
RM-30U
TC-30U
CP-35
6
42
6
5
5
4
3
2
1
+
_
INPUT POWER
(SEE NOTE 1)
3 OHMS MAX
TOTAL LINE RESISTANCE OF
DISCHARGE DEVICE CIRCUIT
CONNECTING WIRES
OPERATING SOLENOID
OR OTHER APPROVED LOAD
(SEE NOTE 1 AND TABLE 2)
CLASS B CONNECTED RELEASING DEVICE CIRCUIT
POLARITY SHOWN IN SUPERVISORY CONDITION
SUPV: 1.0 VDC, 5mA
ACTIVATED: 24 VDC REGULATED, 1.5mA MAX
ALARM ACTIVATED INPUT
24 VDC FULLWAVE UNFILTERED
RECTIFIED, 21mA (MAX) FROM CP-35
(AS SHOWN) OR EQUIVALENT
ACTUATION INPUT
24 VDC
,
3mA (MAX) FROM
CP-35, TERMINAL 42,
ZU-35, TERMINAL 1 OR 7,
OR TL-30U, TERMINAL 3
FULLWAVE
UNFILTERED RECTIFIED
THIS CONNECTION MUST
BE MADE TO PROVIDE
ACTUATION POWER
DURING ALARM ONLY
3A FUSE
RM-30RU
TC-30U
CP-35
6
42
6
5
5
4
3
2
1
+
_
JUMPERS
(3 PLACES--
SEE TABLE 1)
INPUT POWER
(SEE NOTE 1)
3 OHMS MAX
TOTAL LINE RESISTANCE OF
DISCHARGE DEVICE CIRCUIT
CONNECTING WIRES
SERIES CONNECTED OPERATED
SOLENOID(S) RATED 6 VDC EACH
OR OTHER APPROVED LOAD
(SEE NOTES 1 AND 2)
ALARM ACTIVATED INPUT
24 VDC
21mA (MAX) FROM CP-35
(AS SHOWN) OR EQUIVALENT
FULLWAVE UNFILTERED
RECTIFIED,
ACTUATION INPUT
24 VDC FULLWAVE
UNFILTERED RECTIFIED,
3mA (MAX) FROM
CP-35, TERMINAL 42,
ZU-35, TERMINAL 1 OR 7,
OR TL-30U, TERMINAL 3
THIS CONNECTION MUST
BE MADE TO PROVIDE
ACTUATION POWER
DURING ALARM ONLY
3A FUSE
LOAD
ADJUST
JUMPERS
CLASS B CONNECTED RELEASING DEVICE CIRCUIT
POLARITY SHOWN IN SUPERVISORY CONDITION
SUPV: 1.0 VDC, 5mA
ACTIVATED: 24 VDC REGULATED, 1.5mA MAX
NOTES for RM-30RU:
1. Operating solenoids, relay, or other approved loads operate
from a 24 VDC source. Use Battery Transfer Modules BC-35
or DC Program Plug JP-D in P2 of the CP-35.
2. The RM-30RU Releasing Device Module may be used to
activate up to four 6 VDC solenoids. Table 1 describes the
only acceptable combinations of solenoids and/or resistors.
Any other combination not described in Table 1 is not
permitted.
3. Solenoid supervised for open only.
4. All terminals are non-power limited. For wiring instructions
refer to the EB-31/-32/-33/-35 Installation and Power Limited
Wiring Instructions, P/N 315-093680. If power limited wiring
is desired use the PLM-35, P/N 315-093495.
5. For releasing diagram connections of RM-30RU, refer to
P/N 315-049675. The abort switch can have precedence
over the manual release function, or the manual release can
have precedence over the abort switch.
1ELBAT
noitacilppA snemeiS ledoM rodneV rebmuNtraP
forebmuN niseciveD seireS
forebmuN srotsiseR seireSni
orebmuN srepmuJ tuCot
1002APFN )ae722-CFH( 6-CEYPCOCSA 6-235812VH CDV6enO33
6-CEYPCOCSA 6-235812VH CDV6owT22
6-CEYPCOCS
A6-235812VH CDV6eerhT11
6-CEYPCOCSA *6-235812VH CDV6ruoF00
21-CEYPCETITPANS **5F4A-BN2-A3282 CDV21owT00
42-CEYPCETITPA
NS 6F4A-BN2-A3282 CDV42enO00
.desuebtsumsdionelosV6detcennocseiresruoF* CDV6ehtfonoitanibmocynahtiwdionelos
CDV21enoximotdettimreptonsitI** .srotsiserro/dnasdionelos
2ELBAT
noitacilppA snemeiS ledoM rodneV rebmuNtraP
forebmuN nisdioneloS seireS
31APFN A/N701A0128TOCSACDV42enO
)eg
uleDnoitcaerP( A/N701A0128ROCSACDV42enO
1002APFN6-CEYPC6-235812VHOCSACDV6enO
)ae722-CFH( 6-CEYPC6-235812VHOCSACD
V6owT
6-CEYPC6-235812VHOCSACDV6eerhT
6-CEYPC*6-235812VHOCSACDV6ruoF
21-CEYPC**5F4A-BN2-A3282ETITPANSCDV21owT
42
-CEYPC6F4A-BN2-A3282ETITPANSCDV42enO
.dettimreptonsielbatehtnidebircsedtondionelosynA .desuebtsumsdionelo
sV6detcennocseiresruoF* 6ehtfonoitanibmocynahtiwdionelosCDV21enoximotdettimreptonsitI** .sdionelosCDV
NOTES for RM-30U:
1. Operating solenoids, relay, or other approved loads operate
from a 24 VDC source. Use Battery Transfer Modules BC-35
or DC Program Plug JP-D in P2 of the CP-35.
2. For NFPA 13 Automatic Water Control Valve Release, use
an electric solenoid valve.
3. For NFPA 2001 Releasing Service, use only an approved
electric actuator. See Table 2.
4. Solenoid supervised for open only.
5. All terminals are non-power limited. For wiring instructions
refer to the EB-31/-32/-33/-35 Installation and Power Limited
Wiring Instructions, P/N 315-093680. If power limited wiring
is desired use the PLM-35, P/N 315-093495.
6. For releasing diagram connections of RM-30U, refer to P/N
315-049675. The abort switch can have precedence over
the manual release function, or the manual release can
have precedence over the abort switch.
FM Approval
Refer to the System 3 Pre-Action Sprinkler Control Diagram (P/N 315-091776) for an FM approved configuration.
NOTE: THE RELEASING DEVICE MUST BE AN FM APPROVED ELECTRIC SOLENOID VALVE FOR AN AUTOMATIC
WATER CONTROL VALVE RELEASE.
P/N 315-085100-14