RE-1P-2
1-Phase Din-Rail Mount 2kW
Issue Number: 7.1
Date of Issue: 28/04/2020
Four Elms Road Edenbridge
Kent TN8 6AB UK
Features & Benefits
Selectable control input
Over temperature protection with auto reset
Line powered
LED Indication
Efficient electronic switching
No additional heat sinks or RFI filters required
Technical Overview
The 2kW single phase DIN Rail mounting controller is suitable for providing control of electric heating loads from an analogue signal. Applications include
electric heating coils, heating cables and electric furnaces.
The units utilise solid-state switching with “zero crossing technology” to provide accurate switching control. All items are provided with an alarm output for
over temperature protection and LED Indication of Output ON, and are designed to mount on DIN rail.
Specification
Input signal Selectable
0-10V, 0-5V, 2-10V or 4-20mA
Supply (load) 220-255Vac 50/60Hz
Max. load 9A
Dissipated heat 9W
Terminal connections Rising cage
Over temperature:
Trip in temp. @ 90°C
Trip out temp. @ 85°C
LED indication ON when output is on
Alarm output (as power supply) 0V when over temp
alarm is active
Ambient temperature 0-45°C without de-rating *
Dimensions (W, H, D) 75 x 94 x 80mm
Conformity CE Marked
Country of origin UK
* Units are rated at 45°C. If using at higher ambient temp, de-rate the
units by 10% for every 5°C above 45°C
The products referred to in this data sheet meet the requirements of EU
2014/30/EU and 2014/35/EU
Product Codes
RE-1P-2 2kW, 9A, Single-phase Din-rail Mount Heating
Regulator
WEEE Directive:
At the end of the products useful life please dispose as
per the local regulations.
Do not dispose of with normal household waste.
Do not burn.
Tel: +44 (0)1732 861200 - E-mail: sales@sontay.com - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 2 of 4
RE-1P-2
1-Phase Din-Rail Mount 2kW
Issue Number: 7.1
Date of Issue: 28/04/2020
Four Elms Road Edenbridge
Kent TN8 6AB UK
SAFETY REQUIRMENTS & ADVICE SHEET
Introduction
The objective of this leaflet is to provide information to ensure that the safety of the person(s) installing or maintaining the equipment is not compromised
and its location and method of installation does not endanger others, either during or after installation. Customers should be aware of the Health and
Safety at Work Act 1974 (HSW 1974) and the EC “Provision and Use of Work Equipment Regulations 1992” (PUWER). Both are available from the Health
and Safety Executive (HSE) publications, within the UK.
Installation
CE Directives
These are European regulations which apply to our industry. They affect the equipment emissions and immunity to Radio Frequency Interference (RFI) and
various elements of safety for electrical equipment.
The European Community ‘CE’ Directives that mainly concern Sontay Ltd are the Low Voltage Directive (LVD) and the Electromagnetic Compliance
Directive (EMC).
A Declaration of Conformity may be supplied with the product or supplied on request.
Torque Settings
Good working practises must be adhered to ensuring appropriate electrical and mechanical installation. This would include the mechanical fixing of
potentiometer bushes and electrical set screw and/or pillar connections. These Electrical Connections and Mechanical Fastenings must not be over
tightened. We would recommend a typical torque setting of 1 to 5Nm. For specific product information, see appropriate product data sheet, where
applicable.
Cooling Requirements
The use of an additional heatsink (this could be a conductive panel) suitably attached or mounted with the unit, will help to dissipate heat away from the
device(s). An alternative or additional method would be forced air-cooling (using a fan), to assist the natural convection of airflow over an existing
heatsink within the unit. The product fins should be mounted in line with the forced and/or natural airflow.
The equipment’s environment and its initial ambient temperature also need to be considered, as this could have an adverse effect on the overall operating
conditions.
Fusing
We recommend that semiconductor, fast acting to BS88 IEC 269, type fuses or circuit breakers (Semiconductor - MCB) should be used for unit and/or
device protection. The appropriate maximum load current should be known to select the required fuse or MCB, but must not exceed the equipment
rating. The I² t (A² s) rating of the selected fuse must be less than that of the equipment so as to protect the equipment’s discrete device. Further
appropriate fusing may be required for protection of the unit supply using standard fuse links and holders. Failure to address these requirements and the
use of incorrectly selected fuses may cause the equipment to fail.
Earthing
The protective conductor terminal of the equipment must be utilised at all times and bonded to a ‘good’ Earth (ground). The earth bonding (strapping)
leads of any combined equipment should be as short as possible and be substantial, i.e. at least rated higher than the equipment’s load. For further
information, refer to BS7671. Following these simple guidelines will ensure optimum use of any appropriate filter circuits which may be required.
Insulation (over-voltage category) and Protection from electric shock Classification of Equipment
All equipment, unless otherwise stated, is rated to CLASS II Insulation (Over-voltage category) and CLASS I (Protection category).
Maintenance
Before any servicing is carried out, reference should be made to appropriate installation instructions, drawings and labelling which may come with the
equipment. Personnel should switch off the unit supply before accessing or removing any safety cover and be aware of hazardous live parts.
Safety Interlocks for Sontay RE Electric Heater Battery Controllers
Sontay Ltd. recommends that the installation and maintenance of all RE electric heater battery controllers should be done with reference to BS
