Siemens OP121 User manual

Installation Instructions
Models OP121/OH121
Photoelectric Smoke Detector and Photo
Smoke/Thermal Detector
Figure 1 OP121 Photoelectric Figure 2 OH121 Photo Smoke
Smoke Detector Thermal Detector
These instructions are written in accordance with the
installation guidelines of NFPA No. 72, National Fire Alarm
Code, and CAN/ULC-S524, The Installation of Fire Alarm
Systems.
DETECTOR PLACEMENT
For a clear air, 0 to 4000 ft/min velocity application, use 30
foot center spacing (900 sq ft) from NFPA Standard 72
initiating devices chapter and CAN/ULC-S524 as a starting
point for a detector installation layout. This spacing, however,
is based on ideal conditions – smooth ceiling, no air
movement, and no physical obstructions. In some
applications, considerably less area is protected adequately
by each smoke detector. In all installations, place the
detector on the ceiling, a minimum of 6 inches from a side
wall, or on a wall, 6 inches from the ceiling.
Follow the drawings provided or approved by Siemens
Industry, Inc. or by its authorized distributors. See NFPA 72,
National Fire Alarm Code, initiating devices chapter for
additional guidance on special issues such as beamed
construction and high stockpiling.
TO AVOID NUISANCE ALARMS:
DO NOT locate the OP121/OH121 detector where
excessive smoke concentrations exist under normal
conditions, or in areas of prolonged high relative humidity
where condensation occurs.
DO NOT locate the OP121/OH121 detector next to an oil
burner, kitchen, or garage where exhaust fumes can trigger
an alarm. Other causes of false alarms are dust
accumulation, heavy concentrations of steam, heavy pipe
or cigar smoke, and certain aerosol sprays.
AIR CURRENTS
Before a detector can sense a fire, the products of com-
bustion or smoke must travel from the fire to the detector.
Since their travel is especially influenced by air currents,
consider the movement of air in the design of the system.
While combustion products tend to rise, drafts from hallways,
air diffusers, fans, etc., may help or hinder the travel of
combustion products to the detector. When positioning a
detector at a particular location, give consideration to
windows and doors, both open and closed, and to influencing
air movement. Never install a detector in the air stream of a
room air supply diffuser. It is better to position a detector
closer to an air return.
A6V10281367_b_en--
SPECIFICATIONS
Environmental
Operating Temperature (Model OP121): 320F (00C) to 1200F
(490C)
Operating Temperature (Model OH121): 320F (00C) to 1000F
(380C)
Humidity: Up to 95% RH, non condensing
Air Pressure: No effect
Air Velocity: 0 to 4000 ft/min. For open area protection and direct
air duct application.
Thermal Alarm Temp. (Model OH121): 1350F (570C)
UL listed with STI Mechanical Protection Guard Model: STI-9604
(see www.STI-USA.com for details)
Electrical
Voltage: 16-27 VDC
Ripple: 3V peak-to-peak
Supervisory Current: 100μA max
Alarm Current: 30-50mA
Start-up Time: 30 seconds max
DETECTOR WIRING
The OP121/OH121 should be connected as shown in Figure 3 using
the separate mounting base, Model DB-11. Follow the control panel
wiring connection drawing installed on the inside face of each
control panel cover. See DB-11 instruction, P/N 315-094193, for
base mounting. Duplicate wiring information is also in the
Installation, Operation, and Maintenance Manual provided with
every control panel. Note any limitations on the number of
detectors and restrictions on the use of remote devices
permitted for each circuit.
END OF
LINE
DEVICE
(NOTE
POLARITY
WHEN
APPLICABLE)
1a 1b
1b 1b
5
5
6
6
5
+
DB-1
1/DB-1
1E
[WITH REMOTE DEVICE(S)]
+
-
TO INITIATING
CIRCUIT OF
SIEMENS
INDUSTRY, INC.
CONTROL PANEL
(SEE CAUTION 1)
MULTIPLE REMOTE DEVICES
SEE REMOTE DEVICE INSTRUCTIONS
FOR WIRING DETAILS:
each detector/base may have up to 2 remote devices
with the followin g configurations and restrictions only:
If remote devices are supported by the initiating circuit,
DEVICE
RR-11
RLC-11, RLW-11
RSAC-11, RSAW-11
ADB-11
Device 1
Remote
R R -11
R R -11
R LC - 11 , RLW - 11
R LC - 11 , RLW - 11
Device 2
Remote
RLC-11, RLW-11
RSAC-11, RSAW-11
RSAC-11, RSAW-11
RLC-11, RLW-11
Restrictions
See Caution 2
See Caution 2
Wire from base to
RSAC-11/RSAW-11
to RL-11
INSTRUCTIONS
INSTALLATION
P/N 315-094924
P/N 315-094925
P/N 315-094926
P/N 315-096162
DB-1
1/DB-1
1E
[NO REMOTE DEVICE]
-
Figure 3 Installations and Wiring Diagram for OP121/OH121
Conventional Detectors
Siemens, Industry, Inc.
Building Technologies Division
