SMAY SCD User manual

Fire ventilation zone
Operation and Maintenance Manual
SCD Smoke Dampers
SCD
SMOKE DAMPERS

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 2 of 81
CONTENTS
1. INTRODUCTION.........................................................................................................................4
2. FORMAL AND LEGAL ASPECTS OF INTRODUCING SCD SMOKE DAMPERS INTO
THE MARKET .............................................................................................................................4
3. INTENDED USE AND PRODUCT CLASSIFICATION ...........................................................4
4. TECHNICAL DESCRIPTION OF PRODUCTS .........................................................................8
4.1.DESCRIPTION/TYPES.........................................................................................................8
4.2.SINGLE LEAF DAMPERS –DIMENSIONS.....................................................................10
4.3.DOUBLE LEAF DAMPERS –DIMENSIONS...................................................................14
4.4.MANUFACTURING VERSIONS.......................................................................................16
4.5.DAMPER WEIGHTS...........................................................................................................17
4.6.DRIVE SELECTION ...........................................................................................................20
4.7.SMOKE DAMPERS WITH THE SCD-1-W ROOF HATCH FUNCTION .......................32
4.8.OPTIONAL ACCESSORIES...............................................................................................33
4.8.1.WIND DEFLECTORS................................................................................................33
4.8.2.KA ANTI-BURGLAR BARS.....................................................................................34
4.8.3.KZU ANTI-FALL GRATES ......................................................................................34
5. DRIVES AND CONTROL.........................................................................................................35
5.1.PNEUMATIC DRIVES........................................................................................................35
5.1.1.CONFIGURATIONS..................................................................................................35
5.1.2.PNEUMATIC ACTUATORS.....................................................................................37
5.1.3.THERMAL TRIP........................................................................................................39
5.1.4.THERMAL FUSES.....................................................................................................43
5.1.5.CO2CYLINDERS (CARTRIDGES)..........................................................................43
5.1.6.AK ALARM BOXES..................................................................................................44
5.1.7.PLZ VENTILATION BOXES....................................................................................48
5.1.8.ELECTRIC VENTILATION ACTUATORS.............................................................50
5.1.9.PNEUMATIC SYSTEM.............................................................................................53
5.2.ELECTRIC DRIVES............................................................................................................54
5.2.1.CONFIGURATION....................................................................................................54
5.2.2.ELECTRIC ACTUATORS.........................................................................................55
5.2.3.CONTROL PANEL....................................................................................................58
6. SYSTEM EQUIPMENT.............................................................................................................65
6.1.WRS 2B WEATHER CONTROL PANEL..........................................................................65
6.2.ACCESSORIES OF THE WEATHER STATION..............................................................67

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 3 of 81
6.3.OSD63 SMOKE AND HEAT DETECTOR........................................................................68
6.4.SA-K6 SOUNDER...............................................................................................................69
6.5.SO-PD11 OPTICAL INDICATOR......................................................................................70
6.6.RT 2 EMERGENCY PUSH BUTTON................................................................................70
6.7.VENTILATION PUSH BUTTON.......................................................................................71
7. DELIVERY/TRANSPORT.........................................................................................................72
8. INSTALLATION CONDITIONS ..............................................................................................72
8.1.GENERAL GUIDELINES...................................................................................................72
8.2.EXAMPLES OF MOUNTING SCD SMOKE DAMPERS ON TYPICAL ROOFS..........76
8.3.MARKING ON INSTALLED DAMPERS (PUT INTO OPERATION)............................77
9. ENTRY INTO SERVICE ...........................................................................................................78
10. ROUTINE MAINTENANCE INSTRUCTIONS .......................................................................78
11. DAMPERS CLASSIFICATION FOR REPAIR.........................................................................79
12. WARRANTY TERMS................................................................................................................79

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 4 of 81
1. INTRODUCTION
The purpose of this Operation and Maintenance Manual is to familiarize the user with
the intended use, design, operating principle, installation, periodic maintenance and
operation of the product. Observing instructions contained in the Operation and
Maintenance Manual will ensure correct operation of the device throughout its entire
lifetime.
SCD smoke dampers together with the control system may constitute the
configuration of several components made by various Manufacturers. Each component is
delivered along with the Manufacturer’s Manual. Both – assembly companies and the User
–are obliged to read those Manuals and apply them with regard to installation, operation
and maintenance.
2. FORMAL AND LEGAL ASPECTS OF INTRODUCING SCD SMOKE DAMPERS
INTO THE MARKET
Certificate of Constancy of Performance No. 1438-CPR-0503, specified in PN-
EN 12101-2:2005, is a legal basis for using SCD smoke dampers.
3. INTENDED USE AND PRODUCT CLASSIFICATION
SCD smoke dampers are used in public buildings, warehouses, production facilities
etc. They are designed for mounting onto flat roofs slanted at not more than 15°.
The main function of SCD smoke dampers is extracting smoke and hot toxic gases
occurring during fire in the under-ceiling space.
SCD smoke dampers by Smay Sp. z o. o. have openable leafs filled with translucent
material. Therefore, they additionally function as spot skylights. The third function of SCDs,
when appropriate tooling is used, is cyclic ventilation.
In each and every case smoke extraction is the priority function of SCD smoke
dampers. SCDs make it possible to evacuate people and enable rescue services to
undertake appropriate intervention by keeping the lower areas of a building, including
escape routes, free of smoke. Smoke dampers reduce the thermal load of the building
structure by reconducting the heat created during a fire, and thus reducing material injury
caused by the fire.
Using SCD smoke dampers gives the possibility to lower the building fire protection
class, enlarge permissible fire zones and lengthen escape routes.
SCD smoke dampers are classified according to PN-EN 12101-2 criteria, with regard
to the following areas:
Reliability: double action, Re 1000,
Snow load: SL550 –SL 1000 (depending on the drive size and type),
Low temperature: T(00) –T(–25) (depending on the drive size and
type),
Wind load: WL 1500,
Resistance to high temperature: B 300,
Single leaf damper effective areas are presented in Table 1, and double leaf damper
effective areas –in Table 2.
It is possible to make the dampers in the version meeting the requirements of
the BROOF(t1) classification. The properties distinctive for the skylight function are
declared according to EN 1873:2014+A1:2016 requirements

