manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Control Unit
  8. •
  9. Siemens RM-30U User manual

Siemens RM-30U User manual

This manual suits for next models

1

Other Siemens Control Unit manuals

Siemens SIMATIC FM 456-2 Assembly Instructions

Siemens

Siemens SIMATIC FM 456-2 Assembly Instructions

Siemens SINUMERIK 840C User manual

Siemens

Siemens SINUMERIK 840C User manual

Siemens Cerberus Pyrotronics MT-30 User manual

Siemens

Siemens Cerberus Pyrotronics MT-30 User manual

Siemens HTRI-S User manual

Siemens

Siemens HTRI-S User manual

Siemens Simatic 6ES7132-4HB01-0AB0 User manual

Siemens

Siemens Simatic 6ES7132-4HB01-0AB0 User manual

Siemens SINAMICS G120 Quick start guide

Siemens

Siemens SINAMICS G120 Quick start guide

Siemens 3VA9908-0BC Series User manual

Siemens

Siemens 3VA9908-0BC Series User manual

Siemens Logo! CM EIB User manual

Siemens

Siemens Logo! CM EIB User manual

Siemens SINUMERIK 828D PPU Series User manual

Siemens

Siemens SINUMERIK 828D PPU Series User manual

Siemens SIMATIC ET 200S User manual

Siemens

Siemens SIMATIC ET 200S User manual

Siemens SIWAREX JB User manual

Siemens

Siemens SIWAREX JB User manual

Siemens SIMATIC FM 351 User manual

Siemens

Siemens SIMATIC FM 351 User manual

Siemens ASIsafe SIRIUS 3RK1205-0B.00-0AA2 User manual

Siemens

Siemens ASIsafe SIRIUS 3RK1205-0B.00-0AA2 User manual

Siemens 3VL92 Series User manual

Siemens

Siemens 3VL92 Series User manual

Siemens 550-818B User manual

Siemens

Siemens 550-818B User manual

Siemens XCI2001-U1 Guide

Siemens

Siemens XCI2001-U1 Guide

Siemens Synco RMZ792 Operator's manual

Siemens

Siemens Synco RMZ792 Operator's manual

Siemens SINUMERIK 840Di sl User manual

Siemens

Siemens SINUMERIK 840Di sl User manual

Siemens SIPROTEC 4 7XT7100-0 A00/EE Series User manual

Siemens

Siemens SIPROTEC 4 7XT7100-0 A00/EE Series User manual

Siemens SIMOTICS CONNECT 400 User manual

Siemens

Siemens SIMOTICS CONNECT 400 User manual

Siemens SIMATIC ET 200S User manual

Siemens

Siemens SIMATIC ET 200S User manual

Siemens LMU54 Series Operator's manual

Siemens

Siemens LMU54 Series Operator's manual

Siemens SIMATIC FM 353 User manual

Siemens

Siemens SIMATIC FM 353 User manual

Siemens SIRIUS 3RT2 User manual

Siemens

Siemens SIRIUS 3RT2 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Wiring Instructions
Models RM-30U/RM-30RU
Releasing Device Modules
Fire Safety
Description
The Releasing Device Modules, Models RM-30U and
RM-30RU are designed to operate and supervise
solenoid valves or relays used for release of
extinguishing systems and to operate and supervise
relays used for door closing/opening or fan control.
The RM-30U and RM-30RU are functionally the
same except that the RM-30RU incorporates three
(3) series resistors that are used to adjust the
resistance of the circuit to compensate for varying
numbers of solenoids.
Release logic and subsequent activation of the
modules are governed by appropriate zone and
control modules in the System 3 control panel.
The modules are suitable for continuous duty when
used with continuous duty solenoids.
