manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Control Unit
  8. •
  9. Siemens MICROMASTER Vector 6SE32 User manual

Siemens MICROMASTER Vector 6SE32 User manual

Press this
green button
(RUN button)
to start the
motor.
This is the
STOP button.
While the motor is
turning, press this UP
button and watch as
the motor turns faster
and the value in the
display increases. It
will keep increasing
until it reaches 50 Hz.
When the inverter
reaches 50Hz output,
press this DOWN button
and watch the motor
speed and display value
decrease.
P
Jog
Forward/
reverse
MICROMASTER Vector 6SE32
MIDIMASTER Vector 6SE32
Getting Started
Caution: Before installing and
putting this equipment into
operation, please read the
Operating Instructions Manual for
Safety Precautions and Warnings
SIEMENS MICROMASTER
Step 1 Connecting up the MMV and MDV
230V Single Phase 400V Three Phase
The MICROMASTER Vector (MMV) and the
MIDIMASTER Vector (MDV) are a range of frequency
inverters for controlling the speed of three phase AC
induction motors.
Note: Motors above 11kW are usually configured
400V Delta / 690V Star.
In this case the motor should be connected in Delta.
Star connection for
400V 3 phase
Delta connection for
230V 3 phase
MIDIMASTER Vector (MDV)
The MDV electrical installation section of the
Operator Instructions Manual shows the position of
the terminals used to connect the power and the
motor.
At any time, press the 'STOP' button and watch the
motor stop.
Step 3 Changing the speed of the motor
The default output frequency of the drive is 5Hz (see
Hints and Tips to convert this to RPM). This speed will
probably be too low for most applications and a speed
change may be required. The following steps will allow
you to change the preset value of the inverter output to
the required speed.
Step / Action
Press the 'P' button to access the parameter settings. P000
P005
005.0
035.0
P005
P000
000.0
035.0
Press the button 5 times until the display reads P005.
Display
Press the 'P' button to display the current parameter value.
Press the button to change the value to 35Hz. (This
number can be any number between 0 and 50Hz - default.)
Press the 'P' button to store the new value.
Press the button until the display reads P000.
Press the 'P' button to exit the parameterisation procedure.
The display will alternate between the output frequency and
the frequency set point.
The required speed has now been stored.
This method is used to access all parameters.
The drive can now be started by pressing the 'RUN'
button. It will ramp up to the frequency held in parameter
P005 and remain there. To stop the drive press the
'STOP' button, the drive will then ramp down to 0Hz
output.
Default Parameters:
Digital input ParameterTerminal Default
1
2
3
4
5
6
5
6
7
8
16
17
P051 = 1
P052 = 2
P053 = 6
P054 = 6
P055 = 6
P356 = 6
ON right
ON left
Fixed frequency 3
Fixed frequency 2
Fixed frequency 1
Fixed frequency 6
Output
Relays
1
2
18/19/20
21/22
P061 = 6
P062 = 8
Fault identification
Warning active
Fault Codes:
Motor overtemperature by I²t
calculation
Other faults, see manual
F001
F002
F003
F005
F074
Overvoltage
Overcurrent
Overload
Inverter overtemperature
(internal PTC)
http://www.con.siemens.co.uk
For further Technical Support
Information, and to submit your
suggestions for improvements,
see our Web Site:
Siemens plc
Automation and Drives
Varey Road
Congleton
Cheshire CW12 1PH
Great Britain
May 1999
English
Order Number: 6SE3286-4BA86
G85139-H1751-U568-D1
F004 Overheating of motor (PTC)
This is the
STOP button''
STOP''
'DOWN' button
Hz
3_ Mot
IEC 56
IM B3
1LA7053-2AA10
Nr. ED510 3053
IP54 Rot KL 16
12 022
I.CI.F
60Hz 440V Y
0.34A
0.14kW
3360 /min
VDE 0530 S.F. – 1.15
P081 P084
Cos 0.81
P085P082
P083
P080
0.61 0.35A
50Hz 230 400
0.12kW
2800 /min
Cos .810
/Y
/
/
Step 4 Controlling the motor speed with
a potentiometer
A potentiometer can be used to control the running
speed of the inverter. This is achieved by varying the
voltage applied to the analogue input. Connect the
potentiometer to the control terminals shown below.
