P/N 315-099105-6
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
Installation Instructions
Model NIM-1M
Network Interface Modem Module
OPERATION
The Model NIM-1M plug-in modem board from
Siemens Industry, Inc., mounts to and is connected to
the NIM-1W board to provide modem communication
capability for an MXL System XNET network.
The modem transmission line connected to the
NIM-1M can only be Style 4 and can be made using
standard 18 AWG shielded twisted pair or data
grade phone lines.
Note: A pair of NIM-1W / NIM-1M board sets is
referred to as a “bridge” in this document.
INSTALLATION
Remove all system power before installation,
first battery and then AC. To power up, connect AC
first, then the battery.
Setting the Switches
Before mounting the NIM-1M modem module on the
NIM-1W, set all the switches and configuration
jumpers on both modules. Refer to the NIM-1W
Installation Instructions, P/N 315-099165 for infor-
mation on setting the switches on the NIM-1W.
NIM-1M SETTINGS
The NIM-1M has three configuration headers (refer
to Figure 1). The NIM-1Ms are always connected in
board sets, or pairs, with NIM-1Ws to form the
bridge. Designate one board set as NIM-1M LOCAL
and the other as NIM-1M REMOTE. Program the
NIM-1Ms as shown in Table 1.
1ELBAT
sM1-MINEHTGNIMMARGORP
LACOLM1-MINETOMERM1-MIN
1PJ NO 1PJ NO
2PJ NO 2PJ FFO
3PJ FFO 3PJ NO
Mounting
The NIM-1M is mounted on the NIM-1W with 4 nylon
spacers.
1. Snap the 4 nylon spacers into place in the holes
on the underside of the NIM-1M board in the
positions indicated in Figure 2.
2. Position the 4 spacers on the NIM-1M over the 4
holes on the component side of the NIM-1W.
Refer to Figure 3 for representative location of
the NIM-1M on the NIM-1W. Press the spacers
firmly into place in the NIM-1W one at a time.
Cable Connections from NIM-1M to NIM-1W
The NIM-1M has a cable attached to the underside
of the board that connects to JP1 of the NIM-1W.
The cable plug is polarized and connects one way
only. Refer to Figure 3 for the location of JP1. Refer to
the NIM-1W installation instructions, P/N 315-
099106, for installing MXL WAN.
Figure 1
NIM-1M Module Board
NOTES:
1. "ON" IS WHEN THE JUMPER IS IN THE PROPER POSITION
OVER PLUGS JP1, JP2, OR JP3.
2. THE CABLE THAT CONNECTS THE NIM-1M TO THE NIM-1W
IS ATTACHED TO THE UNDERSIDE OF THE NIM-1M.
P1
JP1
NIM-1M
P2
1
2
3
TB1
SHIELD*
RING
TIP
LOCAL EARTH
GROUND
*TIE SHIELD TO EARTH GROUND AT ONE END ONLY
RTSRICDRXDTXDDTRDSRCTSPWR
JP2
JP3
Modem board