Suntex PC-3110-P User manual

1
PC-3110-P
Intelligent
pH/ORP
Transmitter
Operation
Manual

Precautions for installation
Brief Instruction 1
1. Specifications 4
2. Assembly and installation
2.1 Transmitter installation 5
2.2 Illustration of panel mounting 5
2.3 Illustration of Wall mounting and pipe mounting 6
2.4 Assembly of electrode and housing 6
2.4.1 Cable set-up 6
2.4.2 Assembly of housing PP-100A 7
2.5 Illustration and description of junction box 8
3. Overview of Intelligent pH/ORP transmitter PC-3110-P
3.1 Illustration of rear panel 10
3.2 Illustration of terminal function 10
3.3 Description of terminal function 11
3.4 Installation of transmitter PH-300T 12
3.5 Connection of transmitter and accessional transmitter PH-300T 12
3.6 Typical wirings 13
3.7 Illustration of electrical connection 14
4. Configuration
4.1 Illustration of front panel 15
4.2 Keypad 15
4.3 LED indicators 15
4.4 Display 16
5. Operation
5.1 Measurement mode 17
5.2 Set-up menu 17
5.3 Calibration menu 17
5.4 Shortcuts 17
5.5 Factory default value 17
5.5.1 System setting default value 17
5.5.2 Calibration default value 17
6. Settings
Block diagram of settings 18
6.1 Entry of set-up menu 20
6.2 Security code of settings(Code) 21
CONTENTS

6.3 Language 22
6.4 Measurement parameters(Mode) 23
6.5 Multi-point calibration(Multi-Cal) 24
6.6 Temperature 25
6.7 PID control 26
6.8 Relay 1 27
6.9 Relay 2 28
6.10 Wash time(Clean) 29
6.11 Analog output 1 (pH/ORP) 30
6.12 Analog output 2 (temperature/PID) 31
6.13 Date/Time (Clock) 32
6.14 Sample average of measurements (Digital filter) 33
6.15 Backlight settings 34
6.16 Contrast settings 35
6.17 Automatically back to measurement mode(Return) 36
7. Calibration
Block diagram of Calibration 37
7.1 Entry of calibration menu 38
7.2 Security password of calibration 39
7.3 Automatically back to measurement mode(Return) 40
7.4 pH calibration 41
7.4.1 TECH mode (Up to 3-point calibration) 41
7.4.2 NIST mode (Up to 3-point calibration) 41
7.4.3 Asymmetry mode (Up to 3-point calibration) 41
7.4.4 Definition of calibration parameter 42
7.4.5 TECH, NIST buffer Calibration 43
7.4.6 Any Calibration 44
7.5 ORP calibration 45
8. PID control
8.1 The fundamental principle 46
8.2 PID control actions and parameters 46
8.3 PID control signal 49
9. Error messages (Error code) 51
10. Maintenance 52
Appendix 53

Precautionsforinstallation
Wrong wiring will lead to breakdown or electrical shock of the instrument, please read this
operation manual clearly before installation.
zMake sure to remove AC power from the controller before wiring input, output connections,
and remove it before opening the controller housing.
zThe installation site of the controller should be good in ventilation and avoid direct sunshine.
zThe material of signal cable should be special coaxial cable. Strongly recommend using our
coaxial cable. Do not use normal wires instead.
zAvoid electrical surge when using power. Especially when using three-phase power, use
ground wire correctly.
zThe internal relay contact of the instruments is for alarm or control function. Due to safety,
please must connect to external relay which can stand enough ampere to make sure the safety
operation of the instruments.(Please refer to chapter 3.7“Illustration of electrical
connection")
1

