Suntex EC-4110 User manual

1
EC-4110
ʳ
Intelligent
ʳ ʳ
Conductivity
Transmitter
Operation
Manual

Precautions for installation
Wrong wiring will lead to breakdown or electrical shock of the instrument, please read this
operation manual clearly before installation.
zMake sure to remove AC power from the controller before wiring input, output connections,
and remove it before opening the controller housing.
zThe installation site of the controller should be good in ventilation and avoid direct sunshine.
zThe material of signal cable should be special coaxial cable. Strongly recommend using our
coaxial cable. Do not use normal wires instead.
zAvoid electrical surge when using power. Especially when using three-phase power, use
ground wire correctly.
zThe internal relay contact of the instruments is for alarm or control function. Due to safety,
please must connect to external relay which can stand enough ampere to make sure the safety
operation of the instruments.˄Please refer to chapter 3.6ʳ“Illustration of electrical
connectionϙ˅
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!

Precautions for installation
Brief Instruction
1
1. Specifications 4
2. Assembly and installation
2.1 Transmitter installation 5
2.2 Illustration of panel mounting 5
2.3 Illustration of Wall mounting and pipe mounting 6
3. Overview of conductivity / resistivity transmitter EC-4110
3.1 Illustration of rear panel 7
3.2 Illustration of terminal function ˊ
3.3 Description of terminal function ˋ
3.4 Wiring of cable ˌ
3.5 Circuit of cable ˌ
3.6 Illustration of electrical connection 10
4. Configuration
4.1 Illustration of front panel 11
4.2 Keypad 11
4.3 LED indicators 11
4.4 Display 12
5. Operation
5.1 Measurement mode 13
5.2 Set-up menu 13
5.3 Calibration menu 13
5.4 Shortcuts 13
5.5 Reset 13
5.5.1 Set-up reset 13
5.5.2 Calibration reset 13
6. Settings
Block diagram of settings 14
6.1 Entry of set-up menu 16
6.2 Security code of settings(Code) 17
6.3 Measurement parameters(Mode) 18
6.4 Temperature 19
6.5 Compensation 20
6.6 Relay 1 21
6.7 Relay 2 22
CONTENTS

6.8 Wash time(Clean) 23
6.9 Analog output 1 (Cond/Res) 24
6.10 Analog output 2 (˧emperature) 25
6.11 Date/Time (Clock) 26
6.12 Sample average of measurements (Digital filter) 27
6.13 Backlight settings 28
6.14 Contrast settings 29
6.15 Power frequency (Freq.) 30
6.16 Automatically back to measurement mode(Return) 31
7. Calibration
Block diagram of Calibration 32
7.1 Entry of calibration menu 33
7.2 Automatically back to measurement mode(Return) 34
7.3 Security password of calibration 35
7.4 Cell constant calibration (CELL Const.) 36
7.4.1 Resistivity (Res) 36
7.4.2 Conductivity (Cond) 37
7.5 Standard solution calibration (Std. Sol.) 38
8. Error messages (Error code) 39
9. Installation of cells
9.1 Appearance of cells 40
9.2 Correct installation 40
9.3 Incorrect installation 41

Brief Instruction
Description of set-up settings (see chapter 6 for details) ʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳ
Press and simultaneously to see the overview of the set-up settings now. Then press I
if you would like to modify set-up settings. Press keypad according to index of keypad on the screen.
Index of keypad
keypad Accordingly item Description
Back to upper layer
Choose leftward of change to left page
Increase digit
Choose rightward of change to right page
Decrease digit
Confirm settings after modifications and then go through next
step
Selection of set-up items
keypad Accordingly item Description
Mode Measurement mode, to choose Resistivity (Res) or Conductivity
(Cond) measurement
Temperature Temperature measurement and compensation, including MTC,
PTC, NTC (3 types total). MTC---Manual temperature
compensation, PTC/NTC--- auto temperature compensation
Relay 1 First relay setting, to choose action off or Hi/Lo alarm
Relay 2 Second relay setting, to choose action off or Hi/Lo alarm
Clean Automatic wash time setting, to choose electrode clean
equipment’s ON and OFF duration
Analog 1 Current output according to Res or Cond setting range
Analog 2 Current output according to temperature setting range
к

