Quick Installation Guide
v. 1.0
SolarEdge Home
Backup Interface, Three
Phase
BI-EU3P
for use with the SolarEdge Home Hub
Inverter, Three Phase
2
1Mounting the Backup
Interface
1. Select an installation location. Make sure you have enough
space between the Backup Interface and other objects to
securely access all its interfaces.
2. Install the mounting bracket to the wall and secure it with
2-4 screws. If using only 2 screws, use left and right ones.
3. Hang the Backup Interface on the mounting bracket.
4. Hang the lower bracket on the hook behind the bottom
glands, secure it to the wall with a screw.
4
© SolarEdge Technologies, Ltd.
All rights reserved.
Version: 1.0, December 2022
Subject to change without notice.
Support Contact Information
In case of any technical issues with SolarEdge
products, please contact us at:
https://www.solaredge.com/service/support
What’s in the Package
Backup Interface Mounting bracket
Required Tools
Mounting
screws and wall
plugs
X 3
Level
Pencil
Watchmaker flat
screwdriver
Phillips
screwdriver
Torque
wrench
Drill
CAT6 cable M4, M5 Allen
keys
•Read this entire document before installing or operating the Backup Interface (also referred to as BUI). Failure to do so or to follow any of the
instructions or warnings in this document can result in electrical shock, serious injury, or death, or may damage the Backup Interface and other
property, it can also lead to warranty void.
•Do not discard this document! After installation, keep it adjacent to the Backup Interface for future reference!
•Before operating the Backup Interface and inverter, ensure that they are properly grounded. The Backup Interface and inverter must be
connected to a grounded, metal, permanent wiring system, or an equipment-grounding conductor must be run with the circuit conductors and
connected to the equipment grounding terminal or lead.
•Opening the Backup Interface and repairing or testing under power must be performed only by qualified service personnel familiar with the
Backup Interface.
This symbol on the product or in the accompanying documentation denotes a hazard. It calls attention to a procedure that, if not
correctly performed or adhered to, could result in injury or loss of life. Do not proceed beyond a warning note until the indicated
conditions are fully understood and met.
SAFETY AND HANDLING INSTRUCTIONS
WARNINGS!
This symbol on the product denotes risk of electric shock due to stored energy. Before handling the product, wait for at least 5
seconds after disconnecting it from all sources of energy.
For updates, check:
Removing the covers
1. Using M5 Allen key, release six screws and remove the Backup
Interface front cover.
2. Using M4 Allen key, release two screws and remove the Backup
Interface internal lower cover.
3. Make sure the ON/OFF switch is in the OFF position.
OFF
It is forbidden and dangerous to open the upper section.
Only the lower section is for user interface usage.
WARNING!
DANGER!
Before opening the covers and connecting the grid, please make sure that the main CB and the Inverters are OFF.
Bottom interface of the Backup InterfaceMain connection scheme
Load section
Grid section
1
2
3
4
2
3
Comm
Enable
LED Indications
Manually Switching to Grid-Connected Mode
In case the grid is back to operation, but, for
some reason, the "Backup Interface" LED shows
that backup is ON, you can manually connect
the grid back to the loads by following the
below procedure.
When the system is manually switched to the
grid-connected mode, no backup of the loads is
possible.
To switch to the grid-connected mode:
1. Remove the Backup Interface front cover
as shown above.
2. Press “Bypass On” on Manual Control
panel.
3. Close the external cover.
4 N*m
4Closing the Backup
Interface
1. Using M4 Allen key, secure Backup Interface internal lower cover
with two screws.
2. Using M5 Allen key, secure Backup Interface external front cover
with six screws.
3. Now you can turn on the main CB and the inverter.
Configuring Installation
1. Run SetApp.
2. Scan the QR code on the inverter.
3. Follow the on-screen instructions.
4. Configure the import/export meter on SetApp.
SetApp
5
Power Control
Energy Manager
Backup
Configuration
Backup
Commissioning
4 N*m
Grid Backup
ON
On grid or boot
OFF
Backup mode
Blinking
Firmware upgrade
Fast blinking
Backup interface
received request
to identify itself
All LEDs OFF
No power
ON
Fault or boot
OFF
No faults
Blinking
Firmware upgrade
Fault
6Backup system checkup
Note: Before you start, make sure you have the Inverter system operating and producing with battery at above 20%.
Checking the backup operation may cause 2-3 seconds of electricity supply failure to the loads before they are powered up again; if
you have a load sensitive to such interruption, please disconnect it from the load backup section.
Make sure the loads are evenly distributed between phases and do not exceed your inverter rating per phase.
1. Make sure you have power from the grid and your inverter is working.
2. Before you start, check that the Battery SoC level is above 20%.
3. Make sure the Grid LED is ON and there is no fault detected. Turn OFF the main CB coming from the grid. Immediately after
that, all home loads should shut down and the "On grid" LED should turn OFF.
4. Wait for a few seconds till all the home loads are powered up again, the LED marked as "Backup" should turn ON.
5. After a few minutes of stable operation, turn ON the main CB again.
6. “Backup” LED should turn OFF and the "On grid" LED should turn on again.
Connecting the Backup Interface
DANGER!
Before opening the covers and connecting the grid, please make sure that the main CB and the Inverters are OFF.
Note: If your local regulations require a short between Neutral and Protective earth (e. g. according to TNC), use the upper-right
terminal for the Load Neutral (see the figure below and the Main Connection Scheme).
1. Strip 100mm around the external grid cable and strip 8mm from the internal wire insulation. If needed, crimp the wire
ferrules. Open the left gland marked with “Grid” and insert the grid cable. Connect the ground wire first. Torque –6nm.
Connect the wires Ground (yellow) L1 (brown) ,L2 (black), L3 (gray), and Neutral (blue) to their respective terminals.
2. Strip 100mm around the external load cable and strip 8mm from the internal wire insulation. If needed, crimp the wire
ferrules. Open the right gland marked with “Load” and insert the load cable. Connect the ground wire first. Torque –6nm.
Connect the wires Ground (yellow) ,L1 (brown) ,L2 (black), L3 (gray), and Neutral (blue) and to their respective terminals.
3. If your system doesn’t use solaredge home network, connect the Backup Interface to your inverter using a CAT5 E or a
CAT6. Open the communication gland and insert the communication cable, close the gland. Pull out the communication
connector and connect the communication cable wires to the G, A, B, and 12V +/- respectively. Please use a twisted pair
connection for A and B. Connect the other side of this cable to the inverter.
4. Backup Interface includes a built-in meter. If you are using full house backup, you will have to disconnect any other
external export/import meter and remove it from SetApp. The internal meter must be configured as import/export. If you
are using partial home backup, you will have to connect and define an external meter on the main panel and define it as
the import/export meter of the system.
For the Home Hub inverter
installation guide, scan
Cable
Outer diameter of 25-32mm
Cable cross section of 62-162mm
3
6 N*m6 N*m
ON
WARNING!
Only a certified installer is permitted
to perform this operation
ON
In backup or boot
OFF
On grid
Blinking
Firmware upgrade
Fast blinking
Backup interface
received request
to identify itself
ON
Connected to the network/
received modbus packet/ boot
Blinking
There is no communication
over RF or RS485
•On RF –not connected
or temporarily
disconnected
•On RS485 –no packet
received for 30 seconds
Flickering
Bootloader is upgrading
software
Fast blinking
Device received request to
identify itself
Neutral:
Short with
the Ground –
(TNC)
12
1
23
1
2
3
Regular
Neutral
3

