
2 / 14
Siemens RDG40..KN Room thermostats with KNX communications CE1N3192en
Building Technologies 2017-11-21
Use
The RDG40..KN room thermostats are designed for the following types of system:
VAV systems via On/Off or modulating control outputs or KNX LTE-Mode:
∂Single-duct system
∂Single-duct system with electric heater
∂Single-duct system and radiator/floor heating
∂Single-duct system with heating/cooling coil
The room thermostats are delivered with a fixed set of applications.
The required application is selected and activated during commissioning using one
of the following tools:
∂Synco ACS
∂ETS
∂Local DIP switch and HMI
Functions
∂Room temperature control via built-in temperature sensor or external room
temperature/return air temperature sensor
∂Indoor air quality control via external CO2sensor (DC 0…10 V, KNX LTE- or S-
Mode) (RDG405KN)
∂Changeover between heating and cooling mode (automatically via local sensor
or bus, or manually)
∂Selection of applications via DIP switches or commissioning tool (ACS790, ETS)
∂Parameter download with commissioning tool (ACS, ETS)
∂Selection of operating mode via operating mode button on the thermostat
∂Temporary Comfort mode extension
∂Minimum and maximum limitation of room temperature setpoint
∂Minimum and maximum limitation of air flow signal (selectable via ETS)
∂External CO2sensor, DC 0…10 V; 0…2000 ppm (RDG405KN)
∂External CO2sensor, KNX; 0…5000 ppm (RDG405KN)
∂Button lock (automatic or manual)
∂2 multifunctional inputs, freely selectable for:
,Operating mode switchover contact (keycard, window contact, etc.)
(RDG400KN)
,Window contact switches operating mode to Protection (RDG405KN)
,Presence detector switches operating mode to Comfort (RDG405KN)
,Changeover sensor for automatic heating/cooling mode
,External room temperature or return air temperature sensor
,Dewpoint sensor
,Electric heater enable
,Faults
,Monitor input for temperature sensor or switch status
∂1 input DC 0…10 V for external sensor and feedback of air damper position
∂Optimization of pressure control using …
,feedback of air damper position and current air flow value via KNX bus,
,or feedback of air damper position via DC 0...10 V input
∂Floor heating temperature limit
∂Reloading factory settings for commissioning and control parameters
∂KNX bus (terminals CE+ and CE-) for communication with Synco or KNX
compatible devices
∂Display of outside temperature or time of day via KNX bus