manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Control Unit
  8. •
  9. Siemens 3AD8 User manual

Siemens 3AD8 User manual

Instruction manual
Type 3AD8 remote control unit (RCU) DNP3 protocol
instructions
Installation operation maintenance IC1000-F320-A200-X-4A00
Answers for infrastructure and cities.
www.usa.siemens.com/fusesaver
Important
The information contained herein is general in nature and not
intended for specific application purposes. It does not relieve
the user of responsibility to use sound practices in application,
installation, operation and maintenance of the equipment
purchased. Siemens reserves the right to make changes in the
specifications shown herein or to make improvements at any
time without notice or obligation. Should a conflict arise
between the general information contained in this publication
and the contents of drawings or supplementary material or
both, the latter shall take precedence.
Qualified person
For the purpose of this manual a qualified person is one who
is familiar with the installation, construction or operation of
the equipment and the hazards involved. In addition, this
person has the following qualifications:
Is trained and authorized to de-energize, clear, ground
and tag circuits and equipment in accordance with
established safety procedures.
Is trained in the proper care and use of protective
equipment, such as: rubber gloves, hard hat, safety glasses
or face shields, flash clothing, etc., in accordance with
established safety practices.
Is trained in rendering first aid.
Further, a qualified person shall also be familiar with the proper
use of special precautionary techniques, personal protective
equipment, insulation and shielding materials, and insulated tools
and test equipment. Such persons are permitted to work within
limited approach of exposed live parts operating at 50 volts or
more, and shall, at a minimum, be additionally trained in all of the
following:
The skills and techniques necessary to distinguish exposed
energized parts from other parts of electric equipment
The skills and techniques necessary to determine the nominal
voltage of exposed live parts
The approach distances specified in NFPA 70E®and the
corresponding voltages to which the qualified person will be
exposed
The decision-making process necessary to determine the
degree and extent of the hazard and the personal protective
equipment and job planning necessary to perform the task
safely.
Hazardous voltages.
Will cause death, serious injury or property damage.
Always de-energize and ground the equipment before
maintenance. Read and understand this instruction manual before
using equipment. Maintenance should be performed only by
qualified personnel. The use of unauthorized parts in the repair of
the equipment or tampering by unqualified personnel will result in
dangerous conditions which will cause death, severe injury or
equipment damage. Follow all safety instructions contained herein.
Note:
These instructions do not purport to cover all
details or variations in equipment, or to
provide for every possible contingency to be
met in connection with installation, operation
or maintenance. Should further information be
desired or should particular problems arise
which are not covered sufficiently for the
purchaser’s purposes, the matter should be
referred to the local Siemens sales office.
The contents of this instruction manual shall
not become part of or modify any prior or
existing agreement, commitment or
relationship. The sales contract contains the
entire obligation of Siemens Industry, Inc. The
warranty contained in the contract between
the parties is the sole warranty of Siemens
Industry, Inc. Any statements contained herein
do not create new warranties or modify the
existing warranty.
Table of contents
Introduction 04 – 05
DNP3 points and controls 06 – 10
SCADA interface configuration 11 – 14
Remote control unit (RCU) internal database
and controls 15 – 39
Abbreviations
DNP3 Distributed network protocol
PC Personal computer
PID Point identity (analog PID or digital PID)
PTT Push-to-talk
RCU Remote control unit
SCADA Supervisory control and data acquisition
UTC Universal time coordinated
4
Introduction
The purpose of the remote control unit
(RCU) is to provide remote SCADA system
access to monitor and control Siemens
Fusesavers installed on power lines. The
RCU maintains an internal database, which
holds information on the Fusesaver line
being monitored and on the RCU itself. It is
this data that is available to the SCADA
system. The internal database is detailed in
this manual, refer to RCU internal database
and controls section beginning on page 15.
It is usual for a utility to retrieve only a
subset of the data available in the database;
this is called point mapping.
The SCADA system accesses the RCU internal
database with a SCADA protocol and a long-
range radio or modem. Different SCADA
protocols have different capabilities and
methodologies. This manual deals with the
DNP3 protocol over the RCU serial data
connection.
The RCU implements the slave DNP3
protocol using industry standard libraries
provided by Triangle Microworks, Inc.
A subset level of the DNP3 protocol is
supported, which is defined in the DNP3
profile document RCU_DNP3_Profile_Rxx.
xml and is provided separately to this
manual. The profile is a formatted
document determined by the DNP3
committee.
This manual provides additional information
so the user can fully understand the
implementation of the DNP3 protocol on
this equipment, how the RCU internal
database is mapped into the serial DNP3
protocol, and the configuration options
available to the user.
The manual also deals with the settings for
the radio power supply and radio serial data
interface. The target reader of this manual is
already familiar with DNP3 and the user’s
SCADA system.
Introduction
Format and aim of the operating
instructions
These operating instructions apply for the
Siemens RCU.
The purpose of this instruction manual is to
assist the user in configuring the DNP3
protocol to work with the user’s SCADA
system.
In written or verbal communications, please
provide the complete description from the
