Operating instructions
Additional languages www.r-stahl.com
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S

2
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
Contents
1 General Information ............................................................................................3
1.1 Manufacturer .......................................................................................................3
1.2 Information regarding the operating instructions .................................................3
1.3 Further documents ..............................................................................................3
1.4 Conformity with standards and regulations .........................................................3
2 Explanation of the symbols .................................................................................4
2.1 Symbols in these operating instructions .............................................................4
2.2 Warning notes .....................................................................................................4
2.3 Symbols on the device ........................................................................................5
3 Safety notes ........................................................................................................5
3.1 Operating instructions storage ............................................................................5
3.2 Safe use ..............................................................................................................5
3.3 Modifications and alterations ..............................................................................6
4 Function and device design ................................................................................6
4.1 Function ..............................................................................................................6
5 Technical data .....................................................................................................7
6 Transport and storage .........................................................................................8
7 Mounting and installation ....................................................................................9
7.1 Dimensions / fastening dimensions ....................................................................9
7.2 Mounting / dismounting, operating position ......................................................10
7.3 Installation .........................................................................................................14
8 Commissioning .................................................................................................15
9 Operation ..........................................................................................................15
9.1 Troubleshooting ................................................................................................15
10 Maintenance and repair ....................................................................................16
10.1 Maintenance .....................................................................................................16
10.2 Repair ...............................................................................................................17
10.3 Returning the device .........................................................................................17
11 Cleaning ............................................................................................................17
12 Disposal ............................................................................................................18
13 Accessories and Spare parts ...........................................................................18

224618 / FL6S60300010
2018-05-24·BA00·III·en·02
General Information
3
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
1 General Information
1.1 Manufacturer
1.2 Information regarding the operating instructions
ID-No.: 224618 / FL6S60300010
Publication Code: 2018-05-24·BA00·III·en·02
The original instructions are the English edition.
They are legally binding in all legal affairs.
1.3 Further documents
• Data sheet
For documents in additional languages, see www.r-stahl.com.
1.4 Conformity with standards and regulations
See certificates and EC Declaration of Conformity: www.r-stahl.com.
The device has IECEx approval. For certificate please refer to the IECEx homepage:
http://iecex.iec.ch/
R. STAHL Schaltgeräte GmbH
Business Unit Lighting & Signalling
Nordstr. 10
99427 Weimar
Germany
R. STAHL Schaltgeräte GmbH
Am Bahnhof 30
74638 Waldenburg
Germany
Phone:
Fax:
Internet:
E-mail:
+49 3643 4324
+49 3643 4221-76
www.r-stahl.com
Phone:
Fax:
Internet:
E-mail:
+49 7942 943-0
+49 7942 943-4333
www.r-stahl.com

Explanation of the symbols
4224618 / FL6S60300010
2018-05-24·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
2 Explanation of the symbols
2.1 Symbols in these operating instructions
2.2 Warning notes
Warnings must be observed under all circumstances, in order to minimize the risk due to
construction and operation. The warning notes have the following structure:
• Signalling word: DANGER, WARNING, CAUTION, NOTICE
• Type and source of danger/damage
• Consequences of danger
• Taking countermeasures to avoid the danger or damage
Symbol Meaning
Tips and recommendations on the use of the device
General danger
Danger due to explosive atmosphere
Danger due to energised parts
= Strobe
= Earth
= Telephone initiate
DANGER
Danger to persons
Non-compliance with the instruction results in severe or fatal injuries to
persons.
WARNING
Danger to persons
Non-compliance with the instruction can result in severe or fatal injuries to
persons.

224618 / FL6S60300010
2018-05-24·BA00·III·en·02
Safety notes
5
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
2.3 Symbols on the device
3 Safety notes
3.1 Operating instructions storage
• Read the operating instructions carefully and store them at the mounting location of
the device.
• Observe applicable documents and operating instructions of the devices to be
connected.
3.2 Safe use
• Read and observe the safety notes in these operating instructions!
• Observe characteristic values and rated operating conditions on the rating and data
plates!
• Observe additional information plates on the device!
• Use the device in accordance with its intended and approved purpose only!
• We cannot be held liable for damage caused by incorrect or unauthorized use or by
non-compliance with these operating instructions.
• Before installation and commissioning, make sure that the device is not damaged!
• Work on the device (installation, maintenance, overhaul, repair) may only be carried
out by appropriately authorized and trained personnel.
CAUTION
Danger to persons
Non-compliance with the instruction can result in light injuries to persons.
NOTICE
Avoiding material damage
Non-compliance with the instruction can result in material damage to the device and / or
its environment.
Symbol Meaning
05594E00
CE marking according to the current applicable directive.
02198E00
According to marking, device certified for hazardous areas.
15649E00
Input
15648E00
Output

