Parts List
1 - TPS3 03 DC suppressor including 3’ (~1m) conductors
1 - Mounting L bracket
1 - 3/4” conduit nut
2 - Panhead mounting screws
1 - Data Sheet
1 - Installation Sheet (this document)
Table2: Specifications
Specifications
Temperature Operating -40oC (-40oF) to 65oC (+149oF)
Temperature Storage -55oC (-67oF) to 65oC (+149oF)
Wire Size & Installation
Torque
8 AWG; 25 lb - in
6 AWG (Ground); 35 lb - in
NEMA 250 Enclosure Rating Type 4X with appropriate
sealing & sealing condulets
Simplified Explanation of Operation
SPDs sense overvoltage and create a momentary short circuit to redirect
harmful surge energy to earth ground. They reset automatically and
wait for the next surge. This is similar to the pressure relief valve on
a water heater: pressure goes up, valve opens to relieve pressure
and then resets. In an electrical system, an SPD senses overvoltage,
shorts temporarily sending energy to ground and then resets. SPDs
are capable of repeating this function thousands of times.
TPS3 03 DC includes internal overcurrent protection
Supplemental overcurrent protection is not required to protect this SPD.
The TPS3 03 DC models listed above have demonstrated 100kA Short
Circuit Current Ratings (SCCR) including leads on DC power systems.
(See UL Label markings on each SPD or see Data Sheet for specs.)
Follow all applicable codes, which generally require that connecting
conductors have overcurrent protection. Based on the SPD’s #8
conductor, we recommend an immediate upstream overcurrent
protection device rated not greater than 40A. A 40A or smaller circuit
breaker or fuse could serve as a disconnect switch and provide NEC®
or CEC imposed short circuit protection to the conductors.
Similar TPS3 03 DC models have demonstrated 200kA Short Circuit
Current Ratings (SCCR) including leads on AC power systems and have
been rated for Type 1 applications (NEC® Article 285).
This device features internal overcurrent and overtemperature
protection that will disconnect effected surge suppression components
at the end of their useful life, but will maintain power to the load – now
unprotected. If this situation is undesirable for the application, follow
these instructions for replacing the device. TPS3 03 DC is ultrasonically
welded closed and contains no user serviceable parts.
Voltage Rating & Application
Before installing SPD, verify by nameplate voltage or model number
that it has the same voltage rating as the power distribution system.
If unsure, call Siemens TPS Tech Support at 1.888.333.3545 before
proceeding. The SPDs specifier or user should be familiar with the
configuration and arrangement of the power distribution system. The
system is defined by how the secondary windings of the transformer
supplying the service entrance main or load are configured. This
includes whether or not the transformer windings are referenced to
earth via a grounding conductor. The system configuration is not based
on how any specific load or equipment is connected to a particular
power distribution system. SPDs should be installed per the distribution
system, not per a load or motor’s wiring connection.
Figure 2: Dimensions and Weight
Figure 3: Mounting options
• 3/4” pipe nipple (conduit nut included)
• Standard 35mm DIN-rail (not included)
L-bracket tightens onto DIN-rail
• Standard flat mounting surface
Attach L-bracket to surface via mounting holes
3.26”3.26”
1.15”
4.13”
3/4”-14
Sized for std 35mm DIN-Rail
3.31”3.57”
Weight: 1.60 lbs
(0.73 kg)
Bracket Mount
for at surfaces
Std. 3/4”-14 Nipple DIN-rail Mount
(rail not incl.)