Z_ISE3-TF2Z043EN
Page 1 of 3
Instruction Manual
Compact Pressure Switch
ZSE3 / ISE3(L)
The intended use of the compact pressure switch is to measure, monitor
and display pressure and provide an output signal.
1 Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage. These instructions indicate the level of
potential hazard with the labels of “Caution,” “Warning” or “Danger.”
They are all important notes for safety and must be followed in addition
to International Standards (ISO/IEC)*1), and other safety regulations.
*1) ISO 4414: Pneumatic fluid power - General rules relating to systems.
ISO 4413: Hydraulic fluid power - General rules relating to systems.
IEC 60204-1: Safety of machinery - Electrical equipment of machines.
(Part 1: General requirements)
ISO 10218-1: Robots and robotic devices - Safety requirements for
industrial robots - Part 1: Robots.
•Refer to product catalogue, Operation Manual and Handling
Precautions for SMC Products for additional information.
•Keep this manual in a safe place for future reference.
Caution
Caution indicates a hazard with a low level of risk which, if
not avoided, could result in minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk
which, if not avoided, could result in death or serious injury.
Danger
Danger indicates a hazard with a high level of risk which, if
not avoided, will result in death or serious injury.
Warning
•Always ensure compliance with relevant safety laws and
standards.
•All work must be carried out in a safe manner by a qualified person in
compliance with applicable national regulations.
•This product is class A equipment intended for use in an industrial
environment. There may be potential difficulties in ensuring
electromagnetic compatibility in other environments due to conducted
or radiated disturbances.
•Refer to the operation manual or catalogue on the SMC website (URL:
https://www.smcworld.com) for more safety instructions.
2 Specifications
2.1 General specifications
*1: When vacuum is used, there is no influence on the switch even if 0.5
MPa of pressure is supplied instantaneously.
*2: Window comparator mode: Since the hysteresis is 3 digits, P1 should
be separated from P2 by 7 digits or more.
1 digit is the minimum pressure display unit.
*3: Only for the pressure switch with analogue output selected.
*4: In case of ZSE3-#-23 or 24, failure predictive output: Red.
2 Specifications (continued)
2.2 Analogue Output
Model No. Rated pressure range A B
ZSE3 0 to -101 kPa 0 -101 kPa
ISE3L 0 to 98 kPa 0 98 kPa
ISE3 0 to 0.98 MPa 0 0.98 MPa
3 Summary of Product parts
Part Description
RESET button Resets an error and for zero clear of the display.
SET button Selects the setting mode and enters the set value.
LCD display
Displays pressure value, setting mode, and error
codes.
LED
The green LED is ON when output OUT1 is ON.
The red LED is ON when output OUT2 is ON and
failure predictive output.
When both OUT1 and OUT2 are ON, both the
green and red LED’s are ON.
When an error occurs the red LED flashes.
UP button
Selects the peak display mode and increases the
ON/OFF set value.
DOWN button
Selects the bottom display mode and decreases
the ON/OFF set value.
4 Installation
4.1 Installation Warning
Do not install the product unless the safety instructions have been read
and understood.
4.2 Environment Warning
•Do not use in an environment where corrosive gases, chemicals, salt
water or steam are present.
•Do not use in an explosive atmosphere.
•Do not expose to direct sunlight. Use a suitable protective cover.
•Do not install in a location subject to vibration or impact. Check the
product specifications.
•Do not mount in a location exposed to radiant heat.
4 Installation (continued)
4.3 Piping
Caution
•Before connecting piping make sure to clean up chips, cutting oil, dust
etc.
•When installing piping or fittings, ensure sealant material does not
enter inside the port. When using seal tape, leave 1 thread exposed
on the end of the pipe/fitting.
•Connect the digital pressure switch tothe piping with a hexagon socket
head plug and a fitting.
•The tightening torque for the piping port must be 8.8 N•m maximum.
4.4 Lubrication Caution
•SMC products have been lubricated for life at manufacture, and do not