Function and device design
6224618 / FL6S60300010
2018-05-24·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
3.3 Modifications and alterations
4 Function and device design
4.1 Function
Product series FL6S is designed to provide a visual signal which can be used to alert,
warn or draw attention to an event. Corrosion resistance is a key feature of the device
which is ideally suited for applications in the harshest of environments both onshore and
offshore.
The device must be regarded as a supplementary alarm indicator when used for
alerting/evacuating the occupants of the buildings/structures.
In hazardous areas the devices have explosion protection for ATEX/IECEx Zones 1 & 2
for gas and 21 & 22 for dust. Gas groups covered are IIB & IIC, and dust protection for
IIIC.
The device is not intended for continuos use.
The life of the xenon flash tube is guaranteed for the following number of flashes:
DANGER
Explosion hazard due to modifications and alterations to the device!
Non-compliance results in severe or fatal injuries.
• Do not modify or alter the device.
No liability or warranty for damage resulting from modifications and
alterations.
DANGER
Explosion hazard due to improper use!
Non-compliance results in severe or fatal injuries.
• Use the device only according to the operating conditions described in
these operating instructions.
Variant Number of flashes
5 J 2 million

224618 / FL6S60300010
2018-05-24·BA00·III·en·02
Technical data
7
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
5 Technical data
Explosion Protection
Global (IECEx)
Gas and dust IECEx BAS 14.0064
IEC 60079-0: 2011 / IEC 60079-1: 2007 / IEC 60079-31: 2013
Ex d IIB T* Ta -** ... +** °C Gb
Ex d IIC T* Ta -** ... +** °C Gb
Ex tb IIIC T*** °C Ta -** ... +** °C Db IP66
Europe (ATEX)
Gas and dust Baseefa14ATEX0126
EN 60079-0: 2012 / EN 60079-1: 2007 / EN 60079-31: 2009
(IEC 60079-31: 2013)
E II 2 G Ex d IIB T* Ta -** ... Ta +** °C Gb
E II 2 G Ex d IIC T* Ta -** ... Ta +** °C Gb
E II 2 D Ex tb IIIC T*** °C Ta -** ... +** °C Db IP66
Product variant table
Certifications and certificates
Certificates IECEx, ATEX, Kazakhstan (TR), Russia (TR), Belarus (TR)
Ambient conditions
Operating
temperature range
Power and
voltage
Temperature
class
Max. surface
temperature
Ambient temperature
range
5 J 24 V DC T6 T73 °C -60 to +40 °C
T5 T88 °C -60 to +55 °C
T4 T103 °C -60 to +70 °C
5 J 48 V DC T6 T73 °C -60 to +40 °C
T5 T88 °C -60 to +55 °C
T4 T103 °C -60 to +70 °C
5 J 115 V AC T5 T83 °C -60 to +40 °C
T4 T113 °C -60 to +55 °C
5 J 230 V AC T6 T75 °C -60 to +40 °C
T5 T90 °C -60 to +55 °C
T4 T105 °C -60 to +70 °C
24/48 V DC -50 to +70 °C
115 V AC -55 to +55 °C
230 V AC -55 to +70 °C

Transport and storage
8224618 / FL6S60300010
2018-05-24·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
For further technical data, see www.r-stahl.com.
6 Transport and storage
• Transport and store the device only in the original packaging.
• Store the device in a dry place (no condensation) and vibration-free.
• Do not drop the device.
Technical Data
Electrical data
Rated operational
voltage
24 or 48 V DC
115 or 230 V AC
Current consumption
Operational
parameters
+/-10 %
Line monitoring yes
Inrush current
Luminous characteristics
Light source Xenon flash tube
Flash energy 5 J
Flash rate 1/s
Light intensity
Lens colour amber, red, green, opal, blue, clear, yellow, magenta
Mechanical data
Material
Enclosure glass reinforced polyester
Lens cover polycarbonate
Wire guard stainless steel
Assembly parts stainless steel
Bracket stainless steel
Labels polyester foil, adhesive
Degree of protection IP66 / IP67 acc. to IEC 60529
Mounting / Installation
Connection 2.5 mm2 terminals
24 V DC 320 mA
48 V DC 170 mA
115 V AC 204 mA
230 V AC 75 mA
24 V / 48 V DC 115 V AC 230 V AC
Imax duration Imax duration Imax duration
3.2 A 220 μs 11 A 500 μs 8 A 50 μs
Effective candela
(cd)
Luminous flux
(Im)
clear 62 12.5