Clock Clock setting (When out of power and reboot it, the
instrument’s time setting will return to the factory
pre-setting)
Black-light Backlight setting, to set Auto/ON/OFF backlight, brightness,
and sensitivity
Contrast Contrast of screen setting
Digital Filter Take every serial 1~60 measurements, average them
continuously, and make it as the readings
Return Setting of returning to the measurement mode
Code Security code of set-up mode. The factory default is 1111, and a
designated user can change the code. The set-up code is
precedential to calibration code, thus it can pass a different
security code of calibration.
л

Description of calibration settings (see chapter 7 for details)ʳ ʳʳʳʳʳʳʳʳʳʳʳʳʳ
Press and simultaneously to see the last calibration information. Then press if you
would like to make a new calibration or modify setting of calibration. Press keypad according to
index of keypad on the screen.
Index of keypad:
keypad Accordingly item Description
Back to upper layer
Choose leftward of change to left page
Increase digit
Choose rightward of change to right page
Decrease digit
Confirm settings after modifications and then go through next
step
Selection of calibration items (up to three-point calibration)
keypad Accordingly item Description
Code Security code of calibration mode. The factory default is 1100.
Return Time interval setting of returning to the measurement mode
Cell Constant To adjust the instrument cell constant setting until the value the
same with the given cell constant of the sensor
Solution Use the appropriate standard solution to calibrate the system
Note ʳ
SUNTEX reserves the right to change the figure of icons and contents. The actual icons and contents
please refer to the instruments.
м

1. Specifications
Model
!
EC-4110
Measuring modes
!
Resistivity/Conductivity/Temp.
Resistivity 0.00 M·cm~20.00 M·cm
Conductivity 0.00 S/cm~200.0 mS/cm manual or auto range selectable
Ranges
!
Temp.
!
-30.0~130.0˚C
Resistivity 0.01 M·cm
Conductivity 0.01 S/cm
Resolutions
!
Temp.
!
0.1˚C
Resistivity ±1% ±1Digit
Conductivity ±1% ±1Digit
Accuracy
!
Temp.
!
±0.2˚C±1Digit
Temperature
Compensation
!
NTC30K or PT1000 or
Manual temperature compensation selectable
Calibration mode
!
(1)Cell constant adjustment (2)Standard solution calibration
Ambient Temp.
!
0~50 ˚C
Storage Temp.
!
-10~70 ˚C
Cell Constant
!
0.01, 0.05, 0.1, 0.5, 10.00 cm-1 fixed,
freely selectable 0.008~19.99 cm-1
Temperature Coefficient
!
Linear temperature compensation from (0.00%~ 40.00%)
and Non-Linear compensation
Display
!
Large LCD display with environment light sensor
auto/manual illumination function
Analog output 1
!
Isolated DC 0/4~20mA corresponding to main measurement,
max. load 500:
Analog output 2
!
Isolated DC 0/4~20mA corresponding to Temp., max. load 500:
Contact
!
RELAY contactΔ240VAC 0.5A Max.(recommend)
Settings
!
Activate
!
Two sets of individual HIGH or LOW programmable control
Wash RELAY contact: ON 0~99min. 59sec. / OFF 0~999hr 59min.
Certification IP65 (NEMA 4)
Power Supply 100V~240VAC±10%Δ50/60HzΔ5W max.
Installation Wall or Pipe or Panel Mounting
Dimensions 96m × 96mm × 132mm (HuWuD)
Cut off Dimensions 93 mm u93 mm (HuW)
Weight 0.5Kg
Note: The specifications are subject to change without notice.
н

2. Assembly and installation
2.1 Transmitter installation: This Transmitter can be installed through panel mounting, wall
mounting and pipe mounting.
Installation of panel mounting: Firstʿprepare a square hole of 93 x 93mm on the panel box,
and then insert the controller directly into the panel box. Insert the accessorial mounting bracket
from the rear, and make it be fixed in to pickup groove.
2.2 Illustration of panel mounting:
93 mm
93 m
m
Hole size
87 mm
Ѐ
87 mm
Hole distances on the
p
anel box
Mounting bracket
Illustration of panel mounting,
fixed with mounting bracketʳ
Ѐ
ЀЀ
112 m
m
о

2.3 Illustration of Wall mounting and pipe mounting
Installation of pipe mounting
Fixed with U-shaped pipe clip. The
distance between screw holes is 60mm
Installation of wall mounting
Fixed with 4 x M4 screws
Sun Shield (Pipe mounting)
(Optional)
Sun Shield (Wall mounting)
(Optional)
п