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 5 of 81
Declared active areas for single leaf dampers
Position
Nominal
dimensions
SCD-1-P... damper with a straight base
SCD-1-S... damper with a sloping base
Base height [mm]
Base height [mm]
700
500
350
700
500
350
Deflectors
Deflectors
w [mm]
l
(hinges)
[mm]
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
Aa active area [m2]
Aa active area [m2]
1
1000
1000
0.69
0.68
0.66
0.68
0.67
0.66
2
1000
1200
0.83
0.80
0.79
0.80
0.80
0.79
3
1000
1300
0.87
0.86
0.87
0.87
0.86
4
1000
1400
0.94
0.91
0.94
0.94
0.92
5
1000
1500
1.02
1.01
0.98
1.01
1.01
0.99
6
1000
1600
1.07
1.04
1.07
1.07
1.06
7
1000
1700
1.16
1.14
1.11
1.14
1.14
1.12
8
1000
1800
1.22
1.19
1.17
1.21
1.21
1.19
9
1000
1900
1.25
1.24
1.25
1.25
1.25
10
1000
2000
1.36
1.32
1.30
1.32
1.32
1.32
11
1000
2200
1.47
1.45
1.41
1.45
1.45
1.43
12
1000
2300
1.54
1.52
1.47
1.52
1.52
1.50
13
1000
2400
1.61
1.58
1.54
1.56
1.56
1.51
1.54
14
1000
2500
1.68
1.65
1.60
1.63
1.63
1.55
1.60
15
1100
1100
0.83
0.81
0.80
0.82
0.81
0.80
16
1100
2000
1.47
1.45
1.41
1.45
1.45
1.45
17
1150
1150
0.91
0.89
0.87
0.90
0.89
0.87
18
1150
2000
1.54
1.52
1.47
1.52
1.52
1.52
19
1200
1200
0.98
0.96
0.94
0.98
0.96
0.95
20
1200
1500
1.22
1.19
1.17
1.21
1.21
1.19
21
1200
1700
1.39
1.35
1.33
1.37
1.37
1.35
22
1200
1800
1.47
1.43
1.38
1.45
1.45
1.43
23
1200
2000
1.61
1.58
1.54
1.58
1.58
1.58
24
1200
2200
1.77
1.72
1.69
1.74
1.74
1.72
25
1200
2300
1.85
1.79
1.77
1.82
1.82
1.79
26
1200
2500
2.01
1.95
1.92
1.98
1.95
1.86
1.92
27
1250
1250
1.06
1.05
1.02
1.06
1.05
1.03
28
1250
2500
2.09
2.03
1.97
2.06
2.03
1.94
2.03
29
1300
1300
1.15
1.13
1.10
1.15
1.13
1.12
30
1300
1500
1.33
1.29
1.27
1.31
1.31
1.29
* If the field is empty, a deflector is optional

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 6 of 81
Declared active areas for single leaf dampers
Position
Nominal
dimensions
SCD-1-P... damper with a straight base
SCD-1-S... damper with a sloping base
Base height [mm]
Base height [mm]
700
500
350
700
500
350
Deflectors
Deflectors
w [mm]
l
(hinges)
[mm]
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
Aa active area [m2]
Aa active area [m2]
31
1300
1600
1.41
1.37
1.33
1.39
1.39
1.37
32
1300
1800
1.57
1.54
1.50
1.57
1.57
1.54
33
1300
1900
1.65
1.63
1.58
1.65
1.65
1.63
34
1300
2000
1.74
1.69
1.66
1.72
1.72
1.72
35
1300
2200
1.92
1.86
1.83
1.89
1.89
1.86
36
1300
2500
2.15
2.11
2.05
2.15
2.11
2.02
2.11
37
1400
1400
1.33
1.29
1.27
1.33
1.31
1.29
38
1400
1500
1.43
1.39
1.34
1.41
1.41
1.39
39
1400
1800
1.69
1.64
1.61
1.69
1.69
1.66
40
1400
2000
1.88
1.82
1.76
1.85
1.85
1.85
41
1400
2500
2.31
2.28
2.21
2.31
2.28
2.31
2.14
2.28
42
1450
1450
1.43
1.39
1.35
1.43
1.41
1.39
43
1500
1500
1.53
1.49
1.44
1.53
1.51
1.49
44
1500
1700
1.71
1.66
1.63
1.71
1.71
1.68
45
1500
1800
1.81
1.76
1.70
1.81
1.81
1.78
46
1500
2000
2.01
1.95
1.89
1.98
1.98
1.98
47
1500
2200
2.18
2.15
2.08
2.18
2.18
2.15
48
1500
2300
2.28
2.24
2.17
2.28
2.28
2.24
49
1500
2500
2.48
2.44
2.36
2.48
2.44
2.48
2.29
2.44
50
1500
2700
2.67
2.59
2.55
2.67
2.59
2.67
2.43
2.63
51
1500
3000
2.97
2.88
2.79
2.97
2.88
2.97
2.66
2.93
52
1600
1600
1.72
1.66
1.64
1.74
1.72
1.69
53
1600
1700
1.82
1.77
1.71
1.82
1.82
1.80
54
1600
1800
1.93
1.87
1.81
1.93
1.93
1.90
55
1600
2000
2.11
2.08
2.02
2.14
2.11
2.11
56
1600
2200
2.32
2.29
2.22
2.36
2.32
2.29
57
1600
2300
2.43
2.36
2.32
2.47
2.39
2.43
2.32
2.39
58
1600
2500
2.64
2.56
2.52
2.68
2.60
2.64
2.44
2.60
59
1600
2700
2.85
2.76
2.72
2.89
2.76
2.85
2.59
2.81
60
1600
3000
3.12
3.07
2.98
3.22
3.02
3.17
2.78
3.12
61
1700
1700
1.94
1.88
1.82
1.97
1.94
1.91
62
1700
1800
2.05
1.99
1.93
2.05
2.05
2.02
63
1700
2000
2.24
2.18
2.14
2.28
2.24
2.24
64
1700
2200
2.47
2.39
2.36
2.51
2.47
2.43
2.47
65
1700
2300
2.58
2.50
2.46
2.62
2.54
2.58
2.46
2.58
66
1700
2500
2.81
2.72
2.64
2.85
2.76
2.81
2.59
2.81
* If the field is empty, a deflector is optional

