manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Control Unit
  8. •
  9. Siemens MICROMASTER Vector 6SE32 User manual

Siemens MICROMASTER Vector 6SE32 User manual

Press this
green button
(RUN button)
to start the
motor.
This is the
STOP button.
While the motor is
turning, press this UP
button and watch as
the motor turns faster
and the value in the
display increases. It
will keep increasing
until it reaches 50 Hz.
When the inverter
reaches 50Hz output,
press this DOWN button
and watch the motor
speed and display value
decrease.
P
Jog
Forward/
reverse
MICROMASTER Vector 6SE32
MIDIMASTER Vector 6SE32
Getting Started
Caution: Before installing and
putting this equipment into
operation, please read the
Operating Instructions Manual for
Safety Precautions and Warnings
SIEMENS MICROMASTER
Step 1 Connecting up the MMV and MDV
230V Single Phase 400V Three Phase
The MICROMASTER Vector (MMV) and the
MIDIMASTER Vector (MDV) are a range of frequency
inverters for controlling the speed of three phase AC
induction motors.
Note: Motors above 11kW are usually configured
400V Delta / 690V Star.
In this case the motor should be connected in Delta.
Star connection for
400V 3 phase
Delta connection for
230V 3 phase
MIDIMASTER Vector (MDV)
The MDV electrical installation section of the
Operator Instructions Manual shows the position of
the terminals used to connect the power and the
motor.
At any time, press the 'STOP' button and watch the
motor stop.
Step 3 Changing the speed of the motor
The default output frequency of the drive is 5Hz (see
Hints and Tips to convert this to RPM). This speed will
probably be too low for most applications and a speed
change may be required. The following steps will allow
you to change the preset value of the inverter output to
the required speed.
Step / Action
Press the 'P' button to access the parameter settings. P000
P005
005.0
035.0
P005
P000
000.0
035.0
Press the button 5 times until the display reads P005.
Display
Press the 'P' button to display the current parameter value.
Press the button to change the value to 35Hz. (This
number can be any number between 0 and 50Hz - default.)
Press the 'P' button to store the new value.
Press the button until the display reads P000.
Press the 'P' button to exit the parameterisation procedure.
The display will alternate between the output frequency and
the frequency set point.
The required speed has now been stored.
This method is used to access all parameters.
The drive can now be started by pressing the 'RUN'
button. It will ramp up to the frequency held in parameter
P005 and remain there. To stop the drive press the
'STOP' button, the drive will then ramp down to 0Hz
output.
Default Parameters:
Digital input ParameterTerminal Default
1
2
3
4
5
6
5
6
7
8
16
17
P051 = 1
P052 = 2
P053 = 6
P054 = 6
P055 = 6
P356 = 6
ON right
ON left
Fixed frequency 3
Fixed frequency 2
Fixed frequency 1
Fixed frequency 6
Output
Relays
1
2
18/19/20
21/22
P061 = 6
P062 = 8
Fault identification
Warning active
Fault Codes:
Motor overtemperature by I²t
calculation
Other faults, see manual
F001
F002
F003
F005
F074
Overvoltage
Overcurrent
Overload
Inverter overtemperature
(internal PTC)
http://www.con.siemens.co.uk
For further Technical Support
Information, and to submit your
suggestions for improvements,
see our Web Site:
Siemens plc
Automation and Drives
Varey Road
Congleton
Cheshire CW12 1PH
Great Britain
May 1999
English
Order Number: 6SE3286-4BA86
G85139-H1751-U568-D1
F004 Overheating of motor (PTC)
This is the
STOP button''
STOP''
'DOWN' button
Hz
3_ Mot
IEC 56
IM B3
1LA7053-2AA10
Nr. ED510 3053
IP54 Rot KL 16
12 022
I.CI.F
60Hz 440V Y
0.34A
0.14kW
3360 /min
VDE 0530 S.F. – 1.15
P081 P084
Cos 0.81
P085P082
P083
P080
0.61 0.35A
50Hz 230 400
0.12kW
2800 /min
Cos .810
/Y
/
/
Step 4 Controlling the motor speed with
a potentiometer
A potentiometer can be used to control the running
speed of the inverter. This is achieved by varying the
voltage applied to the analogue input. Connect the
potentiometer to the control terminals shown below.