RS485
3. Overview of Conductivity transmitter EC-4110
3.1 Illustration of rear panel:
3.2 Illustration of terminal function:
ʳ
D+(B)
G
D-
(
A
)
+
-
4/20m
A
POWER
AC
INPUT
POWER
+
-
12V
HI LO WA S H
+
-
4/20m
A
2
3!
EC-4110RS
onl
y
˦˛˜˘˟˗
ʳ
˼˄ʳ
ʳ
˄ʳ
ʳ
˅ʳ
ʳ
˼˅ʳ
ʳ
˦˚ʳ
ʳ
t
SHIELD
CELL1
CELL2
CELL3
CELL4
SG
T/P
р

3.3 Description of terminal function:
ѽѾ
ѽѿ
ѽҀ
ѽҁ
ѽ҂
ѽ҃
ѽ҄
҄
ʳNC
Κ
None contact
ѽ҅
100~240AC
Κ
Power supply terminal
ѽ҆ ʳ
NC
Κ
None contact
Ѿѽ
ʳ100~240AC
Κ
Power supply terminal
ѾѾ ʳ
Ѿѿ
ʳ
ѾҀ
CELL1
Κ
The cell connection line: Current electrode 1
Ѿҁ
CELL2
Κ
The cell connection line: Voltage electrode 1
Ѿ҂
CELL3
Κ
The cell connection line: Voltage electrode 2
Ѿ҃
CELL4
Κ
The cell connection line: Current electrode 2
Ѿ҄
SG
Κ
NC
Ѿ҅
TP
Κ
Connect the cell connection line of temperature probe
Ѿ҆
SG
Κ
NC
ѿѽ ʳ
4~20mAЀterminal
Κ
Master measure current output terminal +, for external
recorder or PLC control
ѿѾʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ
4~20mAЁterminal
Κ
Master measure current output terminal -, for external
recorder or PLC control
ѿѿʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ
4~20mAЀterminal / D+(B)
Κ
Temperature current output terminal +, for
external recorder or PLC control
ѿҀʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ
4~20mAЁterminal / G
Κ
Temperature current output terminal -, for external
recorder or PLC control
ѿҁʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ
NC / D-
ΰ
A
αΚ
NC
WASH
Κ
External wash relay terminal
REL2ΚExternal relay terminal second control
REL1ΚExternal relay terminal first control
SHIELD
Κ
The transparent cell connection line
с

3.4 Wiring of cable
3.5 Circuit of cable
SUNTEX Conductivity Cell Others
Terminal
sign
2 Electrode Cell
8-221/8-222/8-223
4-Electrode Cell
8-241/8-241-01/8-242
Fixed Cable
Resistivity Cell
8-11-3
8-11-4
Fixed Cable
Conductivity
Cell 8-12-6
8-12-7
Please read the
instruction of the cells
SHIELD Transparent line Net line Net line SHIELD
CELL 1 Brown line Current electrode 1
CELL 2 Red line
Short with
transparent line
Short with
transparent line Voltage electrode 1
CELL 3 Orange line Voltage electrode 2
CELL 4 Black line
Short with white
line
Short with
green line Current electrode 2
T/P Yellow line Yellow line Red line T/P(the other side for
CELL 4
Note: If use other brand’s two electrode cell, the circuit of cable is the same with that for
8-11-3or8-12-6cell.
SHIELD!
)
trans
p
arent
*
!
CEL
L
1!
)
b
rown
*
!
T/P!)yellow*!
CEL
L
4!
)
b
lac
k
*
!
CEL
L
2!
)
re
d
*
!
CEL
L
3!
)
oran
g
e
*
!
т

3.6 Illustration of electrical connection:
Surge absorber
Surge absorber
Surge absorber
Surge absorber
Transmitter
Washing device
Dose feeder
Dose feeder
100 ~ 240VAC
Surge absorber
Surge absorber
External relay
External relay
External relay
кй