Dual input signals are required for activation of these
modules and a release takes place when a high
going signal is present on both of the input terminals.
These input signals are compatible with the outputs
available from the System 3 zone and control
modules. All agent release logic, time delays, etc.,
are performed ahead electrically of the RM-30U/
30RU by utilizing such System 3 modules as : ZU-35
Zone Module, PM-31 Program Matrix, TL-30U Timer,
and SR-32 Relay Module. The separate release
power input terminals extend the modules’ versatility
and reduces the load on the 10 conductor system bus.
A circuit disconnect switch is provided to deactivate
the module during servicing of the system. When the
switch is in the off position, a local supervisory LED
will be illuminated and an audible will sound.
The modules are provided with a yellow LED trouble
indicator to show an open release circuit condition
when the system is not in alarm. The LED indicator
can be lamp tested from the control panel. In addition
all wiring is monitored by the control panel for ground
faults. The module is also provided with a
supervisory LED, buzzer and silence switch. As
noted above, activating the disconnect switch
activates the supervisory signal. When there is no
disconnect condition and the supervisory silence
switch is in the silence condition, a trouble signal is
activated. The modules are placement supervised,
providing a trouble signal on removal from the
system.
Electrical Information
Module current requirement:
Normal supervisory - 6mA @ 24VDC
Released energized - 1.5A maximum @ 24VDC
Maximum line resistance - 3 ohms for typical
approved load.
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
P/N 315-085100-14
RM-30U
TC-30U
CP-35
6
42
6
5
5
4
3
2
1
+
_
INPUT POWER
(SEE NOTE 1)
3 OHMS MAX
TOTAL LINE RESISTANCE OF
DISCHARGE DEVICE CIRCUIT
CONNECTING WIRES
OPERATING SOLENOID
OR OTHER APPROVED LOAD
(SEE NOTE 1 AND TABLE 2)
CLASS B CONNECTED RELEASING DEVICE CIRCUIT
POLARITY SHOWN IN SUPERVISORY CONDITION
SUPV: 1.0 VDC, 5mA
ACTIVATED: 24 VDC REGULATED, 1.5mA MAX
ALARM ACTIVATED INPUT
24 VDC FULLWAVE UNFILTERED
RECTIFIED, 21mA (MAX) FROM CP-35
(AS SHOWN) OR EQUIVALENT
ACTUATION INPUT
24 VDC
,
3mA (MAX) FROM
CP-35, TERMINAL 42,
ZU-35, TERMINAL 1 OR 7,
OR TL-30U, TERMINAL 3
FULLWAVE
UNFILTERED RECTIFIED
THIS CONNECTION MUST
BE MADE TO PROVIDE
ACTUATION POWER
DURING ALARM ONLY
3A FUSE
RM-30RU
TC-30U
CP-35
6
42
6
5
5
4
3
2
1
+
_
JUMPERS
(3 PLACES--
SEE TABLE 1)
INPUT POWER
(SEE NOTE 1)
3 OHMS MAX
TOTAL LINE RESISTANCE OF
DISCHARGE DEVICE CIRCUIT
CONNECTING WIRES
SERIES CONNECTED OPERATED
SOLENOID(S) RATED 6 VDC EACH
OR OTHER APPROVED LOAD
(SEE NOTES 1 AND 2)
ALARM ACTIVATED INPUT
24 VDC
21mA (MAX) FROM CP-35
(AS SHOWN) OR EQUIVALENT
FULLWAVE UNFILTERED
RECTIFIED,
ACTUATION INPUT
24 VDC FULLWAVE
UNFILTERED RECTIFIED,
3mA (MAX) FROM
CP-35, TERMINAL 42,
ZU-35, TERMINAL 1 OR 7,
OR TL-30U, TERMINAL 3
THIS CONNECTION MUST
BE MADE TO PROVIDE
ACTUATION POWER
DURING ALARM ONLY
3A FUSE
LOAD
ADJUST
JUMPERS
CLASS B CONNECTED RELEASING DEVICE CIRCUIT
POLARITY SHOWN IN SUPERVISORY CONDITION