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 7 of 81
Declared active areas for single leaf dampers
Position
Nominal
dimensions
SCD-1-P... damper with a straight base
SCD-1-S... damper with a sloping base
Base height [mm]
Base height [mm]
700
500
350
700
500
350
Deflectors
Deflectors
w [mm]
l
(hinges)
[mm]
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
Aa active area [m2]
Aa active area [m2]
67
1700
2700
3.03
2.94
2.85
3.08
2.94
3.03
2.75
2.98
68
1700
3000
3.32
3.26
3.16
3.42
3.21
3.37
2.96
3.32
69
1800
1800
2.14
2.07
2.04
2.20
2.17
2.14
70
1800
2000
2.38
2.30
2.23
2.41
2.38
2.38
71
1800
2200
2.61
2.53
2.46
2.65
2.61
2.53
2.61
72
1800
2300
2.73
2.65
2.57
2.77
2.69
2.73
2.61
2.73
73
1800
2500
2.97
2.88
2.79
3.02
2.88
3.02
2.75
2.97
74
1800
2700
3.16
3.11
3.01
3.26
3.11
3.26
2.92
3.21
75
1800
3000
3.51
3.46
3.35
3.62
3.40
3.62
3.13
3.56
76
1920
1900
2.41
2.33
2.26
2.48
2.44
2.41
77
1920
2000
2.53
2.46
2.38
2.61
2.57
2.53
78
1920
2200
2.79
2.70
2.62
2.87
2.75
2.83
2.70
2.79
79
1920
2300
2.91
2.83
2.74
3.00
2.87
2.96
2.78
2.91
80
1920
2500
3.12
3.07
2.98
3.26
3.07
3.22
2.93
3.17
81
1920
2700
3.37
3.32
3.21
3.53
3.32
3.47
3.06
3.42
82
1920
3000
3.74
3.69
3.57
3.92
3.63
3.86
3.28
3.80
* If the field is empty, a deflector is optional
Declared active areas for single leaf dampers
Position
Nominal
dimensions
SCD-2-P... damper with a straight base
SCD-2-S... damper with a sloping base
Base height [mm]
Base height [mm]
700
500
350
700
500
350
Deflectors
Deflectors
w [mm]
l
(hinges)
[mm]
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
Aa active area [m2]
Aa active area [m2]
1
1250
2500
2.09
2.03
1.97
2.16
2.13
2.06
2
1500
1500
1.53
1.49
1.42
1.44
1.55
1.42
1.53
1.35
1.51
3
1500
2500
2.51
2.44
2.36
2.51
2.59
2.44
2.55
2.36
2.48
4
1500
3000
3.02
2.93
2.84
3.11
3.02
3.06
2.88
2.97
5
1600
1600
1.74
1.69
1.61
1.64
1.77
1.59
1.74
1.51
1.72
6
1600
2500
2.68
2.60
2.52
2.68
2.76
2.56
2.72
2.44
2.64
7
1600
2800
3.00
2.91
2.82
3.00
3.09
2.91
3.05
2.78
2.96
8
1600
3000
3.22
3.12
3.02
3.31
3.17
3.26
3.02
3.17
9
1800
1600
1.90
1.96
1.90
1.81
1.81
1.99
1.73
1.96
1.61
1.93
10
1800
1800
2.14
2.20
2.04
2.14
1.98
2.04
2.04
2.24
1.94
2.20
1.85
2.17
11
1800
2500
2.97
3.02
2.84
2.93
2.75
2.84
2.93
3.11
2.79
3.06
2.66
2.97
* If the field is empty, a deflector is optional

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 8 of 81
Declared active areas for single leaf dampers
Position
Nominal
dimensions
SCD-2-P... damper with a straight base
SCD-2-S... damper with a sloping base
Base height [mm]
Base height [mm]
700
500
350
700
500
350
Deflectors
Deflectors
w [mm]
l
(hinges)
[mm]
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
no
yes*
Aa active area [m2]
Aa active area [m2]
12
1800
2800
3.33
3.38
3.18
3.28
3.07
3.18
3.33
3.48
3.18
3.43
3.02
3.33
13
1800
3000
3.56
3.62
3.40
3.51
3.29
3.40
3.56
3.73
3.40
3.67
3.24
3.56
14
2000
2000
2.60
2.72
2.48
2.64
2.40
2.52
2.52
2.76
2.36
2.72
2.16
2.68
15
2000
2400
3.12
3.26
2.98
3.12
2.88
3.02
3.02
3.31
2.88
3.26
2.69
3.22
16
2000
2500
3.25
3.35
3.10
3.25
3.00
3.15
3.15
3.45
3.00
3.40
2.80
3.30
17
2000
2800
3.64
3.75
3.47
3.64
3.36
3.53
3.58
3.86
3.42
3.81
3.19
3.70
18
2000
3000
3.90
4.02
3.72
3.90
3.60
3.78
3.84
4.14
3.66
4.08
3.48
3.96
19
2200
2200
3.10
3.29
2.95
3.19
2.86
3.05
3.00
3.34
2.76
3.29
2.52
3.24
20
2200
2400
3.38
3.59
3.22
3.43
3.12
3.33
3.27
3.64
3.06
3.59
2.80
3.54
21
2200
2500
3.52
3.69
3.36
3.58
3.25
3.47
3.41
3.80
3.19
3.74
2.97
3.63
22
2400
2400
3.63
3.92
3.46
3.80
3.34
3.63
3.46
3.97
3.23
3.92
2.94
3.86
23
2400
2500
3.78
4.08
3.60
3.90
3.42
3.78
3.60
4.14
3.36
4.08
3.06
4.02
24
2500
2500
3.94
4.25
3.75
4.13
3.56
4.00
3.69
4.31
3.44
4.25
3.13
4.19
25
2500
3000
4.73
5.03
4.50
4.88
4.20
4.80
4.50
5.18
4.20
5.10
3.83
4.95
26
3000
3000
5.49
6.03
5.13
5.94
4.77
5.85
4.95
6.21
4.50
6.12
4.05
5.94
* If the field is empty, a deflector is optional
4. TECHNICAL DESCRIPTION OF PRODUCTS
4.1. DESCRIPTION/TYPES
SCD smoke dampers are rectangular in cross-section. They are available as single or
double leaf. The dimension range is specified in Tables 4 and 5.
The opening angle of a single leaf damper is not less than 140°.
The opening angle of a double leaf damper is not less than 90°.
A profiled aluminium drainpipe is mounted on a straight or sloping base, made of
1.5 mm thick galvanised sheet metal. The purpose of the drainpipe is to drain the
condensation moisture created as the result of temperature difference on the inner surface
of the leaf. The drainpipe corners are sealed with silicone and secured with an aluminium
fitting.
The base is adapted for placing insulation material on its entire perimeter. It is
recommended to use mineral wool insulation, 50 mm thick. The insulation material should
be of A1 reaction-to-fire class and be characterised by high density (150 kg/m3 minimum)
and thermal insulation power (thermal resistance Ri = 1.25 m2∙K/W minimum).
Heat-transfer coefficient for the base insulated by means of 50 mm thick mineral wool
is U = 0.80 [W/m2K].
Moisture tightness is obtained by means of applying insulation with bituminous
materials or sheet-metal work, appropriate for the given roof structure.
The drainpipe is connected, alongside the longer side of the damper, by means of a
linear rack hinge, with an openable cover. The hinge is protected against unwanted

