6 / 8
Siemens Water detector QFP910 CE1N2732en
Building Technologies 18.05.2010
Technical data QFP910 – Water sensor
Cable length 2 m
Detector response time ≤2 seconds
Technical data QFP910 – RF transmitter
Battery type 2 x alkaline batteries LR6 (AA); 1.5 V
Battery life (capacity ≥2.5 Ah) 3 years (in "dry" state)
Radio Frequency 868 MHz, unidirectional
RF Range Typically 30 meters inside building
RF protocol KNX RF compatible
Screw terminals for cross-section of 0.1…1.5 mm2(connections interchangeable)
Cable length Max. 10 meters
Conformity to
EMC directive
- Immunity to interference, emissions
Low voltage directive
- Electrical safety
RTTE (Radio & Telecom. Equipment
- Radio communications
2004/108/EC
- EN 60730-1
2006/95/EC
- EN 60730-1
1999/5/EC
- EN 300220-2, EN 301489-1, EN 301489-3
Protection class III as per EN 60730
Housing IP40
2) as per EN 60529
Degree of pollution 2 as per EN 60730
The product environmental declaration
CE1E2732en contains data on
environmentally compatible product design
and assessments (RoHS compliance,
materials composition, packaging,
environmental benefit, disposal)
ISO 14001 (Environment)
ISO 9001 (Quality)
SN 36350 (Environmentally compatible
products)
RL 2002/95/EC (RoHS)
Refer to dimensions
Device packaged with inserts 0.28 kg
Plastic ASA+PC
White NCS S 0502-G
2) Fully mounted
Operation
EN60721-3-3
Transport
EN60721-3-2
Storage
EN60721-3-1
Environmental conditions Class 3K5 Class 2K3 Class 1K3
Temperature 0… +50 °C -25… +70 °C -20… +65 °C
Humidity 5…95 % r.h.
(non-condensing) <95 % r.h. 5…95 % r.h.
Mechanical conditions Class 3M2 Class 2M2 Class 1M2
Maximum elevation above sea level Min. 700 hPa corresponds to a maximum
of 3,000 meters above sea level
Water sensor
Power supply
RF
Electrical connection
Standards
Degree of protection
Environmental
compatibility
Dimensions
Weight
Housing material
Housing color
mbient conditions