4. Configuration:
ʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳ
4.1 Illustration of front panel:
4.2 Keypad:
In order to prevent inappropriate operation by others, before the parameter setting and
calibration, the operation applies multi-keysʿʳand coding protection if necessary. Description of
the key functions is in the following:
ΚIn the parameter set-up mode, pressing this key allows you exit parameter set-up mode
and back to Measurement mode.
ˍIn the Calibration mode, pressing this key allows you exit Calibration mode and back to
Measurement mode.
Κ1. In the parameter set-up mode and Calibration mode, pressing this key to select
leftward or change to another page.
2. When adjusting value, press this key to increase the value.
Κ1. In the parameter set-up mode and Calibration mode, pressing this key to select
rightward or change to another page.
2. When adjusting value, press this key to decrease the value.
ΚKey for confirmation; pressing this key is essential when modifying data value or
selecting the parameter setting items in the window.
4.3 LED indicators:
ACT
Κ
Washing device operation indicator ˴˷ʳ˶ontrolling operation indicator (Relay 1ΕRelay 2)
B.L. : Light sensor; in the automatic display backlit mode, the lamp will light or go out as the
change of environmental brightness.
кк

4.4 Display:
Note: 1. When the wash device is turned on, the display shows and twinkles the description, “Clean
Running”. At the same time, the ACT indicator LED lights up, and the transmitter
automatically turns off Relay 1 and Relay 2 function. After finishing cleaning, the Relay 1
and Relay 2 will automatically back to normal status.
2. When Relay 1 which is set in high setting point is in action, the display shows and twinkles
the description, “REL 1_Hi”, and ACT indicator LED lights up. When Relay 1 which is set
in low setting point is in action, the display shows and twinkles the description, “REL 1_Lo”,
and ACT indicator LED lights up.
3.When Relay 2 which is set in high setting point is in action, the display shows and twinkles
the description, “REL 2_Hi”, and ACT indicator LED lights up. When Relay 2 which is set
in low setting point is in action, the display shows and twinkles the description, “REL 2_Lo”,
and ACT indicator LED lights up.
4. When under measurement mode, if the temperature compensation mode is set in MTC
(Manual adjustment), press or to adjust the MTC temperature manual.
Analog 2 output
current over range
alarm
Control function
on hold
:Measurement mode
:Set-up mode
:Calibration mode
RELʳ1ʳhighʳʳ
˿ point alarm
Wash device in
action condition
Meaurementʳ˼
Clock
RELʳ˅ʳhighʳʳ
˿ point alarm
Analog 1 output
current over range
alarm
Temperature
compensation mode
(MTC/ATC)
Temperature valueʳ
˴˷ʳ˼
Compensation unit
кл

5.Operation
5.1 Measurement mode:
ʳʳʳAfter all electrical connections are finished and tested, connect the instrument to the power
supply and turn it on. The transmitter will automatically entering measurement mode with the
factory default settings or the last settings from user.
5.2 Set-up menu:
ʳʳʳPlease refer to the set-up instructions in Chapter 6. Press and simultaneously to
enter into set-up menu, and press toʳgo press to back to measurementʳmode.
5.3 Calibration menu:
ʳʳʳPlease refer to the calibration instructions in Chapter 7. Press and
simultaneously to enter into calibration menu, and press to go back to measurementʳmode.
5.4 Shortcuts: In the measurement mode, if selecting MTC for temperature compensation mode, you
may press and to adjust MTC temperature value.
ʳ
5.5 Reset:
5.5.1 Master reset:ʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳ
Measurement mode: Conductivity, Auto-Range
Temperature compensation: MTC 25ć
Temperature Coefficient: Lin, 2.00%
Relay 1ΚHigh point alarm: AUTOʿʳSP1= 100.0mSΔDB=10.0mS
Relay 2ΚLow point alarm: AUTOʿʳSP2 =10.0 mSΔDB= 1.00 mS
Wash time: OFF
Analog 1 current output (Cond/Res)Κ420 mAΔ0.00199.9mS
Analog 2 current output (Temp)Κ(Temp)Κ420 mAΔ0100.0C
Display backlit:ʳOFF
Contrast: 0
Code: OFF
Date & TimeΚ2010/1/1 00:00:00
Auto back: Auto, 3 minutes
5.5.2 Calibration reset:
ʳʳʳ ʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳʳ
CalTimeΚ2010/01/01
CalTypeΚNo Cal
CellConstantΚ0.5000
CalTemp.Κnone
Auto back: Auto, 3 minutes
Note: The factory default of calibration presetting is “No Cal”, and the cell constant setting is “0.5000”.
It means that the user has not calibrated the sensor with the transmitter yet. When selecting
standard solution to finish calibration, the display shows cell constant of the cell and the value of
the standard solution.
км