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 9 of 81
impurities by means of an aluminium cover. The cover frame is a one-piece item made of
specially designed aluminium profile, which makes it possible to mount porous
polycarbonate cover, 10, 16, 20 or 25 mm thick.
In the basic version Lexan LT2UV169X Opal White polycarbonate plate, 16 mm thick,
is used. Important properties of this material are presented in Table 3.
Grade-Color
Gauge
[mm]
Weight
(kg/m3)
Sound Red.
Value [dB]
U-Value
[W/m2K]
Hail
Impact
Test [m/se
c]
LT
D65 [%L
T]
DST [DS
T]
TST [%T
ST}
SHGC
LSGR
SC
LT2UV105R17
5
Clear
10
1.75
20
2.39
>21
65
61
62
0.62
1.05
0.72
Opal White
10
1.75
20
2.39
>21
60
58
59
0.59
1.02
0.68
SC IR Green
10
1.75
20
2.39
>21
48
34
48
0.48
1.08
0.56
LT2UV169X
Clear
16
2.5
21
1.77
>21
54
51
54
0.54
1.00
0.62
Opal White
16
2.5
21
1.77
>21
47
45
49
0.49
0.96
0.56
SC IR Green
16
2.5
21
1.77
>21
38
25
39
0.39
0.97
0.44
LT2UV209X
Clear
20
2.8
21
1.59
>21
53
50
53
0.53
1.00
0.61
Opal White
20
2.8
21
1.59
>21
47
46
50
0.50
0.94
0.57
SC IR Green
20
2.8
21
1.59
>21
37
25
39
0.39
0.97
0.44
LT2UV259X
Clear
25
3.0
22
1.40
>21
51
49
52
0.52
0.98
0.60
Opal White
25
3.0
22
1.40
>21
44
42
47
0.47
0.94
0.54
SC IR Green
25
3.0
22
1.40
>21
36
23
37
0.37
0.97
0.42
Explanations for the parameters presented in Table 1 are given in the original Manufacturer’s notation.
Light Transmission D65 (% LT) - Percentage of the incident visible light that passes through an object.
Direct Solar Transmission (%DST) - Percentage of incident solar radiation that passes directly through an
object.
Total Solar Transmission (%TST) - The percentage of incident Solar radiation transmitted by an object which
includes the direct Solar Transmission plus the part of the Solar Absorption reradiated inward.
Solar Heat Gain Coefficient (SHGC) - or g-value is the total solar energy that enters the interior of a building,
divided by 100.
Shading Coefficient (SC) –The ratio of the total solar radiation transmitted by a given material to that
transmitted by normal 3 mm glass, whose light transmission is 87%. SC=%TST/87.
Light to Solar Gain Ratio (LSGR) - The ratio between total light transmission (LT) and the total solar
transmission (TST).
The contact between the polycarbonate plate and the cover profile is sealed by
means of a EPDM profile gasket. The polycarbonate panel is pressured to the gasket by
means of an aluminium lock profile of the height appropriate to the panel thickness.
The airtightness is obtained by means of using a EPDM gasket mounted between the
cover and drainpipe profiles.
The aluminium profile shapes and dimensions are patented.
The whole damper is made with the use of mounting technologies, which may be
used both in a production plant and at a stand prepared at a building site, or directly on the
building roof. The dampers may be delivered as an easy-to-transport set of ideally matched
parts, with all the connecting members needed. The mounting procedure takes place on
the basis of a clearly presented manual, by means of standard fitting tools, without the
need to use a welder or a grinding machine.

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 10 of 81
It is possible to deliver completely assembled dampers. In this case, in each damper
with a pneumatic drive, in order to make it ready for operation, a thermal trip –delivered
separately –needs to be mounted and set. Deflectors are delivered separately as well.
Moreover, the delivery of assembled dampers requires individual agreements on
installation and insulation preparation.
Smoke Dampers with the SCD-1-W Roof Hatch Function
Smoke dampers with the roof hatch function, besides all functions of standard
dampers, also enable workers to get on the roof. They are made with a straight base only,
in two versions:
Version 1 –with a single electric actuator –for dimensions 1000 x 1000 and
1000 x 1200,
Version 2 –with two electric actuators –within the range from 1000 x 1300 to
1800 x 1800. Their detailed description is presented on page 22.
4.2. SINGLE LEAF DAMPERS –DIMENSIONS
1. Base unit
2. Leaf unit
3. Mechanical drive unit
Rys. 1. SCD-1-P... single leaf damper on a straight base
1. Base unit
2. Leaf unit
3. Mechanical drive unit
Rys. 2. SCD-1-S... single leaf damper on a sloping base
W
W1 = W + 134
H
W(A) = W - 200
W1 = W(A) + 134
W
H

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 11 of 81
Rys. 3. SCD-1-P... single leaf damper in open position
Distinctive dimensions of SCD-1... dampers are shown in Table 4.
Pos.
Nominal size
Dimensions in open position
Geometric area
AV [m2]
Cover weight [N]
w [mm]
l (hinges) [mm]
W open
[mm]
H open
[mm]
1
1000
1000
1880
670+h
1.00
190.0
2
1000
1200
1880
670+h
1.20
210.0
3
1000
1300
1880
670+h
1.3
215.0
4
1000
1400
1880
670+h
1.4
225.0
5
1000
1500
1880
670+h
1.5
240.0
6
1000
1600
1880
670+h
1.6
245.0
7
1000
1700
1880
670+h
1.70
250.0
8
1000
1800
1880
670+h
1.80
260.0
9
1000
1900
1880
670+h
1.9
330.0
10
1000
2000
1880
670+h
2.00
340.0
11
1000
2200
1880
670+h
2.20
370.0
12
1000
2300
1880
670+h
2.30
380.0
13
1000
2400
1880
670+h
2.4
375.0
14
1000
2500
1880
670+h
2.50
390.0
15
1100
1100
2060
740+h
1.21
205.0
16
1100
2000
2060
740+h
2.2
355.0
17
1150
1150
2150
770+h
1.32
215.0
18
1150
2000
2150
770+h
2.3
355.0
19
1200
1200
2235
800+h
1.44
230.0
20
1200
1500
2235
800+h
1.80
260.0
21
1200
1700
2235
800+h
2.04
270.0
H open
W open
W