224618 / FL6S60300010
2018-05-24·BA00·III·en·02
Mounting and installation
9
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
7 Mounting and installation
7.1 Dimensions / fastening dimensions
Dimensional Drawings (All Dimensions in mm [inches]) - Subject to Alterations
17149E00 16920E00
GRP Visual Signal Series FL6S
with L-Bracket
GRP Visual Signal Series FL6S
without L-Bracket
17159E00
L-Bracket
189 [7,44]
[4,61]
117
287,50 [11,32]
95
[3,74]
75
[2,95]
105
[4,13]
ØØ
9 [ 0,35]
40 [1,57]
178,50 [7,03]
178,50 [7,03]
3 x M6
75
[2,95]
32
[1,26]
40 [1,57]
148 [5,83]
20 [,9]0 7
75 2 95[, ]
ø9 [,]ø0 35
117 [4,61]
105 4 13[, ]

Mounting and installation
10 224618 / FL6S60300010
2018-05-24·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
7.2 Mounting / dismounting, operating position
• Mount the device on a flat surface suitable for its weight.
• Insert the cables using certified and flameproof cable glands which are suitable for the
gas group.
• Close unused entries using certified and flameproof stopping plugs.
7.2.1 Installation Conditions for Electrical Connection
DANGER
Risk of explosion!
Risk of injuries and material damage!
• Terminal sleeves are fitted, they must be gas-tight and applied with a
suitable tool.
DANGER
Explosion hazard!
Risk of injuries and material damage!
• Carefully remove or replace the components.
• Exposed joint surfaces must not be damaged and must be protected
from dust and dirt.
• Install the end flanges squarely without applying any force. Do not use
a hammer or other tools when working on the flanges and do not use the
fixing screws to pull down the flanges.
DANGER
Explosion hazard!
Risk of injuries and material damage!
• Only use cable glands with corresponding certificate. The cable glands
must be flameproof (Ex d) and suitable for the type of cable used.
• Close unused open holes in the enclosure with flameproof stopping
plugs.
• Close unused cable glands using flameproof plugs.
• Cable glands, stopping plugs and plugs must meet the requirements of
IEC/EN 60079-14.
• Installation of the cable gland must be performed in accordance with the
manufacturer's instructions.
• Cable entry temperature may reach 70 °C.
• To ensure degree of protection IP 66, a non-hardening sealant must be
applied to the threads.
DANGER
Danger due to energised parts!
Risk of death or severe injuries!
• Before opening and dismounting the device, disconnect it from the
power supply.
• Secure the device against unauthorized switching.

224618 / FL6S60300010
2018-05-24·BA00·III·en·02
Mounting and installation
11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
7.2.2 Installation with mounting bracket
• Loosen 6 x cheese head screws (6) and remove strobe flange (5)
• Prepare cable gland
• Ensure earth connection
• Install cable gland
• Connect cables (see electrical connection)
• Fix bracket to wall • Attach device
17161E00 17225E00
17158E00
1End cap
2 PCB Termination board
3 PCB and Xenon flash tube
4Seal
5 Strobe flange
6 Cheese-head screws M5 x 25
Access to the M5 cheese head screws is obscured by the wire guard.
Use a ball end Allen key to allow for the off-axis angle which is required.
4
5
6
3
1
2

Mounting and installation
12 224618 / FL6S60300010
2018-05-24·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
7.2.3 Reassembly of Enclosure
• Lift strobe flange towards device.
• Connect PCB using the plug.
• Install strobe flange.
• Replace cheese-head screws M5 x 25 (see information below) and tighten the screws
with a tightening torque of 4 Nm.
7.2.4 Electrical Connection
Key Components
17229E00
1 Plug for flash PCB
2 Terminal blocks
3 PCB Termination board
17164E00
1 Xenon flash tube
2Flash PCB
Key components FL6S
• Do not touch the Xenon flash tube at anytime during the
installation/assembly of the device.
1
2
3
2
1

224618 / FL6S60300010
2018-05-24·BA00·III·en·02
Mounting and installation
13
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
Cable Connection
Interconnection of devices parallel
Up to 10 devices with common supplies may be connected as a single system loop.
See wiring diagrams for further information.
Circuit diagrams
• The terminals accept wires of 2.5 mm2 or 14 to 18 AWG.
Line monitoring for devices with DC
• by reverse polarity
• by connecting an EOL resistor between 0 V and +V.
The resistance value is defined by the system developer.
15758E00 15759E00
Circuit diagram DC voltages Circuit diagram AC voltages
= Strobe
INITIATE
TELEPHONE
TB1 TB2 TB3 TB4
0V
0V
+V
+V
INITIATE
TELEPHONE
TB1 TB2 TB3 TB4
N
N
L
L