Brief Instruction
Description of set-up settings (see chapter 7 for details)
Press and simultaneously to see the overview of the set-up settings now. Then press I
if you would like to modify set-up settings. Press keypad according to index of keypad on the screen.
Index of keypad
keypad Accordingly item Description
Back to upper layer
Choose leftward of change to left page
Increase digit
Choose rightward of change to right page
Decrease digit
Confirm settings after modifications and then go through next
step
Selection of set-up items
keypad Accordingly item Description
Mode Measurement mode, to choose pH or ORP measurement
Multi-Cal. Multi-point calibration, to choose 1, 2, or 3 points calibration
PID
PID setting, available for Pulse Length, Pulse Frequency,
Analogout, totally three output mode
Temperature
Temperature measurement and compensation, including MTC,
PTC, NTC (3 types total). MTC---Manual temperature
compensation, PTC/NTC--- auto temperature compensation
Relay 1 First relay setting, to choose action off or Hi/Lo alarm
Relay 2 Second relay setting, to choose action off or Hi/Lo alarm
Clean Automatic wash time setting, to choose electrode clean
equipment’s ON and OFF duration
2

Analog 1 Current output according to pH or ORP setting range
Analog 2 Current output according to temperature/PID setting range
Clock Clock setting (When out of power and reboot it, the
instrument’s time setting will return to the factory default
setting)
Black-light Backlight setting, to set Auto/ON/OFF backlight, brightness,
and sensitivity
Contrast Contrast of screen setting
Digital Filter Take every serial 1~60 measurements, average them
continuously, and make it as the readings
Return Setting of returning to the measurement mode
Code
Security code of set-up mode. The factory default is 1111, and a
designated user can change the code. The set-up code is
precedential to calibration code, thus it can pass a different
security code of calibration.
Language
Available for English, Traditional Chinese, Simplified Chinese
3

Description of calibration settings (see chapter 8 for details)
Press and simultaneously to see the last calibration information. Then press if you
would like to make a new calibration or modify setting of calibration. Press keypad according to
index of keypad on the screen.
Index of keypad:
keypad Accordingly item Description
Back to upper layer
Choose leftward of change to left page
Increase digit
Choose rightward of change to right page
Decrease digit
Confirm settings after modifications and then go through
next step
Selection of calibration items (up to three-point calibration)
keypad Accordingly item Description
Code Security code of calibration mode. The factory default is
1100.
Return Time interval setting of returning to the measurement
mode
TECH Use tech buffer as standard solution for calibration
NIST Use NIST standard buffers(DIN 19266) as standard
solution for calibration
Any Use any buffer solution by users’definition for
calibration
Note
Due to the need for continuous improvement of the transmitter function, we reserve the right to modify the
content and the icon of the function. The actual icons and contents are subject to the instrument without notice.
4

1.Specifications
Model PC-3110-P
Measuring modes pH / ORP / Temp.
Ranges
pH -2.00~16.00 pH
ORP -1999~1999 mV
Temp. -30.0~130.0 C
Resolutions
pH 0.01 pH
ORP 1 mV
Temp. 0.1 C
Accuracy
pH ±0.01 pH ±1 Digit
ORP ±0.1% ±1 Digit
Temp. ±0.2C±1 Digit
Temperature
Compensation
NTC30K/ PT 1000 auto temperature compensation
Manual adjustment temperature compensation
Calibration mode Tech., NIST., Any mode, up to three point calibration
Ambient Temp. 0~50C
Storage Temp. -20~70C
Input Impedance > 1012 Ω
Display Large LCM display with environment light sensor
auto/manual illumination function
Analog output 1 Isolated DC 0/4~20mA corresponding to main measurement,
max. load 500
Analog output 2 Isolated DC 0/4~20mA corresponding to Temp., max. load 500
Settings
Contact RELAY contact,240VAC 0.5A Max.(recommend)
Activate Two sets of individual HIGH or LOW programmable control or
PID Pulse Length, Pulse Frequency, control contact
PID control mode Pulse Length, Pulse Frequency, Analogout(current)
Wash RELAY contact: ON 0~99min. 59sec. / OFF 0~999hr 59min.
Voltage Output DC±12V,1W max.
Certification IP65
Power Supply 100V~240VAC±10%,4W max.,50/60Hz
Installation Wall or Pipe or Panel Mounting
Dimensions 96m × 96mm × 132mm (HWD)
Cut off Dimensions 93 mm 93 mm (HW)
Weight 0.5Kg
Note: The specifications are subject to change without notice.
5