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 12 of 81
Pos.
Nominal size
Dimensions in open position
Geometric area
AV [m2]
Cover weight [N]
w [mm]
l (hinges) [mm]
W open
[mm]
H open
[mm]
22
1200
1800
2235
800+h
2.16
280.0
23
1200
2000
2235
800+h
2.40
380.0
24
1200
2200
2235
800+h
2.64
400.0
25
1200
2300
2235
800+h
2.76
410.0
26
1200
2500
2235
800+h
3.00
430.0
27
1250
1250
2315
830+h
1.56
235.0
28
1250
2500
2315
830+h
3.12
430.0
29
1300
1300
2410
865+h
1.69
245.0
30
1300
1500
2410
865+h
1.95
265.0
31
1300
1600
2410
865+h
2.08
275.0
32
1300
1800
2410
865+h
2.34
290.0
33
1300
1900
2410
865+h
2.47
375.0
34
1300
2000
2410
865+h
2.6
385.0
35
1300
2200
2410
865+h
2.86
415.0
36
1300
2500
2410
865+h
3.25
440.0
37
1400
1400
2595
930+h
1.96
265.0
38
1400
1500
2595
930+h
2.1
275.0
39
1400
1800
2595
930+h
2.52
300.0
40
1400
2000
2595
930+h
2.8
405.0
41
1400
2500
2595
930+h
3.5
460.0
42
1450
1450
2690
965+h
2.1
275.0
43
1500
1500
2765
995+h
2.25
290.0
44
1500
1700
2765
995+h
2.55
310.0
45
1500
1800
2765
995+h
2.70
320.0
46
1500
2000
2765
995+h
3.00
430.0
47
1500
2200
2765
995+h
3.30
450.0
48
1500
2300
2765
995+h
3.45
460.0
49
1500
2500
2765
995+h
3.75
480.0
50
1500
2700
2765
995+h
4.05
500.0
51
1500
3000
2765
995+h
4.50
530.0
52
1600
1600
2940
1060+h
2.56
310.0
53
1600
1700
2940
1060+h
2.72
320.0
54
1600
1800
2940
1060+h
2.88
330.0
55
1600
2000
2940
1060+h
3.20
440.0
56
1600
2200
2940
1060+h
3.52
470.0
57
1600
2300
2940
1060+h
3.68
480.0
58
1600
2500
2940
1060+h
4.00
500.0
59
1600
2700
2940
1060+h
4.32
520.0
60
1600
3000
2940
1060+h
4.80
550.0

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 13 of 81
Pos.
Nominal size
Dimensions in open position
Geometric area
AV [m2]
Cover weight [N]
w [mm]
l (hinges) [mm]
W open
[mm]
H open
[mm]
61
1700
1700
3120
1125+h
2.89
330.0
62
1700
1800
3120
1125+h
3.06
340.0
63
1700
2000
3120
1125+h
3.40
460.0
64
1700
2200
3120
1125+h
3.74
490.0
65
1700
2300
3120
1125+h
3.91
500.0
66
1700
2500
3120
1125+h
4.25
520.0
67
1700
2700
3120
1125+h
4.59
540.0
68
1700
3000
3120
1125+h
5.10
570.0
69
1800
1800
3295
1190+h
3.24
350.0
70
1800
2000
3295
1190+h
3.60
480.0
71
1800
2200
3295
1190+h
3.96
510.0
72
1800
2300
3295
1190+h
4.14
520.0
73
1800
2500
3295
1190+h
4.50
540.0
74
1800
2700
3295
1190+h
4.86
560.0
75
1800
3000
3295
1190+h
5.40
590.0
76
1920
1900
3505
1265+h
3.61
480.0
77
1920
2000
3505
1265+h
3.80
500.0
78
1920
2200
3505
1265+h
4.18
530.0
79
1920
2300
3505
1265+h
4.37
540.0
80
1920
2500
3505
1265+h
4.75
560.0
81
1920
2700
3505
1265+h
5.13
580.0
82
1920
3000
3505
1265+h
5.70
610.0

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 14 of 81
4.3. DOUBLE LEAF DAMPERS –DIMENSIONS
1. Base unit
2. Leaf unit
3. Mechanical drive unit
Rys. 4. SCD-2-P... double leaf damper on a straight base
1. Base unit
2. Leaf unit
3. Mechanical drive unit
Rys. 5. SCD-2-S... double leaf damper on a sloping base
H
H
W(A) = W - 200
L(A) = L - 200
L
W
W
L

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 15 of 81
Rys. 6. SCD-2-P... double leaf damper in open position
Distinctive dimensions of SCD-2... dampers are shown in Table 5.
Pos.
Nominal size
Dimensions in open position
Geometric area
AV [m2]
Weight of a
single
cover [N]
w [mm]
l (hinges) [mm]
W open [mm]
h open [mm]
1
1250
2500
1710
630+h
3.13
320
2
1500
1500
1960
830+h
2.25
210
3
1500
2500
1960
830+h
3.75
350
4
1500
3000
1960
830+h
4.50
390
5
1600
1600
2060
880+h
2.56
220
6
1600
2500
2060
880+h
4.00
360
7
1600
2800
2060
880+h
4.48
380
8
1600
3000
2060
880+h
4.80
400
9
1800
1600
2260
880+h
2.88
230
10
1800
1800
2260
980+h
3.24
250
11
1800
2500
2260
980+h
4.50
370
12
1800
2800
2260
980+h
5.04
400
13
1800
3000
2260
980+h
5.40
420
14
2000
2000
2460
1080+h
4.00
340
15
2000
2400
2460
1080+h
4.80
380
16
2000
2500
2460
1080+h
5.00
390
17
2000
2800
2460
1080+h
5.60
420
H open
W open
W

