3
CAUTION
Handle all plug-in cards with extreme care. When
inserting or removing a card, keep the position of
the card at right angles to the OMM-2 board.
Otherwise, the plug-in card can damage or dis-
place other components. Never insert or remove a
plug-in card with power applied to the panel.
WIRING
(Refer to Figures 5 and 6)
All wiring must comply with
national and local codes.
1. A 2-conductor wire cable (P/N 600-192239) is
supplied with the ACM-1 module to use on the
OMM-2 TB1. Use this cable to connect 24 VDC
from P3 on the MMB to TB1 on the OMM-2
module. When using a P R-1, connect two
individual 14 AWG wires between the OMM-2 TB1
and P R-1 TB3-1 and TB3-2.
The terminals on OMM-2 TB1 are marked
+24V and R T.
On MMB P3, 1 is positive and 2 is negative.
On P R-1 TB3, 1 is positive and 2 is negative.
2. Assign plug-in cards to the card edge connectors
as determined above. Once the terminal block
related to each edge connector is wired, place
only the assigned plug-in card in that edge
connector.
3. Refer to the Installation Instructions listed in Table
1 for directions on wiring to the 22 position
OMM-2 terminal blocks and for attaching these
modules to the OMM-2 terminal blocks.
4.
If the system includes more than one OMM-2,
use
the 14-conductor ribbon cable (P/N 555-192155)
to connect P1 of the first OMM-2 to P2 of the
second OMM-2. If there is a third OMM-2,
connect P1 of the second OMM-2 to P2 of the third
OMM-2. No more than three OMM-2s can be
connected together when they are in an MME-3
enclosusre.
It may be necessary to reverse the module
mounting in the lower row of the MLE-6 enclosure
to insure that the 14-conductor cables that are
supplied can be assembled ( ee Figure 6).
5. Note that there are two 8-conductor cables. The
long 8-conductor cable (P/N 555-192243), comes
with the ACM-1. Use this cable for communications
and power from P4 of OMM-2 to either P6 of the
P R or to P6 of the MMB, whichever is present.
This cable is polarized. Observe polarity and DO
NOT U E EXCE IVE FORCE. The black tracer
on the cable indicates the position of pin 1.
6. If there is more than one OMM-2, use the short
8-conductor cable (P/N 555-190967) to connect P3
of the left-hand OMM-2 to P4 of the OMM-2 that is
to its right.
This cable is polarized. Observe polarity and DO
NOT U E EXCE IVE FORCE. The black tracer
on the cable indicates the location of pin 1. If there
is a third OMM, repeat this step.
For additional information on the MXL
System, refer to the MXL Manual, P/N
315-092036.
Figure 4
Mounting the OMM-2 Board
in the MSE-3L En losure
TABLE 1
INSTALLATION
INSTRUCTIONS PART
NUMBER
OCC-1
ASC-1
ASC-2
DMC-1
PLC-4
RCM-1
ZAC-30
ZC1-8B
ZC2-4AB
ZC2-8B
ZC3-4AB
ZCT-8B
315-090918
315-091263
315-092085
315-092692
315-093312
315-093878
315-092960
315-090910
315-091262
315-092116
315-092089
315-092105