operating instructions, quote the serial
number, and use only the designations and
key numbers for sub-parts used in these
locations.
Contact the nearest Siemens representative
if any additional information is desired.
Safety instructions
The RCU, together with the accessories and
special tools also supplied, is in conformity
with the statutory laws, rules, and standards
applicable at the time of delivery, especially
those regulations concerning health and
safety.
Signal words
The signal words “danger,” “warning” and
“caution” used in this manual indicate the
degree of hazard that may be encountered
by the user. These words are defined as:
Danger - Indicates an imminently hazardous
situation that, if not avoided, will result in
death or serious injury.
Warning - Indicates a potentially hazardous
situation that, if not avoided, could result in
death or serious injury.
Caution - Indicates a potentially hazardous
situation that, if not avoided, may result in
minor or moderate injury.
Notice - Indicates a potentially hazardous
situation that, if not avoided, may result in
property damage.
5
Field service operation and warranty
issues
Siemens can provide competent, well-
trained field service representatives to
provide technical guidance and advisory
assistance for the installation, overhaul,
repair and maintenance of Siemens
equipment, processes and systems. Contact
regional service centers, sales offices or the
factory for details, or telephone Siemens
field service at +1 (800) 347-6659 or +1
(919) 365-2200 outside the U.S.
Designated usage
The RCU is used to connect the Fusesaver
pole-mounted circuit breaker into a utility
SCADA system. Any other use is forbidden,
unless the consent of Siemens has been
obtained.
Changes to any part of the Remote Control Unit or
its accessories, that are carried out by the user or
others, and not previously agreed by Siemens, will
void the warranty of the whole product.
Compatibility
This version of the DNP3 protocol manual is
compatible with the following firmware and
software versions:
Application Applicable versions
RCU Firmware 100
Fusesaver Firmware 330-60
Communications
module Firmware 1537-75
Table 1: Compatibility
6
DNP3 points and
controls
Point mapping
RCU database digital and analog inputs can
be configured to suit the SCADA master
needs in a number of ways:
RCU database points can be mapped to
specific DNP3 point indices.
RCU database points can be unmapped,
in which case they will not appear in the
DNP3 point indices and will not be
available to the SCADA system.
For mapped points, the DNP3 class can
be set as described below.
Point mapping is especially useful when
trying to reduce the bandwidth
requirements over the SCADA network by
removing points that are deemed
unnecessary. This can be achieved by
mapping all required points to contiguous
DNP3 indices starting at index 0. Unwanted
points can then be left unmapped (i.e., not
mapped to any class), in which case they
will not be returned by integrity poll or
individual poll or will they generate
unsolicited messages.
Note that all point configuration is carried
out with the RCU Connect PC utility.
Class assignment
For all mapped points, the user can assign
DNP3 class 0, 1, 2, 3 or “None.”
Points with class “None” will not be returned
in an integrity poll. However, these points
can still be read by polling the specific data
type/point index for that point.
The advantage of setting class “None” is that
a point can still be scanned if required but
will not cause use of bandwidth in integrity
polls. The disadvantage is the potential
fragmentation of integrity polls.
Contiguous DNP3 indices
A DNP3 integrity poll will return all DNP3
points that have been mapped to the RCU
internal database and that have been
assigned to class 0, 1, 2 or 3. If the DNP3
mapping has gaps in the sequence of
indices caused either by an unmapped DNP3
index or by a mapped point being set to
class “None,” it will result in multiple DNP3
fragments being sent across the SCADA
network. This problem can be avoided by
mapping the class “None” points to the end
of the DNP3 index.
7
Point mapping example 1
This is a typical DNP3 mapping for the RCU
analog input points to reduce bandwidth
requirements by excluding some points and
keeping the DNP3 indices contiguous so
that an integrity poll will return DNP3
indexes 0 to 13 in a single message. The
points in grey are not mapped and cannot
be read.
Point mapping example 2
A similar mapping to above, but with
unwanted points mapped and assigned to
class “None” at the end of the DNP3 point
index. The unwanted points will not
generate events and will not be returned in
a status poll, but can still be read by issuing
a command to read that point or data type
directly. This mapping will reduce the
bandwidth requirements by the same
amount as the previous example, but the
unwanted points can still be read if
necessary.
Figure 1: Point mapping example 1
Figure 2: Point mapping example 2
8
Digital input point implementation
Digital points are DNP3 binary inputs (object
group 1) and binary input events (object
group 2).
Refer to the section on RCU internal
database and controls beginning on page 15
to understand how the status, events and
qualifiers for each point are generated.
Default input point mapping is DNP3 index =
RCU digital PID.
Analog input point implementation
Analog points are DNP3 analog inputs
(object group 30) and analog input events
(object group 32) for points that generate
events.
Refer to the section beginning on page 15
about RCU internal database and controls to
understand how the status, events and
qualifiers for each point are generated.
Default input point mapping is DNP3 index =
RCU analog PID.
Object flags
DNP3 object flags are generated as shown in
Table 2. Some object flags correspond to the
internal data qualifiers set out in the section
on RCU internal database and controls
beginning on page 15.
DNP3 device attributes
Device attributes (object group 0) come
from the RCU database string points defined
in the RCU operating instructions
(IC1000-F320-A198-X-XXXX).
Note that RCU string points are not
supported in DNP3 in any other way.
DNP3 device attributes are mapped into RCU