Starting and stopping of the motor may be achieved
by connecting a switch to the digital input terminals
shown.
P006 Set to 1 to allow analogue input
P007 Set to 0 to enable control via digital input
The following parameter settings are required
To get the best performance from your drive,
you should enter information from your motor
ratings plate into certain parameters. The
following diagram indicates the location of the
information and the parameters which should
be entered.
Telling the drive about your motor
Commissioning MICROMASTER Vector / MIDIMASTER Vector
Display parameters Basic parameters Motor parameters Frequently used parameters
Select display
via P001
Display frequency,
motor current and
motor speed
P001
0 = output frequency
1 = frequency setpoint
2 = motor current
5 = motor speed (RPM)
Ramp-up time
P002 0-650 sec.
Ramp-down time
P003 0-650 sec.
Frequency setpoint
P006
0 = digital
1 = analog
2 = fixed frequency
3 = digital setpoint addition
Keypad control
P007
0 = disable 1 = enable
Parameter protection
P009
0 = only P001-P009 can be
altered
2, 3 = all can be altered.
Nominal rating plate
motor power factor
P080 0.00-1.00
Nominal rating plate
frequency for motor
P081 0-650Hz
Nominal rating plate
speed for motor
P082 0-9999 RPM
Nominal rating plate
current for motor
P083 0.1-300.0A
Nominal rating plate
voltage for motor
P084 0-1000V
Nominal rating plate
power for motor
P085
0-250kW
Motor current limit
P086 0-250%
Automatic calibration
P088
Minimum motor frequency
P012
0-650Hz
Maximum motor frequency
P013
0-650Hz
Automatic restart after mains
failure
P015
0 = disable 1 = enable
Start on the fly
P016
0 = disable 2 = enable
Analogue input P023
0 = 0-10V/0-20mA,
1 = 2-10V/4-20mA,
3 = -10V to +10V
Fixed frequency operation
P041-044
P046-049
0-650Hz
Input terminal function
P051-055, 356
Selection relay output
P061, 062
DC injection braking
P073 0-200%
Pulse frequency
P076
See Operator Manual
Control mode
P077
See Operator Manual
Continuous Boost
P078 0-250%
See Operator Manual for other
parameters
Hints and Tips
The direction of rotation of the motor can be
reversed during commissioning by changing
over two of the output connections on the
inverter, or by pressing the Forward/Reverse
button.
Parameters P000 to P009 can always be
read or set. Access to all other parameters is
controlled by the contents of P009. The
factory default value is '0' which only allows
access to P000 to P009. Changing its value
to ‘3' allows all parameters to be accessed
permanently. See Operator Manual for the
function of other values of P009.
In case there are problems with the
parameter settings and you wish to start
again, change P944 to '1'. This will reset to
the default settings.
The value displayed in P000 is the output
frequency of the inverter, this is the default
setting but it can be changed by altering the
value in P001. For example, changing P001
to a value of '5' will cause the inverter to
display the RPM of the motor in P000. See
the Operator Manual for other settings of
P001.
The default value (0) of parameter P006
ensures that the drive runs at the frequency
set in P005. In order to control the output
frequency by an analogue input signal, the
value of P006 should be set to '1'. For other
methods of control using P006, see the
Operator Manual.
DIP selection switches are used to select a
range of 0-10V or 0-20mA for the
analogue input. See the Operator Manual for
more information.
An F002 fault is often caused by either too
short a ramp time or too much voltage boost.
An increase in the values in P002 will
increase the ramp time. Alternatively lower
the values in P078 and P079 to reduce the
voltage boost. Please note that if P078 falls
below '100' (default value for MMV) then the
motor may under-perform at low frequencies.
An F001 fault is often caused by attempting
to stop the motor too quickly - increasing the
value in P003 (ramp-down time) will reduce
this possibility.
If the display flashes during operation, the
drive is registering a warning. Check P931
for the cause.