WARNING: CONNECT DETECTOR ONLY TO CIRCUITS SPECIFIED IN DETECTOR
AND PANEL
LITERATURE OR SYSTEM MAY NOT OPERATE.
CAUTION:
1. Do not use looped wire under base
terminal 5. Break wire run to provide
supervision of connection.
2. When a remote relay is used to
control a critical system function, the
relay and its associated detector and
optional module(s) must be the ONLY
devices on the initiating circuit.
Figure 4 OP121 with TM121 Figure 5 TM121 Test Magnet
Test Magnet Placement on OP121
Figure 6 OH121 with TM121 Figure 5 TM121 Test Magnet
Test Magnet Placement on OH121
(after 3 minutes) when the green LED is a single blink every 10
seconds. The test mode provides a reduced test time period
and utilizes less concentration of test gas or aerosol.
Detector and control panel functionality can also be tested
using the TM121 test magnet as shown in Figure 4 for the
OP121 detector and Figure 6 for the OH121 detector. Place the
magnet in the specific area at the bottom of the detector that is
shown in Figure 5 for the OP121 detector and Figure 7 for the
OH121 detector for at least 5 seconds with the colored side
towards the centered LED. The detector will send an alarm to
the panel.
WARNING: Testing with the magnet only tests the circuit; it
does not test the detector’s sensing ability.
WARNING: The TM 121 test magnet is a strong magnet that
can be harmful to pacemaker wearers and to those with
medical implants. Keep the magnet away from magnetic
media such as credit cards and memory disks/chips.
CAUTION: UNDER NO CIRCUMSTANCES IS THE
DETECTOR HEAD TO BE DISASSEMBLED. NO REPAIRS
OR CLEANING SHOULD BE ATTEMPTED.
DO NOT PAINT
The detector/base plastic is marked DO NOT PAINT. This is
intended to prohibit painting during routine maintenance of
the occupancy which can affect proper operation of the
detector. COMPATIBLE CONTROL EQUIPMENT
Equipment
Compatibility Identifier Installation/Wiring
Instructions
SXL-EX
SZM (FS-250C)
P/N 315-095997-8
P/N 315-034850C-4
The detector model number is the compatibility identifier.
A6V10281367_b_en--
INSTALLATION / REMOVAL OF DETECTOR
TO INSTALL:
·Rotate detector counterclockwise while gently pressing
on it until the detector drops fully into base.
·Then rotate the detector clockwise until it stops
and locks
in place. Insert optional locking screw (
Order Model
LK-11).
TO REMOVE:
·Loosen locking screw, if installed. Then rotate the
detector counter clockwise until stop is reached.
·Pull detector out of base.
LED INDICATOR OPERATION
The OP121/OH121 contains an LED indicator capable of
flashing either one
of three distinct colors: green, yellow, or
red. The microprocessor based detector monitors the
following:
·Smoke in its sensing chamber
·Smoke sensitivity is within the range indicated on the
nameplate label (sensitivity verification)
·Internal sensors and electronics
Based on the results of these checks, the LED indicator
flashes as follows:
Flash
Color Condition Flash
Interval
(Seconds)
Green
Normal supervisory operation. Smoke
sensitivity is within rated limits. Double
blinking fir s t 3 min after power up or reset.
Singl e blinking after the first 3 min.
10
Yellow Detector is in trouble and needs replacement. 5
Red Alarm 2½
No
Flashes
Detector is not powered or replacement is
needed.
TESTING AND MAINTENANCE
To assure proper operation of the detector and control panel,
it
is required that both the Sensitivity test and the Functional
test
be conducted using the procedures outlined below.
SENSITIVITY TEST
The OP121/OH121 monitors its smoke sensitivity
automatically and requires no test equipment. A green flash
of
the detector LED about every 10 seconds indicates that the
smoke sensitivity is within its listed limits.
FUNCTIONAL TEST
To test the detector and control panel for functional operation,
use SIEMENS Test Gas, P/N 500-649750. Follow t
he
instructions on the gas canister label.
Smoke entry test mode: To test the detector for smoke entry,
place the detector into a test mode. The test mode condition
is
automatically started after the initial power up and after
every
reset for a period of 3 minutes. It is recommended that
a
control panel reset be performed after every smoke entry
test
is conducted to restart the 3 minute test period. The test
mode
is indicated when the green LED is double blinking every 10
seconds. A normal operational mode is indicated
Siemens Industry, Inc. Siemens Canada Limited
Building Technologies Division Building Technologies Division
Florham Park, NJ 2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