Starting and stopping of the motor may be achieved
by connecting a switch to the digital input terminals
shown.
P006 Set to 1 to allow analogue input
P007 Set to 0 to enable control via digital input
The following parameter settings are required
To get the best performance from your drive,
you should enter information from your motor
ratings plate into certain parameters. The
following diagram indicates the location of the
information and the parameters which should
be entered.
Telling the drive about your motor
Commissioning MICROMASTER Vector / MIDIMASTER Vector
Display parameters Basic parameters Motor parameters Frequently used parameters
Select display
via P001
Display frequency,
motor current and
motor speed
P001
0 = output frequency
1 = frequency setpoint
2 = motor current
5 = motor speed (RPM)
Ramp-up time
P002 0-650 sec.
Ramp-down time
P003 0-650 sec.
Frequency setpoint
P006
0 = digital
1 = analog
2 = fixed frequency
3 = digital setpoint addition
Keypad control
P007
0 = disable 1 = enable
Parameter protection
P009
0 = only P001-P009 can be
altered
2, 3 = all can be altered.
Nominal rating plate
motor power factor
P080 0.00-1.00
Nominal rating plate
frequency for motor
P081 0-650Hz
Nominal rating plate
speed for motor
P082 0-9999 RPM
Nominal rating plate
current for motor
P083 0.1-300.0A
Nominal rating plate
voltage for motor
P084 0-1000V
Nominal rating plate
power for motor
P085
0-250kW
Motor current limit
P086 0-250%
Automatic calibration
P088
Minimum motor frequency
P012
0-650Hz
Maximum motor frequency
P013
0-650Hz
Automatic restart after mains
failure
P015
0 = disable 1 = enable
Start on the fly
P016
0 = disable 2 = enable
Analogue input P023
0 = 0-10V/0-20mA,
1 = 2-10V/4-20mA,
3 = -10V to +10V
Fixed frequency operation
P041-044
P046-049
0-650Hz
Input terminal function
P051-055, 356
Selection relay output
P061, 062
DC injection braking
P073 0-200%
Pulse frequency
P076
See Operator Manual
Control mode
P077
See Operator Manual
Continuous Boost
P078 0-250%
See Operator Manual for other
parameters
Hints and Tips
The direction of rotation of the motor can be
reversed during commissioning by changing
over two of the output connections on the
inverter, or by pressing the Forward/Reverse
button.
Parameters P000 to P009 can always be
read or set. Access to all other parameters is
controlled by the contents of P009. The
factory default value is '0' which only allows
access to P000 to P009. Changing its value
to ‘3' allows all parameters to be accessed
permanently. See Operator Manual for the
function of other values of P009.
In case there are problems with the
parameter settings and you wish to start
again, change P944 to '1'. This will reset to
the default settings.
The value displayed in P000 is the output
frequency of the inverter, this is the default
setting but it can be changed by altering the
value in P001. For example, changing P001
to a value of '5' will cause the inverter to
display the RPM of the motor in P000. See
the Operator Manual for other settings of
P001.
The default value (0) of parameter P006
ensures that the drive runs at the frequency
set in P005. In order to control the output
frequency by an analogue input signal, the
value of P006 should be set to '1'. For other
methods of control using P006, see the
Operator Manual.
DIP selection switches are used to select a
range of 0-10V or 0-20mA for the
analogue input. See the Operator Manual for
more information.
An F002 fault is often caused by either too
short a ramp time or too much voltage boost.
An increase in the values in P002 will
increase the ramp time. Alternatively lower
the values in P078 and P079 to reduce the
voltage boost. Please note that if P078 falls
below '100' (default value for MMV) then the
motor may under-perform at low frequencies.
An F001 fault is often caused by attempting
to stop the motor too quickly - increasing the
value in P003 (ramp-down time) will reduce
this possibility.
If the display flashes during operation, the
drive is registering a warning. Check P931
for the cause.