require lubrication in service.
•If a lubricant is used in the system, use turbine oil Class 1 (no additive),
ISO VG32. Once lubricant is used in the system, lubrication must be
continued because the original lubricant applied during manufacturing
will be washed away.
5 Wiring
5.1 Wiring connections
•Connections should be made with the power supply turned OFF.
•Use a separate route for the product wiring and any power or high
voltage wiring. Otherwise, malfunction may result due to noise.
•If a commercially available switching power supply is used, be sure to
ground the frame ground (FG) terminal. If the switching power supply
is connected for use, switching noise will be superimposed and it will
not be able to meet the product specifications. In that case, insert a
noise filter such as a line noise filter/ferrite between the switching
power supplies or change the switching power supply to a series power
supply.
•Incorrect wiring will lead to digital pressure switch damage, failure or
malfunction. Be sure to confirm the wire colour and terminal number
before wiring.
5.2 Connector attaching / detaching
•When assembling the connector, push it straight onto the pins until the
lever locks into the housing.
•To remove the connector, push the lever down to unlock the hook from
the groove, and withdraw the connector straight out.
Mating connector wiring details:
Wire size: 0.2 to 0.33 mm2max.
Wire sheath diameter 1.7 mm max.
Strip 3.2 to 3.7 mm of lead wire and fit crimp
SMC Part No. DXT170-71-1.
Crimping tool: SMC Part No. DXT170-75-1.
ORIGINAL INSTRUCTIONS
Model No.
ZSE3
Vacuum
ISE3L
Low pressure
ISE3
High pressure
Rated pressure
range
0 to -101 kPa 0 to 98 kPa 0 to 0.98 MPa
Min. display unit
1 kPa
0.01 MPa
Applicable fluid
Air, inert and incombustible gases
Max. operating
pressure
200 kPa *1 1 MPa
Power supply
voltage
12 to 24 VDC ±10%, ripple (P-P) 10% or less
(Protected against inverse connection)
Current
consumption
25 mA or less
Switch output
Output type
NPN open collector output
Max. load
current
80 mA
Max.
applied
voltage
30 VDC
Response
time
5 msec
Repeatability
±1% F.S.
Hysteresis
Hysteresis
mode
*4-2
Variable (0 digits or more)
Window
comparator
mode
Fixed (3 digits)
Analogue output
*2-3
Voltage output: 1 to 5 V ±5%
Output impedance: Approx. 1 kΩ
Display method
3 1/2 digits LCD (character height 5 mm)
Indicator light *3-4
Light when ON OUT1: Green OUT2: Red
Self-diagnosis
function
Detection of overcurrent, overpressure, data
error and pressure during zero clear
Error indication
Indicator: Red flashing,
Error code is displayed on LCD
Environmental
Enclosure
IP40
Ambient
temperature
range
0 to 60 oC (No condensation or freezing)
Withstand
voltage
1000 VAC, 50/60 Hz, 1 minute, Between the
external terminal and the case
Insulation
resistance
2 MΩ (at 500 VDC) Between the external
terminal and the case
Temperature
characteristic
±3% F.S.
Port size
R1/8: M5x0.8
NPTF1/8:
M5x0.8
With suction
filter: M5x0.8
(M6x1 made
to order).
R1/8: M5x0.8
NPTF1/8: M5x0.8
Lead wire
Connector
type
Heat-resistant vinyl electric wire, 4-wire, Cross
section: 0.31 mm
2
, Insulator O.D.: 1.55 mm
Grommet
type
Oil-resistant vinyl cabtire code
-21, -23: 4 cores, ø3.5, Cross section: 0.14 mm2,
Insulator O.D.: 1.0 mm
-22, -24: 5 cores, ø3.5, Cross section: 0.15 mm2,
Insulator O.D.: 1.0 mm
Weight
40 g (including 0.6 m lead wire)
Analogue
output [V]
Z_ISE3-TF2Z043EN
Page 2 of 3
5 Wiring (continued)
5.3 Wiring diagram
5.4 Internal circuit and wiring
ZSE3 / ISE3(L)-#-21
Switch output, NPN open collector output, 2 outputs, Max. 30 V, 80 mA
ZSE3 / ISE3(L)-#-22
Switch output, NPN open collector output, 2 outputs, Max. 30 V, 80 mA
Analogue output: 1 to 5 V, Output impedance: Approx. 1 kΩ
ZSE3 / ISE3(L)-#-23
Switch output, NPN open collector output, 1 output, Max. 30 V, 80 mA
Failure predictive output, NPN open collector output, 1 output.
ZSE3 / ISE3(L)-#-24
Switch output, NPN open collector output, 1 output, Max. 30 V, 80 mA
Failure predictive output, NPN open collector output, 1 output.
Analogue output: 1 to 5 V, Output impedance: Approx. 1 kΩ
6 Pressure Setting
6.1 2 output type
6.2 Output method
•Hysteresis mode (P1≥P2, P3≥P4)
•Window comparator mode (P1<P2, P3<P4)