string points as given in Table 3.
Database object flags
DNP3 object flag Maps to
ONLINE RCU qualifier online
RESTART RCU qualifier restart
COMMS_LOST RCU qualifier
communications lost
REMOTE_FORCED Always clear
LOCAL_FORCED RCU qualifier overridden
CHATTER_FILTER Always clear
ROLLOVER Always clear
OVERRANGE Always clear
DISCONTINUITY Always clear
REFERENCE_ERROR Always clear
DNP3 device attributes
DNP3 device
attribute
Mapping in RCU internal
database
S_PID Name
252: device
manufacturer's
name
0
RCU
manufacturer’s
Name
250: device
manufacturer's
product name and
model
1RCU product name
and model
246: user assigned
ID code/number 2
Utility asset
number
(configurable)
245: user assigned
location name 3Name/location
(configurable)
242: device
manufacturer's
software version
4RCU software
version
Table 2: Object flags
Table 3: DNP3 device attributes
9
Controls
Controls are provided for all the control
points listed in the RCU operating
instructions (IC1000-F320-A198-X-XXXX) as
shown in the supported control options
Table 4. No protocol mapping of controls is
available, RCU control points (C_PIDs) map
directly to DNP3 control point indices.
Pulse times are ignored on all controls.
Time set is mapped to object group 50.
Supported control options
The following options are supported for the
RCU and Fusesaver controls.
No controls can be cancelled when running.
No event class is assigned to the controls.
Refer to RCU Operating Instructions
(IC1000-F320-A198-X-XXXX) for full
description of the control.
When supported, trip, pulse off and latch off
commands may be used interchangeably to
perform the same control.
When supported, close, pulse on and latch
on commands may be used interchangeably
to perform the same control.
DNP3
point
index
RCU
control
point
(C_PID)
Control name
Supported control options
Select/
operate
Direct
operate
Direct
operate
- no ack
Pulse
on
Pulse
off Close Trip Latch
on
Latch
off
0 0 Clear protocol counters Yes Yes Yes Yes Yes Yes
1 1 Trip/close ganged Yes Yes Yes Yes Yes Yes Yes Yes Yes
2 2 Trip/close any Yes Yes Yes Yes Yes Yes Yes Yes Yes
3 3 Phase A trip/close Yes Yes Yes Yes Yes Yes Yes Yes Yes
4 4 Phase B trip/close Yes Yes Yes Yes Yes Yes Yes Yes Yes
5 5 Phase C trip/close Yes Yes Yes Yes Yes Yes Yes Yes Yes
6 6 RCU dummy control Yes Yes Yes Yes Yes Yes Yes Yes Yes
7 7 Fusesaver dummy Yes Yes Yes Yes Yes Yes Yes Yes Yes
8 8 RCU clear flags Yes Yes Yes Yes Yes Yes
9 9 Set protection mode - normal Yes Yes Yes Yes Yes Yes
10 10 Set protection mode - single
shot Yes Yes Yes Yes Yes Yes
11 11 Set protection mode - off Yes Yes Yes Yes Yes Yes
12 12 Set remote mode - no reclose Yes Yes Yes Yes Yes Yes
13 13 RCU reboot Yes Yes Yes Yes Yes Yes
14 14 Set remote mode - fast Yes Yes Yes Yes Yes Yes
15 15 Set/clear “protection off” Yes Yes Yes Yes Yes Yes Yes Yes Yes
16 16 Set/clear “instantaneous
protection” bit Yes Yes Yes Yes Yes Yes Yes Yes Yes
17 17 Set/clear “no reclose
protection bit” Yes Yes Yes Yes Yes Yes Yes Yes Yes
18 18 RCU primary test mode Yes Yes Yes Yes Yes Yes Yes Yes Yes
Table 4: Supported control options
10
Control response codes
Available response codes are given in Table
5, which shows which codes are supported
and where appropriate details the RCU
internal database response code utilized.
Otherwise the response code is as per the
DNP3 specification in IEEE Std. 1815-2012.
Where the table shows that the response
code is not supported, it means that this
code is never returned to the master station.
DNP3 internal indicator bits
DNP3 internal indicator bits are set as
follows:
Config_corrupt is set by the RCU
Configuration Error point D_PID 5
Local_control is set by the RCU Remote
Control Enabled point D_PID 101
Device_trouble never gets set by RCU.
DNP3 control response codes
DNP3 response code Supported Relevant RCU internal response code
SUCCESS Yes SUCCESS
TIMEOUT Yes
NO_SELECT Yes
FORMAT_ERROR Yes
NOT_SUPPORTED Yes
ALREADY_ACTIVE Yes ALREADY_ACTIVE
HARDWARE_ERROR Yes COMMS_LOST or NOT_CONFIGURED
LOCAL Yes REMOTE_CONTROL_OFF or IN_SESSION or LEVER_DOWN
TOO_MANY_OBJS Yes
NOT_AUTHORIZED No
AUTOMATION_INHIBIT No
PROCESSING_LIMITED No
OUT_OF_RANGE No
RESERVED No
NON_PARTICIPATING Yes
UNDEFINED Yes
Table 5: DNP3 control response codes
11
Configuration settings fall into three classes:
Site-specific data that need to be
changed on a per-site basis such as the
DNP3 slave address.
Those that must be set for correct
operation, but which remain constant
across all sites. An example might be the
radio power supply voltage.
Those that should be left as the default
settings unless there is a need to change
them. Examples are the more involved
DNP3 library settings.
Standard RCU configurations for a utility are
held in a configuration template file that
Siemens will set up according to the user
requirements defined in their RCU
configuration specification form
(KMS-3100).
The process to develop the template is as
follows:
1. The user completes an RCU
configuration specification form and
returns to Siemens. This form contains
all configuration settings required for
the RCU and the communications
protocol. The form also details which
settings will be visible to the field user
and which settings can be changed by
the field user. Since most settings are
fixed for a utility, they will usually be
hidden from the field user.
2. Siemens creates the utility specific RCU
configuration file and returns it to the
user.
3. Using the RCU Connect utility, the user
configures the protocol mapping (which
points are to be sent to the SCADA
system) and workshop tests the SCADA
protocol with the RCU Probe PC utility to
be certain that the RCU is working as
expected with the SCADA system.
The user now has a “template” configuration
file for the population of RCUs. Using this
template makes site commissioning easier
by minimizing the amount of site-specific
data required.
This manual lists all the configuration
settings that relate to the SCADA interface,
including the radio power supply, the radio
data interface and the DNP3 protocol. Other
settings that relate to the Fusesaver site are
detailed in the RCU operating instructions
(IC1000-F320-A198-X-XXXX).
SCADA interface
configuration
12
