I. INSTALLATION TECHNOLOGY –RIGID WALL
a. Make an opening in the wall with the 100 [mm] (acceptable 80 ÷ 120 [mm]) greater than the nominal
dimensions of the fire damper = B+100 and H+100.
b. Put the closed fire damper into the installation opening on depth marked by undercuts on the damper body
(dimension 60 mm), from one side fix it with suspension Z1, and from other side fix it to the ventilation duct
suspended on Z2 suspension.
c. After setting the fire damper as described, fill the gap between the fire damper and the wall with cement,
cement-lime mortar, concrete, or PROMASTOP MG III of production of the PROMAT company.
d. After 48 hours from the installation, the suspensions and supports used during installation of fire damper, may
be removed.
ATTENTIONS:
▪Carry out the installation in protective clothing, (gloves, glasses, helmet),
▪Pay attention at the sharp edges of the sheets,
▪Damper Baffle axis must be in horizontal or vertical position after montage
▪Damper cannot be formwork for wall
▪Ventilations duct should be installed that they cannot put any load on the damper, their suspension must
ensure their full load capacity.
▪The suspensions of the ventilation duct connected with the damper battery must be done according to
instruction manufacturer of ventilation ducts
▪In place of suspensions Z1 and Z2, which are installed for the time of assembly of the damper and in place
of mortar binding it can be used mounting brackets, paying attention to the immobilization of the damper.
Figure 1.Installation method of fire dampers KWP-O in rigid wall