2.Assemblyandinstallation
2.1 Transmitter installation: This Transmitter can be installed through panel mounting, wall
mounting and pipe mounting.
Installation of panel mounting: First,prepare a square hole of 93 x 93mm on the panel box,
and then insert the controller directly into the panel box. Insert the accessorial mounting bracket
from the rear, and make it be fixed in to pickup groove.
2.2 Illustration of panel mounting:
93 mm
93 m
m
Hole size
87 mm
+
87 mm
Hole distances on the
p
anel box
Mounting bracket
Illustration of panel mounting,
fixed with mounting bracket
+
++
112 m
m
6

2.3 Illustration of Wall mounting and pipe mounting
2.4 Assembly of electrode and housing
2.4.1 Cable set-up:
a. Make sure to remove the conductive rubber or aluminum-foil paper between the electrode signal
wire and the coaxial shield.
b. Extend the cable to the controller without any joint except specific junction box. Connect the
coaxial inner directly to the Glass contact on the back of controller and connect coaxial shield to
Ref.contact.
Installation of pipe mounting
Fixed with U-shaped pipe clip. The
d
ista
n
ce
b
etween sc
r
ew holes is 60
m
m
Installation of wall mounting
Fixed with 4 x M4 screws
Sun Shield (Pipe mounting)
Order No.: 8-35 and 8-35-1 Sun Shield (Wall mounting)
Order No.: 8-35 and 8-35-2
Coaxial shield
Remove the conductive rubber
Set-up diagram of coaxial cable:
See the correct set-up method on the left:
Note: The black conductive rubber
covering on the coaxial inner should be
removed for use.
7

2.4.2 Assembly of housing PP-100A
1. Insert (H) Electrode through (G) PP Electrode Protective Housing
2. Rinse (H) Electrode properly, so that it can be easily pass through (I) Rubber electrode
holder,leave about 5cm bellow.
3. Install the prepared (I) Rubber electrode holder into (G) PP Electrode Protective Housing
and lock (J) PP pipe protective cover tightly.
4. Insert (H) Electrode cable through (D) Lower cover of round junction box and (C) Cable
fixing point, and use (D) Lower cover of round junction box to lock (G) PP Electrode
Protective Housing tightly.
5. Prepare 15cm cable in the PP pipe, and then lock (C) Cable fixing point MG16A tightly.
Leave (H) Sensing electrode cable for about 12-14cm, and split it carefully.
6. Fix the terminal of electrode coaxial inner on terminal block 1 of round holder; Fix the
terminal of electrode coaxial shield on terminal block 3. (See the instruction of junction
box)
7. Extend the cable to pass through (E) Cable fixing point on (D) Lower cover of round
junction box, and lock (E) Cable fixing point MG16A tightly, leaving 12-14cm in the box
for split.
8. Extend the lead coaxial inner and electrode coaxial inner to connect them; extend the lead
coaxial shield to fix on the terminal block 3. Lock (A) Upper cover of round junction box
to finish the installation.
Mounting bracket:
A------ Upper cover of round joint box
B------ O-ring
C------ Cable fixing point MG16A
D------ Lower cover of round joint box
E------ Cable fixing point MG16A
F------ O-ring
G------ PP Electrode Protective Housing
H------ Electrode (Sensor)
I------- Rubber electrode holder
J------- PP pipe protective cover
8

Our company use L-shaped mounting bracket as electrode mounting bracket. According to the
site necessity, fix the bracket with steel nails or expansion bolts at proper locations by pool.
2.5 Illustration and description of junction box :( Two kinds of link distributing system)
[1]Two-wire distributing system
INPUT terminals Terminal
No.
OUTPUT terminals Terminals on
controller
Coaxial inner 1 Coaxial inner’s extending
wire for electrode
GLASS
Shield (forbidden) 2 Shield (forbidden) ------
Coaxial shield 3 Coaxial shield’s extending
wire for electrode
REF
Temperature probes
red wire
4 Red wire’s extending wire
for electrode
T/P
Temperature probes
green wire
5 Green wire’s extending wire
for electrode
GND
Alternative 6、7 Alternative ------
Note: 1. Our company’s extending wire for electrode material No. is 7202-F94009-BK
and 7202-RG-58
9