Radio power supply settings
Name Range/choice Unit Default Description/comment
Radio/modem power
supply
Off
Battery
Controlled supply
Off
Sets the power source for the radio or modem.
Off - no power supply.
Battery - power supply from the battery via a relay.
Controlled supply - a voltage controlled supply is provided.
Radio supply voltage 3,000-9,000 mV 6,000 mV Voltage when using controlled supply.
Radio average current 10-1,000 mA 100 mA
Enter the average current the installed radio will consume. This is
required for reliable battery management when running from auxiliary
power supply.
This value is an estimate of: the receive current plus the transmit current
x transmit duty cycle. Required accuracy is +/- 50%.
Radio reset time 1-255 10
minutes
2,550
minutes
This is a time-out setting in multiples of 10 minutes. If a protocol
message has not been received for this time, then the radio will be
powered off for 10 seconds and then powered on again. The purpose is
to restart the radio periodically if there is no SCADA activity just in case
the radio is the problem. Range is 1 to 255 giving 10 to 2,550 minutes.
Radio/modem serial interface settings
Name Range/choice Unit Default Description/comment
Radio data interface
type
RS232 signals
Logic level signal
(3-9 V)
RS232 Signals can be RS232 or logic level when logic level, voltage and Tx/Rx
signal polarity can be configured.
Radio signal voltage 3,000-9,000 mV 5,000 This sets the radio signal voltage when using logic-level serial interface.
PTT enabled On/off Off To enable PTT with pre-transmit and post-transmit times as below.
PTT pre-transmit time 0-100 100 ms 0PTT output will be turned on for this time period before transmitting.
PTT post-transmit time 0-100 100 ms 0PTT output will remain on for this time period after transmitting has
stopped.
TTL Tx polarity Normal/inverted Normal
Normal TTL Tx polarity will have a logic high when idle. Start, stop and
data bits will have standard polarity. Inverted TTL Tx polarity will have a
logic low when idle. Start, stop and data bits will be inverted also.
TTL Rx polarity Normal/inverted Normal
Normal TTL Rx polarity will have a logic high when idle. Start, stop and
data bits will have standard polarity. Inverted TTL Rx polarity will have a
logic low when idle. Start, stop and data bits will be inverted also.
Data rate
1,200, 2,400,
4,800, 9.600,
19,200, 38,400,
57,600, 115,200
bps 115,200
CTS handshaking
support Enabled/disabled Disabled When enabled, RCU serial transmission will only occur when the CTS
input pin is asserted. When disabled, the CTS input pin is ignored.
RTS handshaking
support Enabled/disabled Disabled
When enabled, the RCU RTS output pin will be de-asserted in request to
stop receiving serial data (buffer full, unable to process more incoming
data). When disabled, the RTS output pin is de-asserted.
Data bits 8 bits Bits 8 bits
Stop bits 1 or 2 Bits 1
Parity enabled Enabled/disabled Disabled
Parity Odd or even Odd
Table 6: Radio power supply settings
Table 7: Radio/modem serial interface settings
13
SCADA operation settings
Name Range/choice Unit Default Description/comment
SCADA protocol type Serial DNP3 Serial
DNP3 Select this option for serial DNP3.
Automatically clear
fault flags
Yes
No Yes
There are several fault flags in the database (e.g., DPID 20, 21, 22 which
indicate a cleared fault has occurred on the line). These flags can be
cleared by the SCADA system operator with a reset control (CPID 8) and/
or after a time-out. This setting determines if the fault flags will be
cleared after a time-out:
Yes, flags will be cleared by time-out.
No, flags will not be cleared by time-out.
Automatically clear
fault flags time-out 0-3,600 s120 See above.
Always allow trip True
False False
When this setting is false, SCADA controls to Fusesaver are rejected if the
RCU remote control switch is off or a Fusesaver external lever is down.
This setting allows a modification of this behavior so that SCADA trip
controls can always be sent to Fusesavers.
True: The RCU will issue the trip command to the Fusesaver to trip
regardless of RCU remote control switch position and regardless of
Fusesaver external lever position. The Fusesaver will trip regardless of
policy file setting for manual inhibit (see Fusesaver operating
instructions IC1000-F320-A170-XX-XXXX).
False: If the RCU Remote Control switch is off or if the external lever
of the Fusesaver is down, then the RCU will reject the trip command
from the SCADA system.
Note: This setting only modifies the handling of SCADA Fusesaver trip
commands.
Protocol point configuration
Name Range/
choice Unit Default Description/comment
Line current deadband 1-100 0.1 A 20
This setting defines an amount by which the line
current changes an event will be created and sent
through the protocol to the SCADA control center.
Digital point mapping
and class assignment
Default mapping is protocol database index =
DNP3 index with all points assigned to class 1
The mapping and class assignment can be
configured using the RCU Connect utility.
Analog point mapping
and class assignment
Default mapping is protocol database index =
DNP3 index with all points assigned to class 2
The mapping and class assignment can be
configured using the RCU Connect utility.
Table 8: SCADA operation settings
Table 9: Protocol point configuration
14
DNP3 configuration
Name Range/choice Unit Default Description/comment
RCU data link address 0-65,519 DNP3
address 1RCU DNP3 address. This will normally be set on a per-site
basis.
Master data link address 0-65,519 DNP3
address 2Master station DNP3 address. This will normally be
constant for a utility.
Disable group 32 variation 3 Yes
No Enabled Disable if not supported by master.
Disable group 32 variation 4 Yes
No Enabled Disable if not supported by master.
Self-address support enable Yes
No No Refer DNP3 specification in IEEE Std. 1815-2012.
Maximum data link retries 0-100 3Refer DNP3 specification in IEEE Std. 1815-2012.
Application layer confirm time-out 1-7,200 s30 Refer DNP3 specification in IEEE Std. 1815-2012.
Support unsolicited responses Yes
No Yes Refer DNP3 specification in IEEE Std. 1815-2012.
Enable unsolicited responses at start-up Yes
