
eration
II
6.5.1 Selecting Standard
This function is used to
select
the grid's reference standard (see Figure 6.16).
YES=<ENT>NO=<ESC>
Standard:AS4777-02
.A.
Figure 6.16
Press the UP/DOWN keys to selectthe standard (AS4777-02,AS4777-15, VDE4105, VDE0126,
UL-240V-A, UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3
(for4-SkW models), EN50438 DK, EN50438 IE, EN50438 NL and "User-Def" function).
Press the ENTER keyto confirm the setting. Press the ESC keyto cancel changes and returns
to previous menu.
A
NOTE:
~
This
function
is
for
technicians
use
only.
Selecting the "User-Def" menu will access to the following submenu (see Figure 6.17),
NOTE:
OV-G-V1: 260V
OV-G-V1-
T:
1S
.A.
Figure 6.17
The"
User-Def"
function
can
be
only
used
by
the
service
engineer
and
must
be
allowed
by
the
local
energy
supplier.
Below is the setting range
for
"User-Def". Using this function, the limits can be changed
manually.
OV-G-V1: 240---270V OV-G-F1: 50.2-53Hz(60.2-64Hz)
OV-G-V1-
T:
0.1---9S
OV-G-V2: 240---300V
OV-G-V2-T: 0.1---1S
UN-G-V1: 170---21
OV
UN-G-V1-
T:
0.1---9S
UN-G-V2: 110---210V
UN-G-V2-
T:
0.1---1 S
Startup-
T:
10-600S
OV-G-F1-
T:
0.1---9S
OV-G-F2: 50.2-53Hz(60.2-64Hz)
OV-G-F2-
T:
0.1---9S
UN-G-F1: 47-49.5Hz(56-59.8Hz)
UN-G-F1-T: 0.1---9S
UN-G-F2: 47-49Hz(56-59.8Hz)
UN-G-F2-
T:
0.1---9S
Restore-
T:
10-600S
Press the UP/DOWN keys to scroll through items. Press the ENTER key to editthe
highlighted item. Press the UP/DOWN keys again to change the setting. Press the ENTER
key to save the setting. Press the ESC key to cancel changes and returns to the previous menu.
.30.
6. 0 eration
II
6.5.2 Grid ON/OFF
This function is used to
start
up
or
stop the powergeneration
of
Solis Single Phase
Inverter(see Figure 6.18). Grid ON
Grid OFF
.A.
Figure 6.18
Set
Grid ON/OFF
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key
to save the setting. Press the ESC key to return to the previous menu.
II
6.5.3
Clear
Energy
Clear Energy can reset the historyyield
of
inverter
II
These two functions are applicable by maintenance personnel only, wrong
operation will preventthe
inverter
from working properly.
6.5.4 Reset Password
This function is used to
set
the new password
for
menu "Advanced info." and "Advanced
information" (see Figure 6.19).
YES=<ENT>NO=<ESC>
Password: 0000
.A.
Figure 6.19 Reset password
Enter
the right password before
set
new password. Press the DOWN key to move the
cursor, Press the UP key to revise the value. Press the ENTER key to execute the setting.
Press the ESC key to return to the previous menu.
II
6.5.5
Power
Control
Active and reactive powercan be
set
through powersetting button.
There are 5 item
for
this sub menu:
1.
Set
output
power
2.
Set
Reactive
Power
3.
Out_P
With
Restore
4. Rea_P
With
Restore
5.
Select
PF
Curve
A Thisfunction is
~pplicable
by maint.enance.personnel only, wrong operation
~
will prevent the mverterfrom reachmg max1mum power.
.31
.