General
Information
General
LMD-Frame Sentron Series Circuit Breakers are used
in
individual enclosures, switchboards and panelboards. They
are available as thermal magnetic
with
interchangeable trip
units (Type
LMD6
and HLMD6), thermal magnetic
with
non-
interchangeable trip units (Type LMXD6 and HLMXD6), instan-
taneous magnetic only (motor circuit protectors, Type LMXD6-
ETI)
and molded case
switches
(Type LMXD6).
Pressure
wire
connectors, suitable
for
use
with
aluminum or
copper
wire
are available
for
all
LMD-Frame circuit breakers.
Rear connection stud assemblies are also available for both 2
and 3 pole constructions. This assembly
permits
cable or bus
connections
to
be
terminated
behind the circuit breaker rather
than to terminal connectors
mounted
on
the
breaker terminal
pads. UL listed field addable accessories such
as
shunt
trips,
undervoltage devices, auxiliary
switches
and bell alarm
switches
are also available. The installation
of
all
accessories
should be done only by qualified personnel. Information con-
cerning
all
accessories can be found on pages 17-20 and 35.
Thermal Magnetic
LMD6,
LMXD6CD
HLMD6
and
HLMXD6CD
type circuit breakers
provide
complete
overload and short circuit protection by use
of
a
time
delay thermal trip
element
and
an
instantaneous
magnetic trip device. Nominal instantaneous trip values are
externally adjustable
with
the 8 trip points
as
shown
below.
Instantaneous Adjustment Trip Range
Nominal Instantaneous Values
Ampere
:1:25% :1:20%
Ratings Tolerance 2 3 4 5 6 7 Tolerance
low
High
500-600 3000
3430
3860
4290 4710
5140 5570 6000
700-800 3200
3500 3700
4200 4700
6400 7300
8000
Circuit Breakers are calibrated at the factory, under controlled
temperature conditions for applications at 40°C (104°F) ambi-
ent
to
meet
requirements as outlined
In
UL 489 (Molded Case
Circuit Breakers and Circuit Breaker Enclosures) Standard. The
cover on
the
trip unit
is
sealed
to
prevent access
to
the trip
elements. Alterations
of
the calibration
of
these
elements
should not be
attempted.
Removal
of
the special sealed line
cover voids any warranties related
to
this product
as
well
as
voiding
of
the UL listing. Product catalog
number
information
can
be located on pages
34
thru 36.
Molded Case Switch
A molded case
switch
is
available
in
the
LMXD6
type circuit
breaker. This device employs the same operating mechanism
as
the
thermal magnetic and magnetic only circuit breakers.
A preset instantaneous function
is
factory installed
to
allow
the
switch
to
trip and
protect
itself at a high fault level. This
level
is
approximately 8000 amperes. No overload or
low
fault
CDTypes
LMXD6 and
HLMXD6
are UL listed
for
reverse connection applications
current protection
is
provided. This
switch
must
be protected
by a fuse or a molded case circuit breaker
of
equal ampere
rating.
When
protected by a
fuse
or circuit breaker, the switch
is
suitable for use on a circuit capable
of
delivering not more
than:
65,000A RMS Symmetrical @ 240 Volts AC
50,000A RMS Symmetrical @ 480 Volts
AC
25,000A RMS Symmetrical @ 600 Volts AC
Interrupting Ratings -Symmetrical RMS
Amperes (kA) Based on UL 489 Standards
The interrupting ratings
of
the LMD-Frame circuit breakers
are based on circuits adjusted
to
the short circuit (at specified
voltage) before insertion
of
the circuit breaker.
Also
shown
is
IEC
947-2 interruption rating information.
Interrupting Ratings
Based on UL 489 Standards UL File #10848
RMS Symmetrical Amperes (kA)
UlA.I.R.
IECA.I.R.
Breaker Volts
AC
Volts DC Volts
AC
(50/60 Hz)
Type 220/240 380/415 500
240 480 600 250 500 (leu)
(lcs)
(leu)
(lcs)
(leu)
(lcs)
LMD6,
65 50 25 30
(2-P)
25
(3-P)
65 33 40 20 30 15
LMXD6
HLMD6,
100 65 50 30
(2-P)
50
(3-P)
100 50 65 33 42
21
HLMXD6