No No Refer DNP3 specification in IEEE Std. 1815-2012.
Unsolicited response confirmation time-out 100-65,535 ms 10,000 Refer DNP3 specification in IEEE Std. 1815-2012.
Number of unsolicited retries 0-65,535 3Refer DNP3 specification in IEEE Std. 1815-2012.
Enable infinite unsolicited retries Yes
No No Refer DNP3 specification in IEEE Std. 1815-2012.
Enable class 1 event unsolicited responses at
start-up
Yes
No No Refer DNP3 specification in IEEE Std. 1815-2012.
Enable class 2 event unsolicited responses at
start-up
Yes
No No Refer DNP3 specification in IEEE Std. 1815-2012.
Enable class 3 event unsolicited response at
start-up
Yes
No No Refer DNP3 specification in IEEE Std. 1815-2012.
Class 1 events unsolicited response trigger 1-10 1Refer DNP3 specification in IEEE Std. 1815-2012.
Class 2 events unsolicited response trigger 1-10 1Refer DNP3 specification in IEEE Std. 1815-2012.
Class 3 events unsolicited response trigger 1-10 1Refer DNP3 specification in IEEE Std. 1815-2012.
Class 1 event hold time 0-65,535 ms 60,000 Refer DNP3 specification in IEEE Std. 1815-2012.
Class 2 event hold time 0-65,535 ms 60,000 Refer DNP3 specification in IEEE Std. 1815-2012.
Class 3 event hold time 0-65,535 ms 60,000 Refer DNP3 specification in IEEE Std. 1815-2012.
Max time between select and operate 1-60 s10 Refer DNP3 specification in IEEE Std. 1815-2012.
Table 10: DNP3 configuration
15
RCU internal database
and controls
This section details the data and controls
available in the RCU internal database.
Fusesaver data
Status data
Each Fusesaver has internal electronics
executing protection, controlling the
tripping and closing, measuring line current
and so on. The Fusesaver electronics send
Fusesaver status data every second to the
RCU over a short-range radio using a
communications module fitted to the
underside of the Fusesaver. This data is
called the live-data stream. The RCU uses
this live data to update the RCU internal
database so that this status data can be
then sent to a SCADA master station.
Fusesaver time-tagged events
In addition to the live data, the Fusesaver
generates time-tagged events such as
“protection trip” or “line current on.” These
events are also sent over the short-range
radio to the RCU and can be passed on to
the SCADA master station as time-tagged
events. In this case, the event time provided
to the SCADA system is the time given by
the Fusesaver (in other words the time
which would be seen in the Fusesaver event
log).
When retrieving time-tagged events from a
Fusesaver, the RCU will discard events that:
Occurred before the communications
between Fusesaver and RCU were
established, or
Occur while communications between
Fusesaver and RCU have failed.
RCU data
In addition to the data from the Fusesaver,
the RCU itself generates status points in the
database, such as door open or battery end
of life. These points can also generate
events available to the protocol to be sent to
the SCADA system. In this case, the events
will have a time tag from the RCU internal
clock.
Data qualifiers
Data available in the RCU database may
have one of the qualifiers described below.
Refer to page 8 Table 2: Object flags for
details of how the qualifiers are used by the
DNP3 protocol. Changes to qualifiers will
generate events which are tagged by RCU
clock time.
16
Events are also generated by changes to
point data; the time tag for data changes is
detailed in the point list below.
When qualifier events are generated
simultaneously with point data, they are
merged as a single event with time tag set
by point-data event.
Example of points from Fusesaver
A configured point that comes from a
Fusesaver will have online set true and on
restart of the RCU will have restart set true.
When the RCU opens communications to the
Fusesaver and gets data, the restart qualifier
will be set to false and will stay false until a
future restart. If after a restart the RCU
cannot establish communications to the
Fusesaver or if communications fails, then
the communications lost qualifier will be
set.
A point that comes from the Fusesaver but
is not configured in this particular
installation, such as a phase-B point in a
single-phase installation that only has phase
A, will have online set to false and restart
set true and communications lost set false.
Example of point from RCU
A point such as “door open,” which is always
configured and always up-to-date, will
always have online set true and restart set
false and communications lost set false.
Database qualifiers
Item Item Description
1Online
This qualifier indicates if a point has meaning for this site. When supported, this qualifier will be set:
True when the data point is configured to be active.
False when the data point is configured to be inactive (i.e., that phase is not configured) and therefore
unable to obtain valid data.
When not supported, this qualifier will be set true.
Changes to this qualifier generate events tagged with RCU time.
2Restart
This qualifier indicates if a point’s data is not yet updated after a restart. When supported, this qualifier will be
set:
True on restart.
False when data is updated.
When not supported, this qualifier will be set false.
Changes to this qualifier generate events tagged with Fusesaver or RCU time as detailed for that point.
3Communications lost
This qualifier indicates if a point’s data cannot be retrieved from a Fusesaver. When supported, this qualifier
will be set:
True when no data is being received for this point due to a failure in communications (e.g., failed to
communicate with Fusesaver).
False if data is being received for this point.
False on restart and only set to true if there is a failure to establish communications to the Fusesaver.
When not supported, this qualifier will be set false.
Changes to this qualifier generate events tagged with RCU time.
4Overridden
This qualifier indicates that the data for the point has been overridden by a user and is not true data. Normally
this will only occur during protocol testing. When supported, this qualifier will be set:
False on restart.
True when data is overridden.
When not supported, this qualifier will be set false.