7671:2008+A3:2015 (Requirements for Electrical Installations. IET Wiring Regulations).
All users of the IET Wiring Regulations should be aware of changes in Amendment No. 3 to the 17th Edition. Amendment No. 3 came into effect on 1 July
2015.
For international installations, please refer to local regulations for guidance.
Tel: +44 (0)1732 861200 - E-mail: sales@sontay.com - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 3 of 4
RE-1P-2
1-Phase Din-Rail Mount 2kW
Issue Number: 7.1
Date of Issue: 28/04/2020
Four Elms Road Edenbridge
Kent TN8 6AB UK
SAFETY REQUIRMENTS & ADVICE SHEET (continued)
Adherence to BS 7671, Chapter 42 (Protection Against Thermal Effects), and in particular;
420.3 –General Requirements,
421 –Protection Against Fire Caused by Electrical Equipment
o421.1
o412.2
422 –Precautions Where Particular Risks of Fire Exist
o422.1.2
o422.1.3
should be undertaken, and as a minimum, a mains isolation switch, a load-breaker switch and a contact breaker should be installed in the electric heater
battery controller supply. The supply to the contactor coil should be interrupted by an over-temperature (hi-limit) thermostat located in the heater battery
and also upon detection of airflow loss (fan proving), via an air flow switch, air DP switch across the fan or fan current switch in the fan supply.
Additionally, EN 61508-1:2010 (Functional safety of electrical/electronic/ programmable electronic safety-related systems. General requirements)
stipulates the general requirements for electrical, electronic and programmable electronic safety devices, and covers the safety systems of electrical
equipment and their components that could have an impact on the safety of people and the environment if they fail. BS EN 61508-1 also applies to
protection and control systems, and helps organisations to identify hazards to improve overall equipment safety in the workplace.
Failure to incorporate these safety interlocks may result in the invalidation of fire insurance, building and contents insurance, and in extreme cases may
result in the disconnection of the electrical supply by the distributor.
Operation, Installation & Configuration
The RE-1P-2 has been designed to control electric heating loads in proportion to the incoming, selectable analogue signal. Control of the load is facilitated
by the use of solid-state semiconductor devices and feature zero crossing point switching of the AC load which virtually eliminates RFI problems.
Caution
In normal operation the heat sink surface can exceed 90°C. Dangerous voltages exist on the PCB and particular care should be taken. RE-1P-2 must be
installed in accordance with the relevant statutory regulations and installation must be carried out by an experienced and fully qualified engineer.
Ventilation
The RE-1P-2 is suitable for use up to a maximum ambient temperature of 45°C which should not be exceeded. If necessary, enclosures or control panels
should be ventilated with a cooling fan, particularly if the unit is being used to run at full power to provide forced cool air movement over the heat sink.
Over Temperature Monitoring
The RE-1P-2 is provided with an electronic thermal cut-out fitted to the heat sink to protect against over temperature. The unit will switch off the load if
the heat sink temperature exceeds 95°C and will automatically reconnect the load once the heat sink temperature has dropped below 85°C. Upon
switching, the alarm output from the control PCB will change from 24V to 0V.
The heat sink temperature will not reach 95°C under normal operating conditions. However, this might occur if the ambient temperature exceeds 45°C.
The RP-1P-2 is suitable mounting on DIN Rail and must be installed with the heat sink cooling fins orientated vertically. There should be a minimum of
100mm vertically between units.
Electrical Installation
Installation must be carried out by a suitably trained electrician, and in accordance with the relevant statutory regulations.
Load Supply and Back-up Protection
High speed fuses or miniature circuit breakers should be utilised to provide back-up protection to the switching devices. It is recommended that a load
disconnect switch and a contactor are installed in the load supply. The supply to the contactor coil should be interrupted by an over-temperature
thermostat located in the heater battery and also upon detection of airflow loss.
Control Supply
It is essential to connect your neutral to the neutral terminal.
See wiring for details. The control supply common is linked to the 0-10V Input Signal common. Screened cable should be used for connections to BMS
Controllers, where possible the cable screen should be connected to a functional earth and at one end only to avoid earth loops.
Tel: +44 (0)1732 861200 - E-mail: sales@sontay.com - Web: www.sontay.com
© 2017 Sontay Limited. All rights reserved
Page 4 of 4
RE-1P-2
1-Phase Din-Rail Mount 2kW
Issue Number: 7.1
Date of Issue: 28/04/2020
Four Elms Road Edenbridge
Kent TN8 6AB UK
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or expense
from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.
Operation, Installation & Configuration (continued)
Cycle Time
The unit is supplied with the cycle time set to minimum (fully anticlockwise). An on board potentiometer is provided to facilitate adjustment of the cycle
time in the range of 5 (default) to 60 seconds. Adjustment is not normally required, incorrect adjustment can cause an overload condition.
Maximum Heating Load
The power rating of the units are given as a guide. The maximum current (which is dependent on the actual supply voltage and heating load) must not be
exceeded.
Jumper Settings & Connections
Voltage inputs: Current inputs:
0-10Vdc 0-5Vdc 2-10Vdc 1-5Vdc 4-20mA 2-10mA 0-20mA 0-10mA
I/V Jumper
I/V Jumper
Control Signal
0V
NO CONNECTION
NO CONNECTION
24V Alarm (output)
0V Alarm (output)
230Vac Load