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 16 of 81
18
2000
3000
2460
1080+h
6.00
440
19
2200
2200
2660
1180+h
4.84
380
20
2200
2400
2660
1180+h
5.28
400
21
2200
2500
2660
1180+h
5.50
410
22
2400
2400
2860
1280+h
5.76
420
23
2400
2500
2860
1280+h
6.00
430
24
2500
2500
2960
1330+h
6.25
440
25
2500
3000
2960
1330+h
7.50
480
26
3000
3000
3460
1580+h
9.00
530
4.4. MANUFACTURING VERSIONS
Damper type
Main drive
Base type
Base height
Deflectors
Function
Operating mode
Operating
mode
Thickness of PC
filling
straight
sloping
350
500
700
Yes
No
smoke extraction
only
smoke extraction
+ electric
ventilation
smoke extraction
+ pneumatic
ventilation
Open
Open-close
10
16
20
25
Single leaf
pneumatic
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
electric
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Double leaf
pneumatic
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
electric
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 17 of 81
4.5. DAMPER WEIGHTS
Approximate weights* of single leaf dampers are shown in Table 6
w [mm]
L [mm]
(hinges)
Base height 350 mm
Base height 500 mm
Base height 700 mm
St-Pn
St-El
Sl-Pn
Sl-El
St-Pn
St-El
Sl-Pn
Sl-El
St-Pn
St-El
Sl-Pn
Sl-El
1000
1000
73.7
76.1
65.90
68.30
84.40
86.80
75.90
78.30
98.70
101.1
89.20
91.60
1000
1200
78.9
81.3
71.10
73.50
90.40
92.80
81.80
84.20
105.6
108.0
96.10
98.50
1000
1300
81.5
83.9
72.70
75.10
93.30
95.70
83.70
86.10
109.0
111.4
98.50
100.9
1000
1400
84.1
86.5
75.20
77.60
96.20
98.60
86.70
89.10
112.4
114.8
101.9
104.3
1000
1500
86.7
89.1
77.90
80.30
99.20
101.6
89.60
92.00
115.9
118.3
105.4
107.8
1000
1600
89.3
91.7
80.40
82.80
102.2
104.6
92.60
95.00
119.3
121.7
108.8
111.2
1000
1700
91.9
94.3
83.00
85.40
105.1
107.5
95.50
97.90
122.7
125.1
112.2
114.6
1000
1800
94.5
96.9
84.60
87.00
108.1
110.5
97.50
99.90
126.2
128.6
114.7
117.1
1000
1900
103.1
105.5
93.20
95.60
117.0
119.4
106.5
108.9
135.6
138.0
124.1
126.5
1000
2000
105.6
108
94.80
97.20
120.0
122.4
108.4
110.8
139.1
141.5
126.5
128.9
1000
2200
110.8
113.2
101.0
103.4
125.9
128.3
115.3
117.7
146.0
148.4
134.4
136.8
1000
2300
113.4
115.8
102.6
105.0
128.8
131.2
117.3
119.7
149.4
151.8
136.8
139.20
1000
2400
116.0
118.4
105.2
107.6
131.8
134.2
120.2
122.6
152.8
155.2
140.3
142.7
1000
2500
118.6
121.0
107.8
110.2
134.8
137.2
123.2
125.6
156.3
158.7
143.7
146.1
1100
1100
78.80
81.20
70.90
73.30
90.30
92.70
81.60
84.00
105.5
107.9
95.90
98.30
1100
2000
109.2
111.6
98.30
100.7
123.9
126.3
112.2
114.6
143.4
145.8
130.9
133.30
1150
1150
81.40
83.80
73.50
75.90
93.20
95.60
84.60
87.00
108.9
111.3
99.30
101.70
1150
2000
110.9
113.3
100.1
102.5
125.8
128.2
114.2
116.6
145.6
148.0
133.1
135.50
1200
1200
83.90
86.30
75.00
77.40
96.00
98.40
86.50
88.90
112.2
114.6
101.7
104.10
1200
1500
91.70
94.10
82.80
85.20
104.9
107.3
95.30
97.70
122.6
125.0
112.0
114.40
1200
1700
96.90
99.30
88.00
90.40
110.8
113.2
101.3
103.7
129.5
131.9
118.9
121.30
1200
1800
99.40
101.8
89.60
92.00
113.8
116.2
103.2
105.6
132.9
135.3
121.3
123.70
1200
2000
117.7
119.9
107.9
110.1
132.8
135.0
122.2
124.4
152.9
155.1
141.3
143.50
1200
2200
123.9
113.1
139.7
128.1
160.7
148.2
1200
2300
129.0
118.2
145.2
133.6
166.7
154.1
1200
2500
134.2
123.3
151.0
139.5
173.5
161.0
1250
1250
86.40
88.80
77.60
80.00
98.90
101.3
89.40
91.80
115.6
118.0
105.1
107.50
1250
2500
127.4
115.5
144.4
131.8
167.1
153.6
1300
1300
89.00
91.40
80.20
82.60
101.9
104.3
92.30
94.70
119.0
121.4
108.5
110.90
1300
1500
94.20
96.60
85.30
87.70
107.8
110.2
98.20
100.6
125.9
128.3
115.3
117.70
1300
1600
96.80
99.20
87.90
90.30
110.7
113.1
101.2
103.6
129.4
131.8
118.8
121.20
1300
1800
101.9
104.3
93.10
95.50
116.6
119.0
107.0
109.4
136.2
138.6
125.7
128.10
1300
1900
112.6
115.0
101.7
104.1
127.6
130.0
116.0
118.4
147.7
150.1
135.1
137.50
1300
2000
121.2
123.4
110.4
112.6
136.6
138.8
125.1
127.3
157.2
159.4
144.7
146.90
1300
2200
127.4
129.6
116.6
118.8
143.6
145.8
132.0
134.2
165.1
167.3
152.6
154.80
1300
2500
137.7
145.1
125.9
133.3
154.9
162.3
142.4
149.8
177.9
185.3
164.4
171.80
1400
1400
100.2
102.4
91.30
93.50
113.8
116.0
104.2
106.4
131.9
134.1
121.4
123.60
1400
1500
102.8
105.0
93.90
96.10
116.7
118.9
107.1
109.3
135.4
137.6
124.8
127.00
1400
1800
111.6
113.8
101.7
103.9
126.6
128.8
116.0
118.2
146.7
148.9
135.1
137.30
1400
2000
124.7
126.9
113.9
116.1
140.5
142.7
128.9
131.1
161.5
163.7
149.0
151.20

