue
output R/W40008
If SW2 are equal to “00000000”, analogue output
is: 0=voltage; 2=current. In this case, start scale
output is reg.40114/40115, end scale output is
reg.40116/40117
Bit [15:0]
ELECTRICAL
MEASURE TO OUT Registertosettheretransmittedoutput R/W40009
If SW2 are equal to “00000000”: 0=VRMS;
1=IRMS; 2=potentiometer; 3=cosfi;4=frequency;
5=VAR;otherwise:seetheDip-switchtable
Bit [15:0]
ENERGY_L
ENERGY_M
Bit [15:0]
Bit [15:0]
Measure of energy in unsigned long (least
significantword)
Measure of energy in unsigned long (most
significantword)
MeasureofenergyinW/h(LSW).
MeasureofenergyinW/h(MSW).
R
R
40080
40079

MI00117 -E8 ENGLISH - 12/16
WATT_FLOAT_L
WATT_FLOAT_M
FREQ_FLOAT_M
FREQ_FLOAT_L
VARRMS_FLOAT_L
VARRMS_FLOAT_M
COS _FLOAT_M
COS _FLOAT_L
Bit [15:0]
Bit [15:0]
Bit [15:0]
Bit [15:0]
Bit [15:0]
Bit [15:0]
Bit [15:0]
Bit [15:0]
Active power measurement in floating point
(leastsignificantword .)
Active power measurement in floating point
(mostsignificantword .)
Frequency measurement in floating point
(mostsignificantword)
Frequency measurement in floating point
(leastsignificantword)
Reactive power measurement (in VARrms) in
floatingpoint(leastsignificantword).
Reactive power measurement (in VARrms) in
floatingpoint(mostsignificantword).
Cos measurement in floating point (most
significantword)
Cos measurement in floating point (least
significantword)
ActivepowermeasurementinW (LSW).
ActivepowermeasurementinW(MSW).
Frequency measurement in Hz (MSW).
Frequency measurement in Hz (LSW).
ReactivepowermeasurementinVARrms(LSW).
Reactive power measurement in VARrms
(MSW).
Cos measurement(MSW).
Cos measurement(LSW).
R
R
R
R
R
R
R
R
40086
40085
40087
40088
40090
40089
40091
40092

ENGLISH - 13/16
GROUP 3
STATUS
Bit 7
Bit [6:5]
Status Register
Zero cross error
1: signals that the input voltage is less than 40
V.
Reserved.
R/W40093
Bit 4 Communicationerrorwiththesensor:
1: signals an error of communication with the
sensor.
Bit [3:1] Reserved.
IRMS_INT
WATT_INT
VRMS_INT
Bit [15:0]
Bit [15:0]
Bit [15:0]
Register containing the measurement of the
Irmscurrentin0..10000scale.
Register containing the measurement of the
activepowerin0..10000scale.
Register containing the measurement of the
Vrmsvoltagein0..10000scale.
Measurement of the Irms current with 0.. 10000
scale.
Measurement of the active power with 0.. 10000
scale.
Measurement of the Vrms voltage with 0.. 10000
scale.
R
R
R
40096
40097
40095
VAR_INT
COS _INT
Bit [15:0]
Bit [15:0]
Register containing the measurement of the
reactivepowerin0 ..+10000scale.
Register containing the measurement of cos
in0..+10000scale.
Measurement of the reactive power with
0..+10000scale(absolutevalue)
Measurementofcos (absolutevalue)
R
R
40098
40099
MI00117 -E8
FREQUENCY
Bit [15:0]
Measureoffrequency
Measure frequency between 350 (35.0 Hz) and
750(75.0Hz)
R40101
Bit 0 1: Communication error with Feram

MI00117 -E8 ENGLISH - 14/16
START SCALE
OUTPUT_M
Bit [15:0]
Start scale of analogue output in floating-
point (mostsignificantword)
Output start scale value. To know the analogue
output, see reg.40008 (if SW2 are equal to
“00000000”)
R/W40114
COMMAND
COMMANDAUX_M
Bit [15:0]
Bit [15:0]
Registerofcommand
Register of auxiliary command (most
significantword)
0xBACA: this command loads the value
CommandAux in the register energy; 0x6500
forcestheRESETofthemodule.
Valuetoloadintheregisterenergy
R/W
R/W
40102
40103
COMMANDAUX_L
START SCALE
ELECTRIC_M
Bit [15:0]
Bit [15:0]
Register of auxiliary command (least
significantword)
Electricalstartscaleofretransmittedoutputin
floating-point (mostsignificantword)
Valuetoloadintheregisterenergy
start scale value.To knowwhich input isacquired,
seereg.40009(ifSW2are“00000000”)
R/W
R/W
40104
40110
STOP SCALE
ELECTRIC_M
STOP SCALE
ELECTRIC_L
END SCALE
ELECTRIC_L
Bit [15:0]
Bit [15:0]
Bit [15:0]
Electrical end scale of retransmitted output in
floating-point (mostsignificantword)
Electrical end scale of retransmitted output in
floating-point (leastsignificantword)
Electricalstartscaleofretransmittedoutputin
floating-point (leastsignificantword)
stop scale value.To know which input is acquired,
seereg.40009(ifSW2are“00000000”)
R/W
R/W
R/W
40112
40113
40111
Astheprevious(leastsignificantword)
Astheprevious(leastsignificantword)
START SCALE
OUTPUT_L
Bit [15:0]
Start scale of analogue output in floating-
point (leastsignificantword)
Astheprevious(leastsignificantword)
R/W40115

