SMAY WKZ-O User manual

Page 1z 5
IM –WKZ-O
Version: 1.00
Edited: 19.05.21
SMAY Sp. z o.o. / ul. Ciepłownicza 29 / 31-587 Kraków
tel. +48 12 680 20 80 / e-mail: [email protected]
www.smay.eu
Fire Ventilation Zone
INSTALLATION MANUAL
WKZ-O
Fire Dampers
Page 2z 5
IM –WKZ-O
Version: 1.00
Edited: 19.05.21
2434
SMAY Sp. z o.o.
21
2434-CPR-0205
DoP: 031-CPR-2021
EN 15650:2010
Fire damper
Type: WKZ-O
Nominal activation
conditions/sensitivity:
Closure/opening during test at the
right moment and in allowable
time
Pass
Response time/closure time:
Pass
Operational relisbility:
10 000 cycles - pass
Fire resistance:
- Fire integrity - E
- Fire insulation - l
- Smoke leakage - S
- Mechanical stability (under E)
- Cross-section preservation
(under E)
EI 240 (vei↔o) S
Durability:
- response delay
- operational reliability
Pass
Pass
Page 3z 5
IM –WKZ-O
Version: 1.00
Edited: 19.05.21
Version: 1.00
SMAY reserves the right to modify this document.
Contents
1. DEVICE INSTALLATION INSTRUCTION...................................................................................................... 4
2. INSTALLATION TECHNOLOGY –RIGID WALL STRUCTURE ........................................................................ 5
Page 4z 5
IM –WKZ-O
Version: 1.00
Edited: 19.05.21
1. DEVICE INSTALLATION INSTRUCTION
Before installing the fire damper check it for damage during transport or storage.
Check if the damper is able to open and close (full open and close position). In the case of
WKZ-O dampers open the damper with the actuator key. Full opening and closing shall be smooth (not
irregular). Do not pull the damper blade in order to open/close the damper. It may cause permanent
damage to the device, which is not covered by the warranty.
Before the installation verify the gap between the bottom blade and the inside part of the body
under the blade and also between upper blade and the inside part of the body above the blade. The
gap size can not be less than 4 mm.
Before the installation secure the damper with a foil or other material to protect it against dirt
and consequently damage to the elements of the damper.
To maintain EIS240 declared resistance, insulation and smoke leakage, the damper should be
mounted in walls, which were tested and rated as EI240.
It is acceptable to use WKZ-O dampers in walls with other fire resistance rating but in such a
case it should be kept in mind that EI fire resistance rating of the whole WKZ-O damper installation is
equal to the fire resistance rating of the lowest rated element of the system.
Ducts made of flammable or non-flammable materials can be connected to the fire damper. The
ducts must be installed in such a way that, in the event of fire, they do not transfer the load to the fire
damper. Duct lengthening in the event of fire can be compensated by supports and elbows.
NOTE: The distance between fire dampers and between fire dampers and structural members must be
provided in accordance with EN 1366-2 test standard:
a) min. 200 mm between the fire dampers installed in separate ventilation duct systems,
b) min. 75 mm between the fire damper and the structural element (wall/ceiling).
Page 5z 5
IM –WKZ-O
Version: 1.00
Edited: 19.05.21
2. INSTALLATION TECHNOLOGY –RIGID WALL STRUCTURE
1. Make an opening in the wall - 230 [mm] (acceptable 210 ÷ 250 [mm]) greater than the dimension
B and 100 [mm] (acceptable 80 ÷ 120 [mm]) greater than the dimension H, i.e. B+230 i H+100.
2. Insert the closed damper into the assembly opening and support or suspend it so that the
actuator cover on the side of the thermal release is flush with the wall surface. The damper
should be protected against possible undesirable stresses, which could lead to deflection of the
body, e.g. by using assembly struts.
3. After setting the damper as described, fill the space above and below the actuator housing with
the native material of the wall, and then fill the gap between the damper and the wall with
cement mortar, cement-lime mortar or concrete.
4. After the mortar has dried (approx. 48 hours), remove the struts, supports or suspensions which
were used to install the damper. Check the correct operation of the damper, then leave the
damper in the open position.
5. Secure the fire passage with a GKF 15x150 [mm] board band on both sides of the building
partition, then cover the flanges with PROMASTOP-CC Liquid or PROMASTOP-E Coating.
Fig. 1. Assembly diagram of the WKZ-O fire damper in rigid wall structures with a horizontal axis of the blades
rotation.