SUPV: 1.0 VDC, 5mA
ACTIVATED: 24 VDC REGULATED, 1.5mA MAX
NOTES for RM-30RU:
1. Operating solenoids, relay, or other approved loads operate
from a 24 VDC source. Use Battery Transfer Modules BC-35
or DC Program Plug JP-D in P2 of the CP-35.
2. The RM-30RU Releasing Device Module may be used to
activate up to four 6 VDC solenoids. Table 1 describes the
only acceptable combinations of solenoids and/or resistors.
Any other combination not described in Table 1 is not
permitted.
3. Solenoid supervised for open only.
4. All terminals are non-power limited. For wiring instructions
refer to the EB-31/-32/-33/-35 Installation and Power Limited
Wiring Instructions, P/N 315-093680. If power limited wiring
is desired use the PLM-35, P/N 315-093495.
5. For releasing diagram connections of RM-30RU, refer to
P/N 315-049675. The abort switch can have precedence
over the manual release function, or the manual release can
have precedence over the abort switch.
1ELBAT
noitacilppA snemeiS ledoM rodneV rebmuNtraP
forebmuN niseciveD seireS
forebmuN srotsiseR seireSni
f
orebmuN srepmuJ tuCot
1002APFN )ae722-CFH( 6-CEYPCOCSA 6-235812VH CDV6enO33
6-CEYPCOCSA 6-235812VH CDV6owT22
6-CEYPCOCS
A6-235812VH CDV6eerhT11
6-CEYPCOCSA *6-235812VH CDV6ruoF00
21-CEYPCETITPANS **5F4A-BN2-A3282 CDV21owT00
42-CEYPCETITPA
NS 6F4A-BN2-A3282 CDV42enO00
.desuebtsumsdionelosV6detcennocseiresruoF* CDV6ehtfonoitanibmocynahtiwdionelos
CDV21enoximotdettimreptonsitI** .srotsiserro/dnasdionelos
2ELBAT
noitacilppA snemeiS ledoM rodneV rebmuNtraP
forebmuN nisdioneloS seireS
31APFN A/N701A0128TOCSACDV42enO
)eg
uleDnoitcaerP( A/N701A0128ROCSACDV42enO
1002APFN6-CEYPC6-235812VHOCSACDV6enO
)ae722-CFH( 6-CEYPC6-235812VHOCSACD
V6owT
6-CEYPC6-235812VHOCSACDV6eerhT
6-CEYPC*6-235812VHOCSACDV6ruoF
21-CEYPC**5F4A-BN2-A3282ETITPANSCDV21owT
42
-CEYPC6F4A-BN2-A3282ETITPANSCDV42enO
.dettimreptonsielbatehtnidebircsedtondionelosynA .desuebtsumsdionelo
sV6detcennocseiresruoF* 6ehtfonoitanibmocynahtiwdionelosCDV21enoximotdettimreptonsitI** .sdionelosCDV
NOTES for RM-30U:
1. Operating solenoids, relay, or other approved loads operate
from a 24 VDC source. Use Battery Transfer Modules BC-35
or DC Program Plug JP-D in P2 of the CP-35.
2. For NFPA 13 Automatic Water Control Valve Release, use
an electric solenoid valve.
3. For NFPA 2001 Releasing Service, use only an approved
electric actuator. See Table 2.
4. Solenoid supervised for open only.
5. All terminals are non-power limited. For wiring instructions
refer to the EB-31/-32/-33/-35 Installation and Power Limited
Wiring Instructions, P/N 315-093680. If power limited wiring
is desired use the PLM-35, P/N 315-093495.
6. For releasing diagram connections of RM-30U, refer to P/N
315-049675. The abort switch can have precedence over
the manual release function, or the manual release can
have precedence over the abort switch.
FM Approval
Refer to the System 3 Pre-Action Sprinkler Control Diagram (P/N 315-091776) for an FM approved configuration.
NOTE: THE RELEASING DEVICE MUST BE AN FM APPROVED ELECTRIC SOLENOID VALVE FOR AN AUTOMATIC
WATER CONTROL VALVE RELEASE.
P/N 315-085100-14