1.) If temperature probe is not used, the Order No. is 7202-RG-58.
2.) If temperature probe is used, the Order No. is 7202-F94009-BK.
2. If temperatures probe 8-26-3(NTC30K) or 8-26-8(PT1000) is used for two-wire
distribution, the black wire terminal should be forbidden.
〔2〕Three-wire distributing system
IN terminals Terminal
No.
OUT terminals Terminals on controller
Coaxial inner 1 Coaxial inner’s extending wire
for electrode
GLASS
Ground Rods 2 GND GND
Coaxial Shield 3 Coaxial Shield’s extending
wire for electrode
REF
Temperature probes red
wire
4 Red wire’s extending wire for
electrode
T/P
Temperature probes
green wire
5 Green wire’s extending wire
for electrode
GND
Alternative 6、7 Alternative ----
Note: 1. The black wire on the temperature probes of 8-26-3(NTC30K) or 8-26-8(PT1000) is
used as special wire for Ground Rods to be connected at terminal 2.
2. The extending wire for electrode that has a temperature probe or ground rod is
marked with material number 7202-F94009-BK.
10

3. Overview of pH transmitter PC-3110-P
3.1 Illustration of rear panel:
3.2 Illustration of terminal function:
+
-
4/20m
A
GLASS
REF
SG
TP
PH/
ORP
T
POWER
AC
INPUT
POWER
SG
+
-
±12V
HI LO WASH
+
-
4/20m
A
1
2
11

3.3 Description of terminal function:
01
02
03
04
05
06
07 NC: None contact
08 100~240AC: Power supply terminal
09 NC: None contact
10 100~240AC: Power supply terminal
11
12
13 NC: None contact
14 REF: Coaxial shield connecting pH/ORP electrode signal wire
15 SG: The terminal connecting temperature probe, or used as ±12V ground
potential. In two-wire distributing system, there should be a short
circuit between this terminal and REF (a short circuit slice is
attached when going out the factory)
16 T/P: Connect the other end of temperature probe
17 SG: The other terminal connecting temperature probe, or used as ±12V
ground potential.
18
19
20 4~20mA +terminal: Master measure current output terminal +, for external
recorder or PLC control
21 4~20mA – terminal: Master measure current output terminal -, for external
recorder or PLC control
22 4~20mA +terminal: Temperature current output terminal -, for external
recorder or PLC control, or PID Direct/Reverse control
23 4~20mA – terminal: Temperature current output terminal -, for external
recorder or PLC control, or PID Direct/Reverse control
24 NC / D-(A): None contact
WASH: External wash relay terminal
REL2: Second external relay terminal control;
o
r
PID Reverse control
REL1: First external relay terminal control;
o
r
PID Direct control
GLASS: Coaxial inner connecting pH/ORP
electrodesignalwire
DC±12V: Output terminal of direct current voltage ±12V (PH-300T only)
12