•Hysteresis mode (same as for positive pressure use) When the value
of hysteresis is set to 2 digits or less, the switching output might chatter
due to fluctuation of the input pressure around its set point.
•Window comparator mode (same as for positive pressure use) since
the hysteresis will be 3 digits, separate P1 from P2 (in case of 2-output
type, same as for P3 and P4) by 7 digits or more.
* 1 digit is the minimum pressure display unit.
6 Pressure Setting (continued)
6.3 1 Output type with Failure Predictive function
6.4 Failure Predictive function
The failure predictive detection counter is incremented when the switch
is turned on then is turned off, without the pressure (exceeding P1) not
reaching the failure predictive pressure (P3).
The failure predictive detection output is energized when the set failure
predictive counter (EC) is incremented consecutively. When the switch is
turned ON and the pressure (exceeding P1) exceeds the failure
predictive pressure (P3), the failure predictive counter is reset.
(This example shows a case in the hysteresis mode).
7 Other Settings
•Peak Hold mode
•Bottom Hold mode
•RESET button function
•Zero clear function
Refer to the operation manual available on the SMC website (URL:
https://www.smcworld.com)
8 Error Indication
Error Display Error Type Troubleshooting Method
The set data has
been changed
under some
influences.
Press the RESET button
and set all data again.
Load of OUT1 has
short-circuited and
overcurrent is
flowing.
Turn off the power supply
and replace the load
connected to the OUT1
(black wire).
Load of OUT2 has
short-circuited and
overcurrent is
flowing.
Turn off the power supply
and replace the load
connected to the OUT2
(white wire).
Pressure exceeding
0.5 MPa has been
applied.
(In case of positive
pressure, pressure
exceeding the rated
pressure has been
applied.)
Lower the pressure to 0.5
MPa or less. (In case of
positive pressure, lower
the pressure to the rated
pressure or less.)
Compared with the
ambient pressure
-0.07 MPa (in case
of 1 MPa use) or -7
kPa or more (in
case of vacuum use
or 100 kPa use) has
been applied during
zero clear.
After adjusting the
pressure to the ambient
pressure, perform RESET
operation.
If the error cannot be reset after the above measures are taken, then
please contact SMC.
9 How to Order
Refer to the operation manual on the SMC website (URL:
https://www.smcworld.com) for How to order information.
10 Outline Dimensions
Refer to the operation manual or catalogue on the SMC website (URL:
https://www.smcworld.com) for Outline Dimensions.
11 Maintenance
11.1 General Maintenance Caution
•Not following proper maintenance procedures could cause the product
to malfunction and lead to equipment damage.
•If handled improperly, compressed air can be dangerous.
•Maintenance of pneumatic systems should be performed only by
qualified personnel.
•Before performing maintenance, turn off the power supply and be sure
to cut off the supply pressure. Confirm that the air is released to
atmosphere.
•After installation and maintenance, apply operating pressure and
power to the equipment and perform appropriate functional and
leakage tests to make sure the equipment is installed correctly.
•If any electrical connections are disturbed during maintenance, ensure
they are reconnected correctly and safety checks are carried out as
required to ensure continued compliance with applicable national
regulations.
•Do not make any modification to the product.
•Do not disassemble the product, unless required by installation or
maintenance instructions.
How to reset the product after power cut or forcible de-energizing
The setting of the product is remained as that before power cut or de-
energizing. The output condition isalso basically recovered to that before
power cut or de-energizing, but may change depending on the operating
environment. Therefore, check the safety of whole facility before
operating the product. If the facility is under accurate control, wait until
the product has warmed up (approx. 10 minutes).
1. Set value input mode
Press the "SET" button to display "P1-20" *1.
The output OUT1(1) set value input mode is
selected.
*1: If the set value of P1 is -20.