Other manuals for OP121

2

This manual suits for next models

1

Other Siemens Smoke Alarm manuals

Siemens TITANUS 3000 User manual

Siemens

Siemens TITANUS 3000 User manual

Siemens Cerberus DLO1191 User manual

Siemens

Siemens Cerberus DLO1191 User manual

Siemens PE-11C User manual

Siemens

Siemens PE-11C User manual

Siemens DELTA reflex 5TC1 290 Service manual

Siemens

Siemens DELTA reflex 5TC1 290 Service manual

Siemens Cerberus Pyrotronics PB-1191 User manual

Siemens

Siemens Cerberus Pyrotronics PB-1191 User manual

Siemens FDA241 User manual

Siemens

Siemens FDA241 User manual

Siemens DELTA reflex SD230N Service manual

Siemens

Siemens DELTA reflex SD230N Service manual

Siemens FCI2016-U1 Guide

Siemens

Siemens FCI2016-U1 Guide

Siemens FDL241-9 Guide

Siemens

Siemens FDL241-9 Guide

Siemens FDA2 1 Series User manual

Siemens

Siemens FDA2 1 Series User manual

Siemens OP121 User manual

Siemens

Siemens OP121 User manual

Siemens Sinteso Cerberus PRO User manual

Siemens

Siemens Sinteso Cerberus PRO User manual

Siemens BH17 7ER User manual

Siemens

Siemens BH17 7ER User manual

Siemens Cerberus DLO1191 Guide

Siemens

Siemens Cerberus DLO1191 Guide

Siemens AD2-C11 User manual

Siemens

Siemens AD2-C11 User manual

Siemens FDA2 Series Technical manual

Siemens

Siemens FDA2 Series Technical manual

Siemens FDOOT241-9 User manual

Siemens

Siemens FDOOT241-9 User manual

Siemens TITANUS SuperSens User manual

Siemens

Siemens TITANUS SuperSens User manual

Siemens Cerberus DO1101A-Ex Parts list manual

Siemens

Siemens Cerberus DO1101A-Ex Parts list manual

Siemens DELTA reflex SD230N Service manual

Siemens

Siemens DELTA reflex SD230N Service manual

Siemens DELTA Reflex SD9 Service manual

Siemens

Siemens DELTA Reflex SD9 Service manual

Siemens FDOT421 User manual

Siemens

Siemens FDOT421 User manual

Siemens OP121 User manual

Siemens

Siemens OP121 User manual

Siemens OP921 User manual

Siemens

Siemens OP921 User manual

Popular Smoke Alarm manuals by other brands

Xtralis XAS-2-US Product guide

Xtralis

Xtralis XAS-2-US Product guide

Brakel MSD 523 manual

Brakel

Brakel MSD 523 manual

Firex PAT installation manual

Firex

Firex PAT installation manual

NEAT Electronics SMOKE user manual

NEAT Electronics

NEAT Electronics SMOKE user manual

Kidde P9050 user guide

Kidde

Kidde P9050 user guide

Ei Electronics Ei141 Ionisation User instructions

Ei Electronics

Ei Electronics Ei141 Ionisation User instructions

Honeywell DFS8MS manual

Honeywell

Honeywell DFS8MS manual

PNI A023LR user manual

PNI

PNI A023LR user manual

Kidde P9040 user guide

Kidde

Kidde P9040 user guide

System Sensor 2251-COPTIR Installation and maintenance instructions

System Sensor

System Sensor 2251-COPTIR Installation and maintenance instructions

Tanda TXC3100 Installation and operation manual

Tanda

Tanda TXC3100 Installation and operation manual

ADEMCO 5192CP Installation and maintenance instructions

ADEMCO

ADEMCO 5192CP Installation and maintenance instructions

Honeywell FireLite BEAM355 Installation and maintenance instructions

Honeywell

Honeywell FireLite BEAM355 Installation and maintenance instructions

Gentex 7109CS installation instructions

Gentex

Gentex 7109CS installation instructions

FireAngel THERMISTEK HT-630 user manual

FireAngel

FireAngel THERMISTEK HT-630 user manual

Radal Technology CSA-POD24 Product installation guide

Radal Technology

Radal Technology CSA-POD24 Product installation guide

Firex FXW-R user manual

Firex

Firex FXW-R user manual

FireAngel ST-620 Thermoptek user manual

FireAngel

FireAngel ST-620 Thermoptek user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.