This manual suits for next models

1

Other Siemens Control Unit manuals

Siemens ACVATIX VPF53 Series User manual

Siemens

Siemens ACVATIX VPF53 Series User manual

Siemens SINAMICS G120D User manual

Siemens

Siemens SINAMICS G120D User manual

Siemens 3VA9908-0BC Series User manual

Siemens

Siemens 3VA9908-0BC Series User manual

Siemens SINUMERIK 840C Manual

Siemens

Siemens SINUMERIK 840C Manual

Siemens SIRIUS PROFINET User manual

Siemens

Siemens SIRIUS PROFINET User manual

Siemens HOTEL SOLUTION HTC3.1/A User manual

Siemens

Siemens HOTEL SOLUTION HTC3.1/A User manual

Siemens SINAMICS S120 User manual

Siemens

Siemens SINAMICS S120 User manual

Siemens SIMOTION D4 5-2 Series User manual

Siemens

Siemens SIMOTION D4 5-2 Series User manual

Siemens OLM/P11 V4.0 User manual

Siemens

Siemens OLM/P11 V4.0 User manual

Siemens SINUMERIK 840D sl Parts list manual

Siemens

Siemens SINUMERIK 840D sl Parts list manual

Siemens SINUMERIK 828D PPU Series User manual

Siemens

Siemens SINUMERIK 828D PPU Series User manual

Siemens TM Timer DIDQ Quick start guide

Siemens

Siemens TM Timer DIDQ Quick start guide

Siemens TMM-1 User manual

Siemens

Siemens TMM-1 User manual

Siemens 7SC80 User manual

Siemens

Siemens 7SC80 User manual

Siemens Simatic S5 IP 240 Technical Document

Siemens

Siemens Simatic S5 IP 240 Technical Document

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens SINUMERIK 808D Quick start guide

Siemens

Siemens SINUMERIK 808D Quick start guide

Siemens SIMATIC Technical Document

Siemens

Siemens SIMATIC Technical Document

Siemens 7KM4211-1BA00-3AA0 User manual

Siemens

Siemens 7KM4211-1BA00-3AA0 User manual

Siemens SITOP PSE200U 3 A User manual

Siemens

Siemens SITOP PSE200U 3 A User manual

Siemens SINAMICS G120 Datasheet

Siemens

Siemens SINAMICS G120 Datasheet

Siemens SINUMERIK 840D sl Instruction sheet

Siemens

Siemens SINUMERIK 840D sl Instruction sheet

Siemens SENTRON PROFINET Proxy SPP2000 User manual

Siemens

Siemens SENTRON PROFINET Proxy SPP2000 User manual

Siemens CU230P-2 HVAC User manual

Siemens

Siemens CU230P-2 HVAC User manual

Popular Control Unit manuals by other brands

GC5 SFAR-1M-2DI2DO user manual

GC5

GC5 SFAR-1M-2DI2DO user manual

Bosch B443 installation manual

Bosch

Bosch B443 installation manual

Stober ME 200 manual

Stober

Stober ME 200 manual

Bosch Rexroth IndraControl VCP 25.2 Project planning manual

Bosch

Bosch Rexroth IndraControl VCP 25.2 Project planning manual

LEGRAND Wattstopper LMCT-100-2 Quick start gude

LEGRAND

LEGRAND Wattstopper LMCT-100-2 Quick start gude

GEZE IO 420 user manual

GEZE

GEZE IO 420 user manual

Geca CTP24 user manual

Geca

Geca CTP24 user manual

Wandel & Goltermann OLA-35 Description and operating manual

Wandel & Goltermann

Wandel & Goltermann OLA-35 Description and operating manual

THOMSON Grass Valley KAM-XM Series instruction manual

THOMSON

THOMSON Grass Valley KAM-XM Series instruction manual

Eaton Series NRX installation instructions

Eaton

Eaton Series NRX installation instructions

Espressif PAN100 manual

Espressif

Espressif PAN100 manual

Bray 752 Series Installation, operation and maintenance manual

Bray

Bray 752 Series Installation, operation and maintenance manual

Waterbird ITSC1000 user manual

Waterbird

Waterbird ITSC1000 user manual

Bray/VAAS O-Ported Series Operation and maintenance manual

Bray/VAAS

Bray/VAAS O-Ported Series Operation and maintenance manual

Gemu R629 eSyLite operating instructions

Gemu

Gemu R629 eSyLite operating instructions

Avid Technology Pro Tools SYNC HD Guide

Avid Technology

Avid Technology Pro Tools SYNC HD Guide

Lefroy Brooks CW-4050 Installation, operating,  & maintenance instructions

Lefroy Brooks

Lefroy Brooks CW-4050 Installation, operating, & maintenance instructions

Jetter JX3-COM-PND installation manual

Jetter

Jetter JX3-COM-PND installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.