2. OUT1(1) set value input
Pressing the button increases the set value.
Pressing the button decreases the set value.
Press the "SET" button to save the set value and
select the output OUT1(2) set value input mode.
The set value of P2 is displayed.
3. OUT1(2) set value input
Pressing the button increases the set value.
Pressing the button decreases the set value.
Press the "SET" button to save the set value and
select the output OUT1(1) set value input mode.
The set value of P3 is displayed.
4. OUT2(1) set value input
Pressing the button increases the set value.
Pressing the button decreases the set value.
Press the "SET" button to save the set value and
select the output OUT2(2) set value input mode.
The set value of P4 is displayed.
5. OUT2(2) set value input
Pressing the button increases the set value.
Pressing the button decreases the set value.
Press the "SET" button to save the set value and
exit this mode.
P1: Set value for OUT1(1)
P2: Set value for OUT1(2)
P3: Set value for OUT2(1)
P4: Set value for OUT2(2)
1. Set value input mode
Press the "SET" button to display "P1-50" *1.
The output OUT1(1) set value input mode is
selected.
*1: If the set value of P1 is -50.
2. OUT1(1) set value input
Pressing the button increases the set value.
Pressing the button decreases the set value.
Press the "SET" button to save the set value and
select the output OUT1(2) set value input mode.
The set value of P2 is displayed.
3. OUT1(2) set value input
Pressing the button increases the set value.
Pressing the button decreases the set value.
Press the "SET" button to save the set value and
select the failure predictive pressure set value
input mode.
The failure predictive set value is displayed.
4. Failure predictive pressure set value input
Pressing the button increases the set value.
Pressing the button decreases the set value.
Press the "SET" button to save the set value and
select the failure predictive count set value input
mode.
The failure predictive count set value is displayed.
5. Failure predictive count set value input
Pressing the button increases the set value.
Pressing the button decreases the set value.
Press the "SET" button to save the set value and
exit this mode.
P1: Set value for OUT1(1)
P2: Set value for OUT1(2)
P3: Set value for failure predictive pressure.
EC: Set value for failure predictive count.
Analogue output: 1 to 5 V (±5%F.S.)
Analogue output
Analogue output
Z_ISE3-TF2Z043EN
Page 3 of 3
11 Maintenance (continued)
•Replacement of filter elements
If element clogging causes deterioration of the adsorption force or slows
the response time, stop operation and replace the element.
Filter element part no.: ZX1-FE
Confirm that the filter gasket is seated in the groove before reassembling
the parts.
Filter gasket part no.: ZX1-FG
•Filter cases
The case is made of polycarbonate. Therefore, do not use the product in
an environment that is exposed to chemicals such as thinners, carbon
tetrachloride, chloroform, acetic ester, aniline, cyclohexane,
trichloroethylene, sulfuric acid, lactic acid, or water-soluble cutting oil
(alkalinic).
12 Limitations of Use
12.1 Limited warranty and Disclaimer/Compliance Requirements
Refer to Handling Precautions for SMC Products.
Caution
•SMC products are not intended for use as instruments for legal
metrology.
Measurement instruments that SMC manufactures or sells have not
been qualified by type approval tests relevant to the metrology
(measurement) laws of each country.
Therefore, SMC products cannot be used for business or certification
ordained by the metrology (measurement) laws of each country.
13 Product Disposal
This product shall not be disposed of as municipal waste. Check your
local regulations and guidelines to dispose of this product correctly, in
order to reduce the impact on human health and the environment.
14 Contacts
Refer to www.smcworld.com or www.smc.eu for your local distributor /
importer.
URL: https://www.smcworld.com (Global) https://www.smc.eu (Europe)
SMC Corporation, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, Japan
Specifications are subject to change without prior notice from the manufacturer.
© 2021 SMC Corporation All Rights Reserved.
Template DKP50047-F-085M

