RWD45U Controller Installation and Commissioning Guide Document Number 129-409
October 5, 2009
Siemens Industry, Inc. Page 7 of 13
Initial Program
Settings
(New Controller)
There are five levels of parameter setting (PS) modes: PS1 through PS4, and a
setpoint mode. Each PS has a set of default parameters, which can be changed during
commissioning.
When powered the first time, the controller will proceed to PS1 with default
application 10. See below for commissioning steps.
PS 1 – Application Settings
Select number of compressor stages
Select reversing valve output – On or Off during no demand
After completing PS1, the user has the option to progress to setpoint mode (only for new RWD) by waiting for
two seconds and default parameters will be accepted. If parameters PS2 through PS4 need to be adjusted,
press the +σbutton immediately to the next PS (see Commissioning Flowchart).
PS 2 – Input X1, X2 and X3
Enter X1 sensor calibration offset (Ni or Pt only)
±
Enter X1 active sensor range (0 to 10 Vdc only) -100 to 2400 32°F to 122°F
Select auxiliary sensor X2
Ni1000, Pt1000, 0 to 10 Vdc
Enter X2 sensor calibration offset (Ni or Pt only)
±
Enter X2 active sensor range (0 to 10 Vdc only)
32°F to 122°F
(0°C to 50°C)
Select sensor X3 (for Economizer sensor)
Ni1000, Pt1000, 0 to 10 Vdc
Enter X3 sensor calibration offset (Ni or Pt only)
±
Enter X3 active sensor range (0 to 10 Vdc only) -100 to 2400 32°F to 122°F
Select unit for X3 (for Independent control sensor) C, F, %, -----, or
X1 32°F to 122°F (0°C to
°
⇒
F
Ni1000, Pt1000, 0 to 10 Vdc
Enter X3 sensor calibration offset (Ni or Pt only)
±
Enter X3 active sensor range (0 to 10 Vdc only)
PS 3 – Digital, Auxiliary Function, Eco and Ind. (Y)
D/N, Filter Alarm, Alarm, on/off
Aux. Function = Setpoint reset
Setpoint reset start point, reverse acting
Setpoint reset sensor range
Setpoint reset end point, reverse acting
Setpoint reset sensor range
Setpoint reset shift
Setpoint reset sensor range
Setpoint reset start point, direct acting
Setpoint reset sensor range
Setpoint reset end point, direct acting
Setpoint reset sensor range
Setpoint reset shift
Setpoint reset sensor range
Aux. function = WIN SUM analog
Enter changeover setpoint for winter
Enter changeover setpoint summer
Enter changeover time delay, winter
⇔