General
MD and ND-Frame Solid State Sensitrip style breakers of the
Sentron family, as shown on page 5, are for use in individual
enclosures, switchboards, and power distribution panel
boards. They are available both as 80% and 100% rated
devicesand in three interruption ranges as shown in the table
below.
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAA
AAA
AAA
AAA
AAAA
AAAA
AAA
AAA
A
A
AAA
AAA
A
A
AAA
AAA
Symmetrical RMS Amperes UL Interruption Ratings
Interruption
Rating Type 240V AC 480V AC 600V AC
Standard SMD6-SND6 65kA 50kA 25kA
High Rating SHMD6-SHND6 100kA 65kA 50kA
Current Limiting SCMD6-SCND6 200kA 100kA* 65kA*
*Not current limiting at 480 v AC and 600 v AC
SCMD6 and SCND6 type circuit breakers are designed to
meet the requirement of current limiting as outlined in the
National Electric Code, article 240-11 (1) and UL 489(2)
standards. SCMD6 and SCND6 type circuit breakers are
fuseless and therefore eliminate the requirement of locating
and replacing blown fuses should a high current fault occur.
The common trip feature of the circuit breaker is completely
retained so that all poles of the circuit breaker open when
caused to trip due to an overcurrent condition.
Pressure wire connectors, suitable for use with aluminum or
copper wire are available for all MD and ND-Frame circuit
breakers. Rear connection studs or plug-in connector(3)
assemblies are also available. The latter mounting arrange-
ment permits the removal of the circuit breaker from its leads
without physically coming in contact with either the line or
load terminals. UL listed special features such as a shunt trip,
auxiliary and alarm switches and undervoltage trip devices
are available for internal mounting. The installation and/or
removal of these devices is to be accomplished by qualified
personnel only. Information concerning special features can
be found on page 58.
The chart below illustrates the functions available in all
Sentron Solid State Sensitrip circuit breakers.
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAA
AAA
AAA
AAA
AAAA
AAAA
A
AAA
AAA
AA
AA
Adjustments Breaker Suffix Letters
AAG ANT ANGT
Long Time Adj.
Current Setting ✓ ✓ ✓ ✓
Adj.
Long Time Delay ✓ ✓ ✓ ✓
Adj.
Instantaneous
Setting ✓ ✓ ✓ ✓
Adj.
Short Time Pick Up ✓ ✓
Adj.
Short Time Delay ✓ ✓
Adj.
Short Time I²t
Pick Up ✓ ✓
Adj.
Ground Fault
Pick Up ✓ ✓
Adj.
Ground Fault Delay ✓ ✓
General Information
Circuit Breaker Operation
With the mechanism latched and the contacts open, the
operating handle will be in the OFF position. Moving the
handletotheONpositionclosesthecontactsandestablishes
a circuit through the circuit breaker. Under overload or short
circuit conditions sufficient to trip or open the breaker auto-
matically, the operating handle moves to a position between
ON and OFF To relatch the circuit breaker after automatic
operation, move the operating handle to the extreme OFF
position. The circuit breaker is now ready for reclosing.
The overcenter toggle mechanism is trip free of the operating
handle. The circuit breaker therefore, cannot be held closed
bymeansofthehandleshouldatrippingconditionexist.After
automatic operation, the handle will assume an intermediate
position between ON and OFF, thus displaying a clear
indication of tripping.
Maintenance
Experience has shown that properly applied molded case
circuit breakers normally do not require maintenance. How-
ever, some industrial users may choose to establish an
inspection and maintenance procedure to be carried out on
a regular basis. For detailed information, consult applicable
NEMA publications or your local Siemens sales office.
(1) National Electrical Code (240-11) A current limiting overcurrent protective device, which,
when interrupting currents in its current limiting range, will reduce the current flowing in the
faulted circuit to a magnitude substantially less than that obtainable in the same circuit, if the
device were replaced with a solid conductor having comparable impedance.
(2)UnderwritersLaboratories(UL489,Par2.5)Acircuitbreakerthatdoesnotemployafusible
elementandthatwhenoperatingwithinitscurrentlimitingrange,limitsthelet-through12tto
a value less than the I2t of a 1/2 cycle wave of the symmetrical prospective current.
(3) Plug-in assembly not available for ND-Frame