This manual suits for next models

1

Other Siemens Control Unit manuals

Siemens Synco RMZ792 Operator's manual

Siemens

Siemens Synco RMZ792 Operator's manual

Siemens SINUMERIK 802D Installation guide

Siemens

Siemens SINUMERIK 802D Installation guide

Siemens LMV 5 Series User manual

Siemens

Siemens LMV 5 Series User manual

Siemens SINUMERIK 808D User manual

Siemens

Siemens SINUMERIK 808D User manual

Siemens SIMATIC FM 351 User manual

Siemens

Siemens SIMATIC FM 351 User manual

Siemens 3VA9.37-0VF10 User manual

Siemens

Siemens 3VA9.37-0VF10 User manual

Siemens SINUMERIK 828D Turning User manual

Siemens

Siemens SINUMERIK 828D Turning User manual

Siemens SIMATIC RF120C User manual

Siemens

Siemens SIMATIC RF120C User manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens LOGO! CMR2020 User manual

Siemens

Siemens LOGO! CMR2020 User manual

Siemens ASIsafe K45 F User manual

Siemens

Siemens ASIsafe K45 F User manual

Siemens VKF46 Series User manual

Siemens

Siemens VKF46 Series User manual

Siemens FDCL221-M User manual

Siemens

Siemens FDCL221-M User manual

Siemens TX-I/O TXM1.8D Parts list manual

Siemens

Siemens TX-I/O TXM1.8D Parts list manual

Siemens SIDOOR ATD4 W Series User guide

Siemens

Siemens SIDOOR ATD4 W Series User guide

Siemens SENTRON 7KM PAC 4DI/2DO User manual

Siemens

Siemens SENTRON 7KM PAC 4DI/2DO User manual

Siemens ZAM-180 User manual

Siemens

Siemens ZAM-180 User manual

Siemens HCP User manual

Siemens

Siemens HCP User manual

Siemens SIMOTION Parts list manual

Siemens

Siemens SIMOTION Parts list manual

Siemens SINUMERIK 802D sl Owner's manual

Siemens

Siemens SINUMERIK 802D sl Owner's manual

Siemens SIPROTEC 4 7XT71 Series User manual

Siemens

Siemens SIPROTEC 4 7XT71 Series User manual

Siemens SIMATIC FM 456-2 Assembly Instructions

Siemens

Siemens SIMATIC FM 456-2 Assembly Instructions

Siemens SIMATIC 8DO 24 V DC/0.5 A HF User manual

Siemens

Siemens SIMATIC 8DO 24 V DC/0.5 A HF User manual

Siemens SIMATIC IM 178-4 User manual

Siemens

Siemens SIMATIC IM 178-4 User manual

Popular Control Unit manuals by other brands

BENDIX SC-3 INLINE SINGLE CHECK VALVES manual

BENDIX

BENDIX SC-3 INLINE SINGLE CHECK VALVES manual

DeZurik APCO CVS-6000 Installation, operation and maintenance manual

DeZurik

DeZurik APCO CVS-6000 Installation, operation and maintenance manual

Giacomini R314DN manual

Giacomini

Giacomini R314DN manual

Piratelogic EVE Construction manual

Piratelogic

Piratelogic EVE Construction manual

Samson 3510 Mounting and operating instructions

Samson

Samson 3510 Mounting and operating instructions

Panasonic CF-BAS04GU operating instructions

Panasonic

Panasonic CF-BAS04GU operating instructions

Cornelius LEOPARD ERV Operator's manual

Cornelius

Cornelius LEOPARD ERV Operator's manual

Definox DPAX GEN 2 Maintenance manual

Definox

Definox DPAX GEN 2 Maintenance manual

NI PXIe-8623 SAFETY, ENVIRONMENTAL, AND REGULATORY INFORMATION

NI

NI PXIe-8623 SAFETY, ENVIRONMENTAL, AND REGULATORY INFORMATION

Honeywell D06FN-1B Installation instruction

Honeywell

Honeywell D06FN-1B Installation instruction

Sencon BCM500 instruction manual

Sencon

Sencon BCM500 instruction manual

ADTRAN Octal E&M user manual

ADTRAN

ADTRAN Octal E&M user manual

Hasco H1252 operating instructions

Hasco

Hasco H1252 operating instructions

Cutler-Hammer Digitrip OPTIM 550 installation instructions

Cutler-Hammer

Cutler-Hammer Digitrip OPTIM 550 installation instructions

GEM 695 operating instructions

GEM

GEM 695 operating instructions

Socla Sylax Technical manual

Socla

Socla Sylax Technical manual

Holley pro-jection 2D Installation, Tuning, & Troubleshooting Manual

Holley

Holley pro-jection 2D Installation, Tuning, & Troubleshooting Manual

Epson RX8804CE Applications manual

Epson

Epson RX8804CE Applications manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.