Once a point has been overridden, the overridden qualifier will remain true until the RCU is restarted.
Changes to this qualifier generate events tagged with RCU time.
Table 11: Database qualifiers
17
Digital point description
The list below defines the digital-input
points in the RCU.
Digital points are identified by Digital_Point
IDentity or D_PID.
The following data is given for each point.
D_PID: the identifier for this point
including a phase identifier if valid.
Source: the source of the data, namely
the RCU or the Fusesaver.
The valid states, such as open/close
The source of the event time tag (if the
point generates events), which may be
the RCU itself or the Fusesaver.
How the status is determined.
How events are determined.
How the status is set on restart of the
RCU.
Data qualifiers which are supported for
that point.
Some digital points behave like protection
relay flags; they are set by a particular
protection event.
These flag points can be cleared by the
SCADA operator sending “Clear Flags”
control.
They can also be set to be cleared
automatically after the passing of a set time
period, for example, one hour.
These points are:
Protection flags
Digital
point
D_PID
Use
17, 18,
19
Indicates permanent fault on the line,
which the Fusesaver could not clear
20, 21,
22
Indicates transient fault on the line,
which was cleared by the Fusesaver
23, 24,
25
Indicates a fault current was detected
but ended before the Fusesaver tripped.
For example, a downstream transformer
fuse may have cleared the fault.
54, 55,
56
Indicates a very short-lived current
surge -possibly due to lightning activity.
See Table 15: RCU database digital points
list for a full list of all digital points available
in pages 20-29.
Analog point description
The list below defines the analog-input
points in the RCU.
Analog points are identified by Analog_Point
Identity or A_PID.
The following data is given for each point:
A_PID: the identifier for this point
including nominating the relevant phase
if valid.
Source: the source of the data, namely
the RCU or the Fusesaver.
The engineering units, range and
resolution.
The source of the event time tag (if the
point generates events), which may be
the RCU itself or the Fusesaver.
A description of the data.
What happens on restart of the RCU.
Data qualifiers, which are supported for
that point.
See Table 16: RCU database analog points
list for a full list of all analog points available
in pages 30-32.
Events and deadbands
Some analog points generate events on
change of value controlled by their
deadband. Other points do not generate
events on change of value, refer to Table 16:
RCU database analog points list for Analog
points on page 30.
As an example, DNP3 points can be
configured to belong for class 1, 2 or 3,
which will mean they will generate DNP3
protocol events if they have that capability
or alternatively they may be set to class 0,
which do not generate DNP3 protocol
events.
Deadbands are fixed for most points (a
deadband is the value by which a point
must change in order for it to generate an
event). However, the deadband can be
configured for some points so that the
utility can control the bandwidth used.
Table 11: Protection flags
18
Fault current recording
Analog points 12-17 act as a record of the
measured value of fault currents. For
example, a fault might have been measured
as 480 A peak on phase A. In this case A_PID
12 will be set to that value. These values are
overwritten each time there is a new fault
on that phase and will generate a new
event. They are volatile and are cleared on
RCU restart.
String point description
The RCU can return string data to a SCADA
system if supported by the protocol. String
data is usually data about the site, such as
site name.
String points are identified by String_Point
IDentity or S_PID. The following data is
given for each point:
S_PID: the identifier for this point
including nominating the relevant phase
if valid.
Source: the source of the data, namely
the RCU or the switchgear and how it is
set up.
A description of the data.
What happens on restart of the RCU.
Data qualifiers which are supported for
that point.
Controls description
Controls are commands that can be sent by
a protocol to operate Fusesavers or to affect
the RCU (for example, to reset fault flags).
The full list of available controls are listed in
Table 12: Internal response codes.
Control points are identified by Control_
Point IDentity or C_PID. The following data
is given for each point:
C_PID: The control point identifier.
Target: This specifies what is controlled.
Control type: This specifies what type of
control is sent to the target.
When a control is received, it is accepted or
rejected by the RCU. Table 12 describes the
internal control response codes that may be
associated with each control. One of these
codes will be returned by the RCU as a
response to a control request from the
SCADA system, refer to Table 5: DNP3
control response codes on page 10.
Where multiple responses apply, the lowest
numbered one will be reported.
Trip/close controls for Fusesaver are passed
to the Fusesaver and take time to have an
effect, at least 60 seconds and up to 120
seconds.
Some protocols may only be able to support
limited types of control.
Controls to RCU, such as clear flags or
counters, are always accepted. Controls to
Fusesaver may be rejected depending on
other conditions, such as communications
to Fusesaver lost or remote control disabled.
Internal control response codes
Code Description
1SUCCESS Command request has been accepted and command has been initiated.
2NOT_CONFIGURED Request not accepted because the control target has not been configured (e.g., C phase not configured).
3COMMS_LOST Request not accepted because either the RCU is starting up and has not yet fully verified the Fusesaver, or at
some later date has lost communications to the Fusesaver.
4ALREADY_ACTIVE Request not accepted because the control queue is full or the control is already active.
5REMOTE_CONTROL_OFF Request not accepted because remote switch is off.
6IN_SESSION Request not accepted because a Siemens Connect session is in progress and has control of the Fusesaver.
7LEVER_DOWN Request not accepted because the a Fusesaver external lever is in the down position.
