
Page 2
Moisture and particles too small for the inlet strainer are harm-
ful to the system and must also be removed. Therefore, for
complete system protection, it is recommended that a Catch-
All Filter-Drier be installed in the liquid line according to the
application recommendations given in Bulletin 40-10.
Moisture detection is easily and inexpensively provided with
the installation of a See·All moisture and liquid indicator.
Complete information is given in Bulletin 70-10. Furthermore,
a See·All moisture and liquid indicator at the receiver is
necessary to charge the system properly.
BRAZING PROCEDURES — Any of the commonly used
brazing alloys for high side usage are satisfactory. However,
when soldering or brazing, it is very important that the
internal parts be protected by wrapping the valve with a
WET cloth to keep the body temperature below 250°F for
the OROA and ORI; and, 300°F for the ORD-4. Also, when
using high temperature solders, the torch tip should be large
enough to avoid prolonged heating of the copper connections.
And, always direct the flame away from the valve body.
TEST and OPERATING PRESSURES — Excessive leak
testing or operating pressures may damage these valves and
reduce the life of the operating members. For leak detection,
an inert dry gas, such as nitrogen or CO2, may be added to an
idle system to supplement the refrigerant pressure.
CAUTION: Inert gases must be added to the system
carefully through a pressure regulator. Unregulated
gas pressure can seriously damage the system and
endanger human life. Never use oxygen or explosive
gases.
The table below lists the maximum values each valve can
withstand without damage. Precautions must be taken to keep
test or operating pressures below these values.
VALVE SETTINGS and ADJUSTMENT — A complete
discussion on pressure settings is given in the Application
Section of Bulletin 90-30. To determine the proper setting for
a specific system, that section should be reviewed.
Table 1 lists the setting data for the OROA, ORI and ORD
valves. Other ORI settings can be obtained by adjusting the
valves a proportionate amount between those values shown.
The ORD-4-20 setting means that the ORD-4 will start to
open when the pressure difference between the discharge
line and the receiver is 20 psig. This setting is suitable for
all systems where the combined pressure drop through the
condenser, the ORI and connecting piping is less than 14
psi. Therefore, if the ORI is selected for 2 psi ∆P, then the
maximum allowable pressure drop through the condenser is
12 psi. Normally, condenser pressure drop on refrigeration
systems is less than 10 psi. However, many condensers on
air-conditioning systems may have pressure drops up to 25
psi. Therefore, when in doubt, consult with the equipment
manufacturer or, if possible, measure it by reading the dis-
charge pressure at the compressor and the receiver pressure
during full load operation. That is, this reading should be
taken with a normal condensing temperature at full load. For
systems where the condenser pressure drop is higher than
normal, OROA and ORD valves with higher settings are
available upon special request. See Table 4, page 4.
To adjust the ORI valve, remove the cap and turn the adjust-
ment screw with the proper size hex wrench (1/4” for ORI-6
and 5/16” for ORI-10). A clockwise rotation increases the
valve setting while a counter-clockwise rotation decreases
the setting. To obtain the desired setting, a pressure gauge
should be utilized at the compressor discharge service valve
so the effects of any adjustment can be observed. Small
adjustments are recommended to allow the system adequate
time to settle out after each adjustment.
NOTE: Even though the ORI valve is selected on the basis
of the full load conditions or summer operation, it should be
adjusted to maintain the desired condensing pressure when-
ever the ambient is below 70°F.
REFRIGERANT CHARGE AND CHARGING
PROCEDURES — When this method of head pressure con-
trol is utilized on a system, there must be enough refrigerant
to flood the condenser at the lowest expected ambient and
still have enough charge in the system for proper operation.
A shortage of refrigerant will cause hot gas to enter the liquid
line and the expansion valve, and refrigeration will cease.
Secondly, the receiver must have sufficient capacity to hold
at least all of the excess liquid refrigerant in the system, since
it will be returned to the receiver when high ambient condi-
tions prevail. If the receiver is too small, liquid refrigerant
will be held back in the condenser during the high ambient
conditions and excessively high discharge pressures will be
experienced.
CAUTION: All receivers must utilize a pressure relief device
according to the applicable standards or codes (e.g. ARI
Standard 495).
The charging instructions described on page 3 use average val-
ues. The exact charge required will vary with unit design and
piping. These instructions are intended to provide assistance to
the service technician where specific charging instructions for
the condensing units involved are not available.
Charging Procedure:
1. Before starting the system, charge approximately 2-1/2
lbs. per ton of liquid refrigerant into the receiver or
enough refrigerant to provide a liquid seal in the receiver.
2. Put refrigerant vapor into the suction side to break the
vacuum.
3. Start the system and charge to a clear See·All moisture
and liquid indicator.
Table 1
Valve Type Maximum Rated
Pressure - psig
OROA 450
ORI-6-65/225-H 450
ORI-10-65/225-H 450
ORD-4 680
Valve
Type
Standard Factory
Setting for
Refrigerants
12 & 134a
Setting For Refrigerants
22, 404A & 507
Pressure
Setting
psig
Depth of
adjusting
nut from
top of
Spring
Housing
Pressure
Setting
psig
Depth of
adjusting
nut from
top of
Spring
Housing
Turns IN
from
Refrigerant
12 Setting
OROA 100 - 180 - -
ORI-6 120 1/4” 200 1/2” 3
ORI-10 120 3/8” 200 3/4” 5
ORD-4-20 20 - 20 - -