Other SMAY Fire And Smoke Damper manuals

SMAY KTM User manual

SMAY

SMAY KTM User manual

SMAY KWP-L Guide

SMAY

SMAY KWP-L Guide

SMAY WKP-O User manual

SMAY

SMAY WKP-O User manual

SMAY WKP-O Guide

SMAY

SMAY WKP-O Guide

SMAY KWP-P-E Guide

SMAY

SMAY KWP-P-E Guide

SMAY WKP-P User manual

SMAY

SMAY WKP-P User manual

SMAY KWP-L Guide

SMAY

SMAY KWP-L Guide

SMAY KTS-O-E User manual

SMAY

SMAY KTS-O-E User manual

SMAY KWP-O-E User manual

SMAY

SMAY KWP-O-E User manual

SMAY SCD User manual

SMAY

SMAY SCD User manual

SMAY CDH-F User manual

SMAY

SMAY CDH-F User manual

SMAY KTS User manual

SMAY

SMAY KTS User manual

SMAY KWP-L User manual

SMAY

SMAY KWP-L User manual

SMAY WKP-P User manual

SMAY

SMAY WKP-P User manual

SMAY WKP User manual

SMAY

SMAY WKP User manual

SMAY KWP-O-E-EX User manual

SMAY

SMAY KWP-O-E-EX User manual

Popular Fire And Smoke Damper manuals by other brands

KOOLAIR CEVH Mounting instructions

KOOLAIR

KOOLAIR CEVH Mounting instructions

Advanced Air 0160 Series quick start guide

Advanced Air

Advanced Air 0160 Series quick start guide

Mandik FDML Technical documentation

Mandik

Mandik FDML Technical documentation

Swegon REACT Pa Instructions for use

Swegon

Swegon REACT Pa Instructions for use

Greenheck CRD-300WT Installation, operation and maintenance manual

Greenheck

Greenheck CRD-300WT Installation, operation and maintenance manual

Ace FYN-N1 Operating and mounting instructions

Ace

Ace FYN-N1 Operating and mounting instructions

Trox Technik FKR-EU Supplementary Operating Manual

Trox Technik

Trox Technik FKR-EU Supplementary Operating Manual

SOLID AIR FDC25 manual

SOLID AIR

SOLID AIR FDC25 manual

SOLID AIR WH45 Series Maintenance and use manual

SOLID AIR

SOLID AIR WH45 Series Maintenance and use manual

Emerson Enardo EN FVFA Series instruction manual

Emerson

Emerson Enardo EN FVFA Series instruction manual

NuTone RDFUWT installation guide

NuTone

NuTone RDFUWT installation guide

Lindab RECTANGULAR Series Installation booklet

Lindab

Lindab RECTANGULAR Series Installation booklet

mercor mcr WIP PRO Series Technical manual

mercor

mercor mcr WIP PRO Series Technical manual

Honeywell TrueZONE EARD Series installation instructions

Honeywell

Honeywell TrueZONE EARD Series installation instructions

dalap ELIS user manual

dalap

dalap ELIS user manual

Greenheck ABD-Z2 Installation, operation and maintenance manual

Greenheck

Greenheck ABD-Z2 Installation, operation and maintenance manual

JRClancy 016-410L installation instructions

JRClancy

JRClancy 016-410L installation instructions

System air F-B90 user manual

System air

System air F-B90 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.