Table 12: Internal response codes
19
Protection mode bits
A Fusesaver can be in one of five protection
modes. Refer Fusesaver operations manual
(IC1000-F320-X170-X-XXXX).
Controlling the protection in the Fusesaver
are three bits, which are available in the
database as digital points in Table 13.
Protection is operating normally when all
the bits are clear.
When there is a change of protection mode
(e.g., the mode is changed from Normal to
Fast Single), the protection bits are changed
as shown in Table 14.
In the database and controls available to the
SCADA system, the RCU provides indication
and control of both protection modes and
protection bits.
In other words, when setting up the SCADA
system the engineer can choose to control
the protection bits directly (CPID 15, 16, 17)
or by control of modes (CPID 9, 10, 11, 12,
14).
The choice between these two methods is
wholly up to the user. Both methods give
equivalent control of the Fusesaver
protection; however, each may have its own
advantages to the utility.
Control of protection modes is simple to
implement and allows the user to easily
restrict the choice for the operator to the
two or three modes that are going to be
used operationally (it is unlikely that a utility
will want to use all the five available
modes). Also, to change between modes,
such as protection normal and protection
fast single, requires only one command in
mode control, but two commands in bit
control (to change the auto-reclose bit and
the instantaneous bit). Consequently, there
is more room for operator error in
controlling bits.
On the other hand, if the SCADA and other
operators in the utility are familiar with
changing protection on a bit-by-bit basis,
then control of bits may be a better fit with
existing practices compared to control of
modes.
Protection mode bits
Bit DPID State Functionality in Fusesaver
Protection OFF 119, 120, 121 Set Protection tripping inhibited
Clear Will trip on protection
Auto-reclose OFF 125, 126, 127 Set Auto-reclose inhibited
Clear Will auto-reclose
Instantaneous trip 122, 123, 124 Set Protection will trip at as soon as the
pick-up current is exceeded
Clear Protection will trip as configured
Table 13: Protection mode bits
Protection mode/protection control bit relationship
New mode Protection OFF
bit
Auto-reclose
OFF bit
Instantaneous
bit
Name Indication DPID
Protection OFF 80, 81, 82 Set Not changed Not changed
Normal 74, 75, 76 Clear Clear Clear
Normal single 98, 99, 100 Clear Set Clear
Fast 116, 117, 118 Clear Clear Set
Fast single 77, 78, 79 Clear Set Set
Table 14: Protection mode/protection control bit relationship
Finally, there is a further set of bits in the
database, which show the remote set status
of all the protection mode and protection
bits. These are the points that are kept by
the Fusesaver when the external lever is
pulled down and will be re-instated when
the external lever is returned up. These
points may be of little interest to the SCADA
operator for operational purposes, but they
do indicate the protection that will be in
force when the Fusesaver external lever is
returned to the up position. The remote
protection mode bits are DPID 65 to 73, 95
to 97, 113 to 115. It is recommended that
these bits are not mapped unless they are of
specific interest.
20
Digital points
RCU database digital points list
D_PID Phase Name/states/source Status/events/restart/qualifiers
0
RCU - Door open
Source: Remote control unit (RCU)
States: Open/closed
Event time tag: RCU time
State: Set when the door is open. Cleared when the door is closed.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart. No event generated when state
is updated on restart.
Data qualifiers: Override.
1
RCU - Remote control on/off
Source: RCU
States: On/off
Event time tag: RCU time
State: Set when remote control switch on front panel is on. Cleared when
remote control switch on front panel is off.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart. No event generated when state
is updated on restart.
Data qualifiers: Override.
2
RCU - Battery needs to be replaced
Source: RCU
States: Needs to be replaced/OK
Event time tag: RCU time
State: Set when RCU battery needs to be replaced. Cleared when RCU battery is
replaced.
Events: Events generated by change of state above.
On restart: Non-volatile - This state is non-volatile and is carried through a
restart.
Data qualifiers: Override.
3
RCU - Source power on
Source: RCU
States: Has power source/no power source
Event time tag: RCU time
State: Set when RCU has a power source (auxiliary supply or solar). Cleared
when the RCU has no power source.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override.
4
RCU - Solar panel problem
Source: RCU
States: Solar panel OK/solar panel problem
Event time tag: RCU time
State: Set when RCU is configured for solar operation and detects that the solar
panel has not been supplying any voltage or has not been able to fully recharge
the battery over a period of several days. Cleared when the solar panel does
recharge battery or on RCU restart.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override.
5
RCU - Configuration error
Source: Fusesavers all phases
States: OK/configuration error
Event time tag: RCU time
State: Set when there is a configuration error, which means there is a
discrepancy between the configuration loaded into the RCU and Fusesaver on
the line. Cleared when a valid configuration is detected.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, restart.
6
Fusesaver unaccessible
Source: Fusesavers all phases
States: Unaccessible/accessible
Event time tag: RCU time
State: Set when the RCU is unable to access Fusesavers due to a Siemens
Connect user on site having established an operating session with the
Fusesavers. In this case, the RCU can report data but cannot make controls or
retrieve events. This means that events will be delayed for the duration of the
Siemens Connect session (but will still have the correct time tag when they are
retrieved). Cleared when Siemens Connect session finishes.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override.
Table 15: RCU database digital points list