MI00117 -E8 ENGLISH - 15/16
STOP SCALE
OUTPUT_M
STOP SCALE
OUTPUT_L
Bit [15:0]
Bit [15:0]
Stopscaleofanalogueoutputinfloating-point
(mostsignificantword)
Stopscaleofanalogueoutputinfloating-point
(leastsignificantword)
Output stop scale value. To know the analogue
output, see reg.40008 (if SW2 are equal to
“00000000”)
Astheprevious(leastsignificantword)
R/W
R/W
40116
40117
DIG. OUT ENERGY
RATIO_M
DIG. OUT ENERGY
RATIO_L
Bit [15:0]
Bit [15:0]
Digital output energy ratio (unsigned long,
mostsignificantword)
Digital output energy ratio (unsigned long,
leastsignificantword)
Partition coefficient with which a pulse is
generated.Ifitis1:thepulseisgeneratedforeach
unit increment of energy, if it is 10: the pulse is
generatedevery10incrementsofenergy,etc...
Astheprevious(leastsignificantword)
R/W
R/W
40118
40119
ENERGY RATIO_M
ENERGY RATIO_L
Bit [15:0]
Bit [15:0]
Energyratio(mostsignificantword)
Energyratio(leastsignificantword)
Multiplier coefficient with which the energy
counter is incremented. If it is 1: the energy is
counted as W/h, if it is 0,001: the energy is
countedaskW/h,etc... Default:0,001
Astheprevious(leastsignificantword)
R/W
R/W
40120
40121

APPENDIX A : Retransmission scaling (from Dip-Switch)
Disposal of Electrical & Electronic Equipment (Applicable throughout the European Union and other
European countries with separate collection programs) This symbol, found on your product or on its
packaging, indicates that this product should not be treated as household waste when you wish to
dispose of it. Instead, it should be handed over to an applicable collection point for the recycling of
electrical and electronic equipment. By ensuring this product is disposed of correctly, you will help
prevent potential negative consequences to the environment and human health, which couldotherwise
be caused by inappropriate disposal of this product. The recycling of materials will help to conserve
naturalresources.For moredetailedinformationabouttherecyclingofthisproduct,pleasecontactyour
localcityoffice,wastedisposalserviceorthèretailstorewhereyoupurchasedthisproduct.
MI00117 -E8 ENGLISH - 16/16
100 % Scaling: Retransmission scaling
50 % Scaling: Retransmission scaling
25 % Scaling: Retransmission scaling
Electrical
Quantities Selectable analogue output
Vrms 0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
Irms
Active Power
Reactive Power (*)
cos
Frequency
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
Measurement
range
0..125 Vrms
0..1,25 A
0..625 W
0..625VAR
0..0,25
40..60 Hz
Electrical
Quantities Selectable analogue output
Vrms 0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
Irms
Active Power
Reactive Power (*)
cos
Frequency
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
Measurement
range
0..250 Vrms
0..2,5 A
0..1250 W
0..0,5
45..75 Hz
0..1250VAR
Electrical
Quantities Selectable analogue output
Vrms 0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
Irms
Active Power
Reactive Power (*)
cos
Frequency
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
0..10 V, 0..5 V, 0..20 mA or 4..20 mA
Measurement
range
0..500 Vrms
0..5 A
0..2500 W
0..1
35..65 Hz
0..2500VAR
(*)absolutevalues
SENECA s.r.l.
Via Austria, 26 – 35127 – PADOVA – ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287
For manuals and configuration software, please see:www.seneca.it
This document is property of SENECA srl. Duplication and reprodution are forbidden, if not authorized.
Contents of the present documentation refers to products and technologies described in it.All technical data
contained in the document may be modified without prior notice Content of this documentation is subject to
periodicalrevision.
Table of contents
Other Seneca Measuring Instrument manuals

Seneca
Seneca UT-M12 Manual

Seneca
Seneca R203 User manual

Seneca
Seneca R203 User manual

Seneca
Seneca S203TA-D User manual

Seneca
Seneca S203RC-D User manual

Seneca
Seneca Z203-2 User manual

Seneca
Seneca MY-PT User manual

Seneca
Seneca S311D L Series User manual

Seneca
Seneca S311D-XX-H User manual

Seneca
Seneca S311A-XX-L User manual
Popular Measuring Instrument manuals by other brands

TESTO
TESTO Smart Probes 510i instruction manual

EUTECH INSTRUMENTS
EUTECH INSTRUMENTS STANDARD TDSCAN 4 CONDUCTIVITY TESTER instructions

Thornton
Thornton 550 Series instruction manual

Siemens
Siemens Sitrans F Series operating instructions

MFJ
MFJ MFJ-224 instruction manual

Keysight Technologies
Keysight Technologies N4373E Setup guide