Application Note Product: 512C
Document Number: 4002 Keywords: Quick Set-Up
If you have questions, please call the Product Support Group at (704) 588-3246.
Issue 1.1 4-Jun-10 Page 3 of 4
OFF OFF OFF ½A 1A * 2A * 4A *
ON OFF OFF 1A 2A * 4A * 8A *
OFF ON OFF 1½A 3A * 6A * 12A *
ON ON OFF 2A 4A * 8A * 16A *
OFF OFF ON 2½A 5A 10A 20A
ON OFF ON 3A 6A 12A 24A
OFF ON ON 3½A 7A 14A 28A
ON ON ON 4A 8A 16A 32A
Example Customer wishes to run 14 Amp Motor.
Option 1 Using 512/16 - From table 4.2 set SW7 ON, SW6 ON, SW5 OFF Ia = 14
Amp
Option 2 Using 512/32 From table 4.2 set SW7 OFF, SW6 ON, SW5 ON - Ical = 16
Amp
Turn down I Limit (P4) to give 14 Amps
Note: * 8 Amp, 16 Amp and 32 Amp controllers can be scaled to currents of 4 Amp, 8
Amp or 16 Amp or less but it is recommended that lower current controllers be
used in these circumstances.
Current Motor Scaling
SW8
(OFF) Current Meter Buffered Current Meter Output
5V Equivalent to 100% of Controller Current Rating.
i.e. 4 Amp on 512C/04
8 Amp on 512C/08
16 Amp on 512C/16
32 Amp on 512C/32
SW8
(ON) Current Meter Buffered Current Meter Output
5V Equivalent to 100% of Calibrated Current Rating.
For Example 512C/16 SW5-ON,SW6-ON,SW7-OFF
Calibrated Current = 8 Amp therefore 5V = 8amp.
POTENTIOMETERS
P1 Ramp Up Rate Rotate Clockwise for Faster Acceleration to Set
Speed.
Same
(Linear :- 1 to 40 seconds) as 512
P2 Ramp Down Rate Rotate Clockwise for Faster Deceleration to Set
Speed.
Same
(Linear :- 1 to 40 seconds) as 512