Other manuals for 3AD8

1

Other Siemens Control Unit manuals

Siemens SIMOTION D4 5-2 Series User manual

Siemens

Siemens SIMOTION D4 5-2 Series User manual

Siemens SINAMICS G120 User manual

Siemens

Siemens SINAMICS G120 User manual

Siemens SIRIUS ACT 3SU1400-1EK10-6AA0 User manual

Siemens

Siemens SIRIUS ACT 3SU1400-1EK10-6AA0 User manual

Siemens ASIsafe K45 F User manual

Siemens

Siemens ASIsafe K45 F User manual

Siemens QAW850 User manual

Siemens

Siemens QAW850 User manual

Siemens VVF Series User manual

Siemens

Siemens VVF Series User manual

Siemens SITRANS LU SAM User manual

Siemens

Siemens SITRANS LU SAM User manual

Siemens SINAMICS S120 User manual

Siemens

Siemens SINAMICS S120 User manual

Siemens VAG60 Series User manual

Siemens

Siemens VAG60 Series User manual

Siemens SIRIUS 3SB38 User manual

Siemens

Siemens SIRIUS 3SB38 User manual

Siemens OMM-2 User manual

Siemens

Siemens OMM-2 User manual

Siemens SINUMERIK Series Parts list manual

Siemens

Siemens SINUMERIK Series Parts list manual

Siemens SIMATIC FM 351 User manual

Siemens

Siemens SIMATIC FM 351 User manual

Siemens SENTRON 7KM PAC 4DI/2DO User manual

Siemens

Siemens SENTRON 7KM PAC 4DI/2DO User manual

Siemens LMV37.4 Series Operator's manual

Siemens

Siemens LMV37.4 Series Operator's manual

Siemens SINUMERIK MC Quick start guide

Siemens

Siemens SINUMERIK MC Quick start guide

Siemens LAL Series User manual

Siemens

Siemens LAL Series User manual

Siemens 7153 User manual

Siemens

Siemens 7153 User manual

Siemens MOD-16 User manual

Siemens

Siemens MOD-16 User manual

Siemens simovert masterdrives User manual

Siemens

Siemens simovert masterdrives User manual

Siemens SITOP UPS1600 User manual

Siemens

Siemens SITOP UPS1600 User manual

Siemens RWF50 User guide

Siemens

Siemens RWF50 User guide

Siemens TX-I/O TXM1.8D Parts list manual

Siemens

Siemens TX-I/O TXM1.8D Parts list manual

Siemens SOAM User manual

Siemens

Siemens SOAM User manual

Popular Control Unit manuals by other brands

imagistics DL170 Setup guide

imagistics

imagistics DL170 Setup guide

schmersal SRB 202MSL operating instructions

schmersal

schmersal SRB 202MSL operating instructions

HEROSE 0131 Series operating instructions

HEROSE

HEROSE 0131 Series operating instructions

Skov BlueControl Insect Technical user guide

Skov

Skov BlueControl Insect Technical user guide

Honeywell ADEMCO 4204 installation instructions

Honeywell

Honeywell ADEMCO 4204 installation instructions

AVANCIS POWERMAX Safety, installation, and operation manual

AVANCIS

AVANCIS POWERMAX Safety, installation, and operation manual

Pilz PNOZ mc7p operating instructions

Pilz

Pilz PNOZ mc7p operating instructions

GE Multilin MM300 Communications guide

GE Multilin

GE Multilin MM300 Communications guide

Notifier IDR-MD quick start guide

Notifier

Notifier IDR-MD quick start guide

GatesAir Intraplex DS-64NC Installation and operation manual

GatesAir

GatesAir Intraplex DS-64NC Installation and operation manual

Viessmann Vivotronic 050 HK1S Installation and service instructions

Viessmann

Viessmann Vivotronic 050 HK1S Installation and service instructions

HYDAC International FCU 1000 Series Operating and maintenance instructions

HYDAC International

HYDAC International FCU 1000 Series Operating and maintenance instructions

Aprimatic CV10 Technical instructions

Aprimatic

Aprimatic CV10 Technical instructions

Lenze E82ZAFD manual

Lenze

Lenze E82ZAFD manual

Flowserve Series 081000 User instructions

Flowserve

Flowserve Series 081000 User instructions

Walther SMS-07 Assembly instructions

Walther

Walther SMS-07 Assembly instructions

Linx HumPRC Series Data guide

Linx

Linx HumPRC Series Data guide

Texas Instruments DRV601EVM user guide

Texas Instruments

Texas Instruments DRV601EVM user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.