Mounting and installation
14 224618 / FL6S60300010
2018-05-24·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
7.2.5 Earth Connection
Use of metallic cable glands
A slip on earth tag is provided with each device. This should be connected to the external
earth stud detailed above.
Device material
The GRP material used for the device enclosure has electrically conductive properties.
The material is antistatic and prevents build-up of electrical charges on its surface.
Surface resistivity < 108 Ω accordance to IEC 60093
7.3 Installation
17191E00
Earth connection
WARNING
Danger of electric shock due to energised parts!
Non-compliance can result in severe or fatal injuries.
• All connections and wiring must be disconnected from the power supply.
• Secure the connections against unauthorized switching.
DANGER
Explosion hazard!
Risk of injuries and material damage!
• Operate the device only if it is not damaged.
• If the thread is damaged, the device must be replaced immediately.
• Handle the device and the components very carefully.
• Exposed joint surfaces must be protected from dust, dirt and damage.
• Mount the end flanges squarely and do not apply any force.
• Do not use a hammer or any other metal instruments to work on the
flange.
• Do not use the fixing screws to pull down the flange.
• Install the device only in a clean and dry operating environment.
E

224618 / FL6S60300010
2018-05-24·BA00·III·en·02
Commissioning
15
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
8 Commissioning
Before commissioning, ensure the following:
• the device has been installed according to regulations.
• the power supply voltage and the rated operational voltage are identical.
• the required cable diameter for cable glands has been used.
• the cable entries and stopping plugs have been securely tightened.
• the cables are correctly connected.
• the connection has been performed correctly.
• all screws and nuts are tightened according to regulations.
• the connection chamber is clean.
• the device is not damaged.
• no foreign bodies are inside the device.
• the device is sealed according to regulations.
• flash circuit board is connected.
9 Operation
The device is used to warn and alert by means
• of a visual signal.
24 V DC and 48 V DC voltage variants - visual signal
9.1 Troubleshooting
If an error occurs please re-visit the earlier sections of this document.
If the error cannot be eliminated using the mentioned procedures:
• Contact R. STAHL Schaltgeräte GmbH.
For fast processing, have the following information ready:
• Type and serial number
• Purchase information
• Error description
• Intended use (in particular input / output wiring)
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation and function before
commissioning.
• Comply with the national regulations.
At temperatures below -40°C initial start-up and stabilization of flash
frequency may be delayed.

Maintenance and repair
16 224618 / FL6S60300010
2018-05-24·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
10 Maintenance and repair
10.1 Maintenance
• Determine the type and extent of inspections in compliance with the relevant national
regulations.
• Adapt inspection intervals to the operating conditions.
The following tests and measures must be carried out during regular maintenance.
WARNING
Risk of electric shock or malfunctioning of the device due to unauthorized
work!
Non-compliance can result in severe injuries and material damage.
• Work performed on the device must only be carried out by appropriately
authorized and qualified electricians.
Observe the relevant national regulations in the country of use.
Check Measures
the permissible ambient temperature If exceeding the permissible ambient
temperature or falling below the device
must be taken out of operation.
the enclosure components for formation
of cracks and damage.
Replace the exchangeable enclosure
components. If the enclosure components
are non-exchangeable, the device must be
taken out of operation.
its intended use If the device is not used according to its
intended use, it must be taken out of
operation.
if the conductors are clamped properly clamp loose conductors tightly.
the cables for ageing and damage replace damaged or aged cables.
the seals for ageing and damage replace damaged, aged and porous seals
and completely change enclosure
components with foamed seal.

224618 / FL6S60300010
2018-05-24·BA00·III·en·02
Cleaning
17
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
10.2 Repair
10.3 Returning the device
• Only return or package the devices after consulting R. STAHL!
Contact the responsible representative from R. STAHL.
R. STAHL's customer service is available to handle returns if repair or service is required.
• Contact customer service personally.
or
• Go to the www.r-stahl.com website.
• Under "Support" > "RMA form", select "Request RMA slip".
• Fill out the form and send it.
Confirmation will be sent. R. STAHL's customer service will contact you.
You will receive an RMA slip after speaking with customer service.
• Send the device along with the RMA slip in the packaging to
R. STAHL Schaltgeräte GmbH (refer to Section 1.1 for the address).
11 Cleaning
• Clean the device only with a cloth, brush, vacuum cleaner or similar items.
• When cleaning with a damp cloth, use water or mild, non-abrasive, non-scratching
cleaning agents.
• Do not use aggressive detergents or solvents.
DANGER
Explosion hazard due to improper repair!
Non-compliance results in severe or fatal injuries.
• Repair work on the devices must be performed only by
R.STAHL Schaltgeräte GmbH.

Disposal
18 224618 / FL6S60300010
2018-05-24·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
GRP Flameproof Visual Signal - 5 Joule
Series FL6S
12 Disposal
• Observe national and local regulations and statutory regulation regarding disposal.
• Separate materials when sending it for recycling.
• Ensure environmentally friendly disposal of all components according to the statutory
regulations.
13 Accessories and Spare parts
NOTE
Malfunction or damage to the device due to the use of non-original components.
Non-compliance can result in material damage.
• Use only original accessories and spare parts from R. STAHL Schaltgeräte GmbH.
For accessories and spare parts, see data sheet on our homepage
www.r-stahl.com.