5.1.3. Fixed outputs - Dry contacts
5.1.3.1. Description
As standard, the SIRCOMOTPV is equipped with four xed outputs located on
the motorisation module.
(Dry contacts to be powered by the user).
1 2 3 4 56
75A413 200A Ue 750V 19PV3020 3 TRI
75A414 250A Ue 750V 19PV3025 3 TRI
75A415 400A Ue 750V 19PV3040 3 TRI
75A416 500A Ue 750V 19PV3050 3 TRI
75A417 630A Ue 750V 19PV3063 3 TRI
75A425 200A Ue 1000V 19PV4020 4 TETRA
75A426 250A Ue 1000V 19PV4025 4 TETRA
75A427 400A Ue 1000V 19PV4040 4 TETRA
75A428 500A Ue 1000V 19PV4050 4 TETRA
75A429 630A Ue 1000V 19PV4063 4 TETRA
75A430 I800A Ue 1000V 19PV4080 4 TETRA
75A431 1000A Ue 1000V 19PV4100 4 TETRA
75A432 1250A Ue 1000V 19PV4120 4 TETRA
75A433 1600A Ue 1000V 19PV4160 4 TETRA
75A434 2000A Ue 1000V 19PV4200 4 TETRA
75A436 3200A Ue 1000V 19PV4320 4 TETRA
5.1.3.2. Position auxiliary contact
The SIRCOMOTPV is equipped with integrated position (I – O) auxiliary contact outputs through 3 off micro switches.
Pins13,04,24
(Normally Open contacts with pin 13 as common)
5.1.3.3. SIRCOMOTPV Product available output (motorisation)
Pin63A–64A
(Normally Open contact that is held closed when the motorisation is available).
This contact gives constant feedback about the product’s availability and it’s capacity to operate.
The SIRCOMOTPV performs a self diagnostics test on the motorisation module at startup, when put from Manual
-> Auto and then every 5 minutes. This test ensures that the SIRCOMOTPV is operational in terms of control inputs.
Should one of the tests fail, a second test is performed to reconrm the error state. Should the SIRCOMOTPV
motorisation module become unavailable, contact 63A – 64A are opened, the power/ready LED’s are switched off,
and the fault LED is activated. The fault LED will remain active for as long as sufcient power is available and the fault
condition is not reset. The fault is reset when the product is switched from AUT -> Manual -> Auto mode.
SIRCO MOT PV (Motorisation) Product Available / Unavailable Watchdog relay will open for any of the following
reasons below: For added security, “Product Availability” is informative and does not necessarily inhibit motor
operation.
ProductUnavailable+WarningLEDCondition: Inhibition
Product in manual mode Yes
Motor not detected (Autotest) No
Control voltage out of range Yes
Operating factor fault active (N° of operations / min) Yes
Powerfail active Yes
Customer input autotest failed No
Invalid product customisation No
Abnormal switching when not in manual mode Yes
Requested position not reached Yes
Locked mode active when not in manual mode Yes
External Fault -> User input No
Unexpected current owing through the motor when idle Yes
Sampling rate for the above is every 10 ms
Exception: motor detection sampling rate is every 5 min
5.1.3.4. Technical data
Auxiliary Contact Quantity 2
Conguration NO
Mechanical Endurance 800 cycles
Response Time 5 – 10 ms
Startup duration 200ms
Rated Voltage / Switching Voltage 250Vac
Rated Current 5A
Surge protectionVin_sg: 4.8kV (1.2/50µs surge)