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 18 of 81
w [mm]
L [mm]
(hinges)
Base height 350 mm
Base height 500 mm
Base height 700 mm
St-Pn
St-El
Sl-Pn
Sl-El
St-Pn
St-El
Sl-Pn
Sl-El
St-Pn
St-El
Sl-Pn
Sl-El
1400
2500
141.2
148.6
129.3
136.7
158.8
166.2
146.2
153.6
182.2
189.6
168.7
176.10
1450
1450
103.7
105.9
93.80
96.00
117.7
119.9
107.1
109.3
136.3
138.5
124.7
126.90
1500
1500
106.3
108.5
96.40
98.60
120.6
122.8
110.0
112.2
139.7
141.9
128.2
130.40
1500
1700
111.4
113.6
101.6
103.8
126.5
128.7
115.9
118.1
146.5
148.7
135.0
137.20
1500
1800
116.5
123.9
106.7
114.1
132.0
139.4
121.4
128.8
152.5
159.9
141.0
148.40
1500
2000
130.7
138.1
118.8
126.2
146.8
154.2
134.3
141.7
168.3
175.7
154.8
162.20
1500
2200
136.9
144.3
125.1
132.5
153.8
161.2
141.2
148.6
176.2
183.6
162.7
170.10
1500
2300
139.5
146.9
127.6
135.0
156.7
164.1
144.1
151.5
179.7
187.1
166.1
173.50
1500
2500
144.7
132.8
162.6
150.1
186.6
173.0
1500
2700
149.9
138.0
168.6
156.0
193.5
179.9
1500
3000
162.0
150.1
181.7
169.1
208.1
194.5
1600
1600
111.3
113.5
101.5
103.7
126.4
128.6
115.8
118.0
146.4
148.6
134.9
137.10
1600
1700
113.9
116.1
104.1
106.3
129.4
131.6
118.8
121.0
149.9
152.1
138.4
140.60
1600
1800
116.5
118.7
106.7
108.9
132.3
134.5
121.7
123.9
153.3
155.5
141.8
144.00
1600
2000
131.7
133.9
119.9
122.1
148.2
150.4
135.7
137.9
170.2
172.4
156.7
158.90
1600
2200
137.9
140.1
126.0
128.2
155.1
157.3
142.5
144.7
178.1
180.3
164.5
166.70
1600
2300
140.5
142.7
128.7
130.9
158.1
160.3
145.5
147.7
181.5
183.7
168.0
170.20
1600
2500
152.5
156.4
140.6
144.5
170.8
174.7
158.2
162.1
195.2
199.1
181.6
185.50
1600
2700
157.7
145.8
176.7
164.1
202.1
188.5
1600
3000
165.4
152.6
185.6
172.0
212.4
197.9
1700
1700
116.4
118.6
106.6
108.8
132.2
134.4
121.6
123.8
153.2
155.4
141.7
143.90
1700
1800
121.5
128.9
111.7
119.1
137.6
145.0
127.1
134.5
159.2
166.6
147.6
155.00
1700
2000
137.7
145.1
125.9
133.3
154.6
162.0
142.0
149.4
177.1
184.5
163.5
170.90
1700
2200
143.9
151.3
132.0
139.4
161.5
168.9
148.9
156.3
184.9
192.3
171.4
178.80
1700
2300
150.8
138.9
168.7
156.2
192.7
179.1
1700
2500
156.0
143.1
174.7
161.0
199.6
185.0
1700
2700
161.1
148.3
180.5
167.0
206.4
191.9
1700
3000
169.9
156.1
190.4
175.8
217.7
202.2
1800
1800
125.0
132.4
114.1
121.5
141.5
148.9
129.9
137.3
163.5
170.9
151.0
158.40
1800
2000
144.5
132.6
161.7
149.1
184.7
171.1
1800
2200
151.7
138.8
169.6
156.1
193.6
179.0
1800
2300
154.3
141.4
172.6
159.0
197.0
182.5
1800
2500
159.5
146.6
178.5
164.9
203.9
189.4
1800
2700
164.6
151.8
184.4
170.8
210.7
196.2
1800
3000
173.4
159.6
194.2
179.7
222.0
206.5
1920
1900
145.7
133.8
163.0
150.4
186.1
172.5
1920
2000
149.3
136.4
166.9
153.4
190.5
175.9
1920
2200
155.5
142.6
173.9
160.3
198.4
183.8
1920
2300
158.0
145.2
176.8
163.2
201.8
187.3
1920
2500
163.2
150.4
182.7
169.1
208.7
194.1