Other Sontay Controllers manuals

Sontay RE-3P Series User manual

Sontay

Sontay RE-3P Series User manual

Sontay SC-RC User manual

Sontay

Sontay SC-RC User manual

Sontay WD-AMX User manual

Sontay

Sontay WD-AMX User manual

Sontay RE-1P-4N User manual

Sontay

Sontay RE-1P-4N User manual

Sontay RE-PR3-E Series User manual

Sontay

Sontay RE-PR3-E Series User manual

Sontay WD-AMX User manual

Sontay

Sontay WD-AMX User manual

Sontay RE-3P-105 User manual

Sontay

Sontay RE-3P-105 User manual

Popular Controllers manuals by other brands

Xylem McDonnell & Miller 1575 Series instruction manual

Xylem

Xylem McDonnell & Miller 1575 Series instruction manual

ARMATURA OmniAC20CAPQ installation guide

ARMATURA

ARMATURA OmniAC20CAPQ installation guide

elco PISCES MINIFILL E1/1 INSTRUCTIONS FOR INSTALLATION, SERVICING & MAINTENANCE

elco

elco PISCES MINIFILL E1/1 INSTRUCTIONS FOR INSTALLATION, SERVICING & MAINTENANCE

Emerson Bettis BHH Series Installation, operation and maintenance manual

Emerson

Emerson Bettis BHH Series Installation, operation and maintenance manual

Danfoss EKC 202A instructions

Danfoss

Danfoss EKC 202A instructions

Kongskilde EAR 100 quick start guide

Kongskilde

Kongskilde EAR 100 quick start guide

SMC Networks JXCP1 Original instructions

SMC Networks

SMC Networks JXCP1 Original instructions

Novanta ScanMaster user manual

Novanta

Novanta ScanMaster user manual

Pilz PSS Series operating manual

Pilz

Pilz PSS Series operating manual

Casambi NB. 1 quick start guide

Casambi

Casambi NB. 1 quick start guide

Vyrsa Skydrop Installation and quick start guide

Vyrsa

Vyrsa Skydrop Installation and quick start guide

Topcon ISOCAN installation manual

Topcon

Topcon ISOCAN installation manual

Emerson FISHER SR8 installation guide

Emerson

Emerson FISHER SR8 installation guide

Seg CA01H instruction manual

Seg

Seg CA01H instruction manual

Emerson Fisher EZR series installation guide

Emerson

Emerson Fisher EZR series installation guide

Canarm MC3 installation instructions

Canarm

Canarm MC3 installation instructions

STORK TRONIC ST181-VL4KA.12 manual

STORK TRONIC

STORK TRONIC ST181-VL4KA.12 manual

Satel ABAX 2 ACU-280 manual

Satel

Satel ABAX 2 ACU-280 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.