Other SolarEdge Recording Equipment manuals

SolarEdge SMI-35-3C-01 User manual

SolarEdge

SolarEdge SMI-35-3C-01 User manual

SolarEdge StorEdge BI-NUSGN-01 User manual

SolarEdge

SolarEdge StorEdge BI-NUSGN-01 User manual

SolarEdge storedge User manual

SolarEdge

SolarEdge storedge User manual

SolarEdge SMI-180 User manual

SolarEdge

SolarEdge SMI-180 User manual

SolarEdge storedge User manual

SolarEdge

SolarEdge storedge User manual

SolarEdge SMI-180 User manual

SolarEdge

SolarEdge SMI-180 User manual

Popular Recording Equipment manuals by other brands

ESI NeON manual

ESI

ESI NeON manual

NEAL 9102 operating instructions

NEAL

NEAL 9102 operating instructions

Arexx SCHOOL LAB CP-01 manual

Arexx

Arexx SCHOOL LAB CP-01 manual

Samson MD1 Direct Box quick start guide

Samson

Samson MD1 Direct Box quick start guide

LS Industrial Systems SV-iS7 Series user manual

LS Industrial Systems

LS Industrial Systems SV-iS7 Series user manual

ProFire 3100 product manual

ProFire

ProFire 3100 product manual

Tapco 2200 user manual

Tapco

Tapco 2200 user manual

TK Audio Transceiver 2 manual

TK Audio

TK Audio Transceiver 2 manual

Zoom G11 Operation manual

Zoom

Zoom G11 Operation manual

Xaoc Devices Poczdam 1989 Leibniz Device Komutator Operator's manual

Xaoc Devices

Xaoc Devices Poczdam 1989 Leibniz Device Komutator Operator's manual

Eventide DIR911 Specifications

Eventide

Eventide DIR911 Specifications

Interface IFVF-2.5K Installation & user manual

Interface

Interface IFVF-2.5K Installation & user manual

Mastervolt MasterBus CANopen Interface user manual

Mastervolt

Mastervolt MasterBus CANopen Interface user manual

Xilica Audio Design XD-8080M user manual

Xilica Audio Design

Xilica Audio Design XD-8080M user manual

MED Associates SG-7000 Series manual

MED Associates

MED Associates SG-7000 Series manual

Symetrix 610 user guide

Symetrix

Symetrix 610 user guide

ETS SM5-EQ instructions

ETS

ETS SM5-EQ instructions

Barco R9828960 quick start guide

Barco

Barco R9828960 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.