6. Settings
ʳ ʳ ʳʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ ʳ
Block diagram of settings 1:
˦˸˼˺
ˢ˸˼˸
ˠ˷˸
˸˼˺
ʳ˖˷˸
˸˼˺
˧˸˸˴˸
˸˼˺
˥˸˿˴˄
˸˼˺
˥˸˿˴˅
˸˼˺
˖˿˸˴
˸˼˺
˶˷˸
ʳ˼
ˢ˙˙ ˢˡ
˸ʳ
˶˷˸
˸˼˺
˥˸˂˖˷
˷˸ʳ˸˿˸˶ʳ
˖˸˴˼
˷˸
ˠ˧˖ ˣ˧˖
˥˸˿˴˄
˦ˣʳ˼
˥˸˿˴˄ʳ
˗˕ʳ˼
˥˸˿˴˄
ˢˡ˂ˢ˹˹
˸˿˸˶
˥˸˿˴˄
˸
˥˸˿˴˅
ʳ˗˕ʳ˼
˥˸˿˴˅
ˢˡ˂ˢ˙˙
˸˿˸˶
˥˸˿˴˅
˸
˥˸˿˴˅ʳ
˦ˣʳ˼
˖˿˸˴
ˢ˙˙ʳ˼˸ʳ
˼
˖˿˸˴
˗˕ʳ˼
˖˿˸˴
˸
˖˿˸˴
ˢˡʳ˼˸ʳʳ
˼
Κ
Κ
Κ
ˡ˧˖
˴˿˸ʳ
˼
˴˿˸ʳ
˶˸˶
˴˿˸ʳ
˶˸˶
˥˸˿˴˄
˛˼˂˟
˸˿˸˶
˥˸˿˴˅
˛˼˂˟
˸˿˸˶
˦˸˼˺ʳˠ˷˸
˕˴˶˾ʳʳ˻˸ʳ˸˼ʳ
˶˿˴ʳ˂ʳ˴˶˼ˍ
˖˷˂˥˸
˸˼˺
˥˸
˸˼˺
˖˼˸˷ʳʳ˸ʳ˴˺˸˶˼˸˷ʳʳ˸ʳ˴˺˸
˥˴˺˸ʳ
˸˿˸˶
˧ˁ˖ˁ
˸˼˺
˧ˁ˖ˁ
˴˿˸ʳ
˼
˟˼ ˡˀ˟˼ʳ
˥˸ ˖˷
˖˿˸˴
ˢˡ˂ˢ˙˙
˸˿˸˶
Continued on next page Continued on next page
кн

Block diagram of settings 2:
Cond/Res
current
output 1
Temp
current
output 2
Clock
setting
Filter
setting
Relative
value to 0 or
4mA
Relative
value to
20mA
Relative
value to
0 or 4mA
Relative
value to
20mA
0/20 or
4/20mA
mode select
Year
input
Date
input
Time
input
Signal
average
0/20 or
4/20mA
mode select
Backlight
setting
Mode
select
Return
setting
Time
input
Method
select
Auto Manual
Auto ON OFF
Bright-
ness
setting
Sensit-
ivity
setting
Bright-
ness
setting
Clean
Setting
Contrast
setting
Contrast
input
connected previous page
Code
setting
connected previous page
Κ
Κ
Κ
Back to the previous
class / action:
Freq
setting
Freq.
select
Connected with previous page Connected with previous page
ко

6.1 Entry of set-up menu
In the measurement mode, pressing the two keys and simultaneously allows
you enter the overview of current setting, and press to enter the set-up mode to
modify the setting if necessary.
Enter set-up menu
“Measurement (Mode)”
Pressʳʳor
Pressʳʳ
Pressʳʳor
Pressʳʳto confirm it
кп
This manual suits for next models
1
Table of contents
Other Suntex Transmitter manuals

Suntex
Suntex CT-6300RS User manual

Suntex
Suntex PC-3310 Installation manual

Suntex
Suntex TC-7310-RS User manual

Suntex
Suntex CT-6300 User manual

Suntex
Suntex EC-4110-I User manual

Suntex
Suntex TC-7100 User manual

Suntex
Suntex CT-6110-POL User manual

Suntex
Suntex PC-3110-P User manual

Suntex
Suntex PC-300A Series User manual

Suntex
Suntex IT-8100 User manual