This manual suits for next models

2

Other SMC Networks Switch manuals

SMC Networks ZSE30 Series User manual

SMC Networks

SMC Networks ZSE30 Series User manual

SMC Networks D-F7NJL Series Instruction Manual

SMC Networks

SMC Networks D-F7NJL Series Instruction Manual

SMC Networks SMCEZNET-16SW User manual

SMC Networks

SMC Networks SMCEZNET-16SW User manual

SMC Networks SMCGS26C-SMART - FICHE TECHNIQUE Operating and safety instructions

SMC Networks

SMC Networks SMCGS26C-SMART - FICHE TECHNIQUE Operating and safety instructions

SMC Networks PF3A703H-L User manual

SMC Networks

SMC Networks PF3A703H-L User manual

SMC Networks SMCGS501 - FICHE TECHNIQUE Operating and safety instructions

SMC Networks

SMC Networks SMCGS501 - FICHE TECHNIQUE Operating and safety instructions

SMC Networks SMC8612XL3 F 1.0.1.3 User manual

SMC Networks

SMC Networks SMC8612XL3 F 1.0.1.3 User manual

SMC Networks PFM3 Series User manual

SMC Networks

SMC Networks PFM3 Series User manual

SMC Networks PF3A-H Series User manual

SMC Networks

SMC Networks PF3A-H Series User manual

SMC Networks 6726AL2 - annexe 1 User manual

SMC Networks

SMC Networks 6726AL2 - annexe 1 User manual

SMC Networks ZSE10F Series User manual

SMC Networks

SMC Networks ZSE10F Series User manual

SMC Networks 6709L2 User manual

SMC Networks

SMC Networks 6709L2 User manual

SMC Networks PFA Series User manual

SMC Networks

SMC Networks PFA Series User manual

SMC Networks ZSE30A series User manual

SMC Networks

SMC Networks ZSE30A series User manual

SMC Networks TigerAccess EE SMC7816M/VSW User manual

SMC Networks

SMC Networks TigerAccess EE SMC7816M/VSW User manual

SMC Networks ZK2-ZS L A Series User manual

SMC Networks

SMC Networks ZK2-ZS L A Series User manual

SMC Networks ISE35 User manual

SMC Networks

SMC Networks ISE35 User manual

SMC Networks PFM7 Series User manual

SMC Networks

SMC Networks PFM7 Series User manual

SMC Networks ISE70 User manual

SMC Networks

SMC Networks ISE70 User manual

SMC Networks ZSE10 Series Instruction Manual

SMC Networks

SMC Networks ZSE10 Series Instruction Manual

SMC Networks SMC8606SX User manual

SMC Networks

SMC Networks SMC8606SX User manual

SMC Networks TigerStack 100 1000BASE-X Programming manual

SMC Networks

SMC Networks TigerStack 100 1000BASE-X Programming manual

SMC Networks SMC8606T User manual

SMC Networks

SMC Networks SMC8606T User manual

SMC Networks EZ Switch SMC-EZ1024FDT User manual

SMC Networks

SMC Networks EZ Switch SMC-EZ1024FDT User manual

Popular Switch manuals by other brands

Samsung WAM250 user manual

Samsung

Samsung WAM250 user manual

FXC FXC5024 user manual

FXC

FXC FXC5024 user manual

EuroLite LVH-7 user manual

EuroLite

EuroLite LVH-7 user manual

Dungs AA-A1-0 Series installation instructions

Dungs

Dungs AA-A1-0 Series installation instructions

Lightwave Communications ServerSwitch 8200 user manual

Lightwave Communications

Lightwave Communications ServerSwitch 8200 user manual

Lutron Electronics Maestro MS-OPS6-DDV manual

Lutron Electronics

Lutron Electronics Maestro MS-OPS6-DDV manual

Digitus DN-80111 manual

Digitus

Digitus DN-80111 manual

SsecureNetworx StreamBuddy user guide

SsecureNetworx

SsecureNetworx StreamBuddy user guide

Hawking HKS104 Quick installation guide

Hawking

Hawking HKS104 Quick installation guide

Huawei CR-SRUB Specifications

Huawei

Huawei CR-SRUB Specifications

EUCHNER STP AS1 Series operating instructions

EUCHNER

EUCHNER STP AS1 Series operating instructions

D-Link DSS-100E-18P Quick installation guide

D-Link

D-Link DSS-100E-18P Quick installation guide

Clas Ohlson MA-001 quick start guide

Clas Ohlson

Clas Ohlson MA-001 quick start guide

Kathrein EXD 158 Twin manual

Kathrein

Kathrein EXD 158 Twin manual

3Com SuperStack 4 Configuration guide

3Com

3Com SuperStack 4 Configuration guide

Cisco Intelligent Gigabit Ethernet Switch Module manual

Cisco

Cisco Intelligent Gigabit Ethernet Switch Module manual

Farnell SY-UHD-S41A installation guide

Farnell

Farnell SY-UHD-S41A installation guide

DRIESCHER-WEGBERG LDTM Operation and assembly instructions

DRIESCHER-WEGBERG

DRIESCHER-WEGBERG LDTM Operation and assembly instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.