Building Technologies 2017-11-21
Commissioning notes
For the pairing process between transmitter and receiver, refer to Operating
Instructions CB1B1428en, together with CB1B1431en for the RDD100.1RF, or
CB1B1432en for the RDE100.1RF.
The table below describes the behavior of the RDE-MZ6:
State of receiver State of LED
Power up (or reset) All 6 red and green LEDs flash alternately for 5
seconds and then extinguish.
Note: If the receiver zone was programmed before,
it will immediately change to constantly red.
Learning mode
Successful learning mode
The respective zone’s red and green LEDs flash
alternately.
The respective green LED will flash for 10 minutes
if learning was successful.
Signal ok and output status
change
For boiler or pump release
The respective zone’s green LED is constantly lit. If
the output state changes, the green LED will flash
for 3 seconds and then changes back to constantly
green.
Zone 6:
The green LED is lit when the relay is energized. It
extinguished when any other relay is deenergized.
Fails to receive wireless data If the respective zone of the RDE-MZ6 fails to
receive wireless data, the red LED will start to flash
after 125 minutes.
If RDE-MZ6 signal is recovered, it will return to the
previous LED state.
The specific zone has no ID The respective LED extinguishes.
Zone 6 of the receiver can be reconfigured for pump or boiler release. In that case,
the user is required to set the DIP switch inside the receiver housing to 1 (ON) (for
details, refer to Mounting Instructions CB1M1428xx).
The multizone receiver provides an override function (testing, emergency
operation). It allows the installer to override the relay of each zone to be
permanently energized, regardless of the wireless data received.
To activate the override function, press and hold the zone button for at least 10
seconds and release. The LED is constantly green and off once every 5 seconds,
indicating that the override function is enabled.
To disable the override function, press the zone button once.
Maintenance note
The multizone receiver is maintenance-free.
Disposal
The device is considered an electronic device for disposal in terms of the
European Directive 2012/19/EU and may not be disposed of as domestic
garbage.
∂Dispose of the device through channels provided for this purpose.
∂Comply with all local and currently applicable laws and regulations.
LED indication on
RDE-MZ6
Pump or boiler release
Override