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 19 of 81
w [mm]
L [mm]
(hinges)
Base height 350 mm
Base height 500 mm
Base height 700 mm
St-Pn
St-El
Sl-Pn
Sl-El
St-Pn
St-El
Sl-Pn
Sl-El
St-Pn
St-El
Sl-Pn
Sl-El
1920
2700
169.5
155.6
189.6
175.1
216.6
201.0
1920
3000
177.2
163.4
198.5
183.9
226.9
211.4
St –straight base Pn –pneumatic actuator (exemplary selection. The actuator type depends on T, SL class)
Sl –sloping base El –electric actuator
Damper weight* –applies to dampers with 16 mm thick polycarbonate filling and SL 550
Approximate weights* of double leaf dampers are shown in Table 7.
w [mm]
L [mm]
(hinges)
Base height 350 mm
Base height 500 mm
Base height 700 mm
St-Pn
St-El
Sl-Pn
Sl-El
St-Pn
St-El
Sl-Pn
Sl-El
St-Pn
St-El
Sl-Pn
Sl-El
1250
2500
162.7
167.5
153.7
158.5
179.7
184.5
170
174.8
202.4
207.2
191.8
196.6
1500
1500
126
130.8
117
121.8
140.4
145.2
130.6
135.4
159.5
164.3
148.8
153.6
1500
2500
173.5
178.3
162.5
167.3
191.4
196.2
179.7
184.5
215.4
220.2
202.7
207.5
1500
3000
200.4
204.8
191.4
195.8
220.1
224.5
210.4
214.8
246.5
250.9
235.8
240.2
1600
1600
133.7
138.5
124.7
129.5
148.8
153.6
139.1
143.9
168.8
173.6
158.2
163
1600
2500
177.4
182.2
166.4
171.2
195.7
200.5
184
188.8
220.1
224.9
207.5
212.3
1600
2800
198.8
203.2
187.9
192.3
218.2
222.6
206.5
210.9
244.1
248.5
231.4
235.8
1600
3000
204.3
208.7
195.3
199.7
224.4
228.8
214.7
219.1
251.3
255.7
240.6
245
1800
1600
139.6
144.4
130.6
135.4
155.4
160.2
145.6
150.4
176.4
181.2
165.7
170.5
1800
1800
147
151.8
138.1
142.9
163.5
168.3
153.8
158.6
185.5
190.3
174.9
179.7
1800
2500
185.3
190.1
174.3
179.1
204.3
209.1
192.6
197.4
229.7
234.5
217
221.8
1800
2800
206.7
211.1
195.7
200.1
226.8
231.2
215.1
219.5
253.7
258.1
241
245.4
1800
3000
218.1
232.9
207.2
222.0
239
253.8
227.3
242.1
266.8
281.6
254.1
268.9
2000
2000
172.4
177.2
163.4
168.2
190.3
195.1
180.6
185.4
214.3
219.1
203.6
208.4
2000
2400
189.3
194.1
180.4
185.2
208.7
213.5
199
203.8
234.6
239.4
223.9
228.7
2000
2500
203.3
207.7
192.3
196.7
223.1
227.5
211.4
215.8
249.4
253.8
236.8
241.2
2000
2800
218.5
233.3
207.6
222.4
239.4
254.2
227.7
242.5
267.2
282
254.5
269.3
2000
3000
226
240.8
215
229.8
247.6
262.4
235.9
250.7
276.3
291.1
263.7
278.5
2200
2200
191.7
196.5
180.8
185.6
211.1
215.9
199.4
204.2
237
241.8
224.3
229.1
2200
2400
197.2
202
188.2
193
217.3
222.1
207.6
212.4
244.2
249
233.5
238.3
2200
2500
211.2
215.6
200.2
204.6
231.7
236.1
219.9
224.3
259
263.4
246.3
250.7
2400
2400
219.2
234
210.3
225.1
240.1
254.9
230.4
245.2
267.9
282.7
257.2
272
2400
2500
223
237.8
214
228.8
244.2
259
234.5
249.3
272.5
287.3
261.8
276.6
2500
2500
227
241.8
218
232.8
248.5
263.3
238.8
253.6
277.3
292.1
266.6
281.4
2500
3000
254.2
262.0
243.2
251.0
277.6
285.4
265.9
273.7
308.8
316.6
296.1
303.9
3000
3000
272.2
280.0
261.2
269.0
294.9
302.7
283.2
291.0
325.3
333.1
312.6
320.4
St –straight base Pn –pneumatic actuator (exemplary selection. The actuator type depends on T, SL class)
Sl –sloping base El –electric actuator
Damper weight* –applies to dampers with 16 mm thick polycarbonate filling and SL 550
In exceptional situations there is the possibility of making dampers with different hole
dimensions, but only within the range of terminal dimensions shown in Tables 4 and 5.
The basic heights of the damper bases are 350, 500 or 700 mm.
It is possible to make dampers with other base dimensions, however not smaller than
350 mm. For dampers with base heights other than the basic ones, the dampers with a
lower base should be considered as valid declarations for Aa active area.

Operation and Maintenance Manual –SCD Smoke Dampers
Version 1
Date 04 2018 Page 20 of 81
4.6. DRIVE SELECTION
In SCD smoke dampers, a basic function of emergency opening in order to extract
smoke is carried out by a pneumatic or electric 24 V actuator.
The function of damper release in order to vent for dampers with a pneumatic drive is
carried out by the 230 V or 24 V electric actuator (for dampers with maximum leaf
dimensions up to 1920 x 2500), double action pneumatic actuator or a second electric
actuator.
The power transmission from the actuator to the damper’s cover is carried out by a
special mechanism, and the cover position is set by a spring lock.
The selection of actuators for individual single leaf damper sizes is presented in
Table 8, and for double leaf damper sizes in Table 9. For intermediate dimensions or other
classification than the one given in Tables 8 and 9, it is possible to approximate actuators
meeting the durability and mechanical criteria.
W [mm]
L [mm]
(hinges)
Type of the electric
actuator, SL550 T(-25)
classification
W [mm]
L [mm]
(hinges)
Type of the electric actuator,
SL550 T(-25) classification
1000
1000
SG26F/25S
1000
1700
SG26M/25A
SG20M/25A
SG40B/25A
SG40B/25A
SG60N/25A
1000
1200
SG26F/25S
SG60F/25S
SG20M/25A
1000
1800
SG40B/25A
SG40B/25A
SG60N/25A
1000
1300
SG26F/25S
SG60F/25S
SG26M/25A
1000
2000
SG40M/25A
SG40B/25A
SG60N/25A
1000
1400
SG26M/25A
1000
2200
SG40M/25A
SG40B/25A
SG60N/25A
1000
1500
SG26M/25A
1000
2300
SG40M/25A
SG40B/25A
SG60N/25A
SG60N/25A
1000
2400
SG60N/25A
SG60F/25S
SG60F/25S
1000
1600
SG26M/25A
1000
2500
SG60F/25S
SG40B/25A
SG80T/25S
SG60N/25A
1100
1100
SG40B/25A
SG60F/25S
1100
2000
SG60N/25A
SG60F/25S
1150
1150
SG40B/25A
1300
2000
SG60N/25A
SG60N/25A
SG80T/25S
SG60F/25S
SG100R/25A
Table of contents
Other SMAY Fire And Smoke Damper manuals
Popular Fire And Smoke Damper manuals by other brands

Greenheck
Greenheck MBD-15 Installation, operation and maintenance manual

ATI Technologies
ATI Technologies LS1 Installation instruction

Rf-t
Rf-t CR2 manual

Rf-t
Rf-t KAMOUFLAGE MP Series manual

System air
System air DKIR1 ORIGINAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Greenheck
Greenheck ABD-Z2 Installation, operation and maintenance manual

Honeywell Home
Honeywell Home TrueZONE Bypass installation instructions

mercor
mercor mcr FID S c/P Series Operation and maintenance manual

Alnor
Alnor MANDIK FDMC manual

BESA
BESA TB/001 Technical bulletin

Lindab
Lindab FNC1 Installation booklet

Mandik
Mandik FDMQ 120 Installation, operation, maintenance and service manual