3.4 Installation of transmitter PH-300T: (alternative equipment)
PH-300T transmitter is mainly installed on the electrode protective pipe, but also can apply
wall mounting and pipe mounting. For long distance transmission (100m), if PC-3110 is more
than 30m far away from the electrode, PH-300T transmitter is recommended to avoid the
attenuation of electrode signal, and for the convenience of onsite observation, measurement,
and calibration.
3.5 Connection of transmitter PC-3110 and transmitter PH-300T:
A. Connect the GLASS point of transmitter PH-300T’s terminal to the electrode coaxial inner.
(Note: Remove the black conductive rubber); connect the REF point of transmitter
PH-300T’s terminal to the electrode coaxial shield.
B. See the two-wire distributing system and three-wire distributing system in the following
page.
C. Sign “PT-1000” on transmitter PH-300T’s terminal is the connector for automatic
temperature compensation probe, PT-1000, or applies a fixed temperature compensation
resistance.
D. The V+ and V- of transmitter PH-300T’s terminal respectively connect to DC12V+ and –
of the controller.
E. The S+ and S- on transmitter PH-300T’s terminal respectively connect to GLASS and REF
of the controller.
F. The I+ and I- on transmitter PH-300T’s terminal are output (4-20mA), which can connect
to devices that receive current signals. (Note: The current output signal of this
transmitter is not insulating, so use it with much care!)
Note: Refer to the following table for proper fixed temperature compensation resistance
Temperature 0℃ 5℃ 10℃ 15℃ 20℃
R value 1000Ω1019.25Ω1038.5Ω1057.75Ω1077Ω
Temperature 25℃ 30℃ 35℃ 40℃ 45℃
R value 1096.25Ω1115.5Ω1134.75Ω1154Ω1173.25Ω
Temperature 50℃ 55℃ 60℃ 65℃ 70℃
R value 1192.5Ω1211.75Ω1231Ω1250.25Ω1269.5Ω
Temperature 75℃ 80℃ 85℃ 90℃ 100℃
R value 1288.75Ω1308Ω1327.25Ω1346.5Ω1385Ω
13

3.6 Typical wirings:
Three-wire distribution
GND REF
.
GLAS
pH/
ORP
Coaxial
inner
Coaxial
shield
Blac
k
Two-wire distribution
GND REF. GLAS
pH/
ORP
Coaxial
inner
Coaxial shiel
d
Short circuit slice
14

3.7 Illustration of electrical connection:
Surge absorber
Surge absorber
Surge absorber
Surge absorber
Transmitter
Washing device
Dose feeder
Dose feeder
100 ~ 240VAC
Surge absorber
Surge absorber
External relay
External relay
External relay
15

4. Configuration:
4.1 Illustration of front panel:
4.2 Keypad:
In order to prevent inappropriate operation by others, before the parameter setting and
calibration, the operation applies multi-keys, and coding protection if necessary. Description of
the key functions is in the following:
:In the parameter set-up mode, pressing this key allows you exit parameter set-up mode
and back to Measurement mode.
:In the Calibration mode, pressing this key allows you exit Calibration mode and back to
Measurement mode.
:1. In the parameter set-up mode and Calibration mode, pressing this key to select
leftward or change to another page.
2. When adjusting value, press this key to increase the value.
:1. In the parameter set-up mode and Calibration mode, pressing this key to select
rightward or change to another page.
2. When adjusting value, press this key to decrease the value.
:Key for confirmation; pressing this key is essential when modifying data value or
selecting the parameter setting items in the window.
4.3 LED indicators:
ACT: Washing device operation indicator and controlling operation indicator (Relay 1, Relay 2)
B.L. : Light sensor; in the automatic display backlit mode, the lamp will light or go out as the
change of environmental brightness.
16

4.4 Display:
Note: 1. When the wash device is turned on, the display shows and twinkles the description, “Clean
Running”. At the same time, the ACT indicator LED lights up, and the transmitter
automatically turns off Relay 1 and Relay 2 function. After finishing cleaning, the Relay 1
and Relay 2 will automatically back to normal status.
2. When Relay 1/ Relay 2 which is set in high setting point is in action, the display shows and
twinkles the description, “REL 1_Hi/ Relay 2_Hi”, and ACT indicator LED lights up. When
Relay 1/ Relay 2 which is set in low setting point is in action, the display shows and twinkles
the description, “REL 1_Lo/ Relay 2_Lo”, and ACT indicator LED lights up.
3. When Analog 1 current output exceeds the upper/lower setting range, the display shows and
twinkles the symbol ”pH-mA▲/ pH-mA▼” or ”ORP-mA▲/ ORP-mA▼”. When Analog
2 current output exceeds the upper/lower setting range, the display shows and twinkles the
symbol ” °C-mA▲/ °C -mA▼”.
4. When PID using Relay 1/Analog 2 as Direct control, the display twinkles the description:
“REL1-Lo/ pH(ORP)-mA▼; When PID using Relay 2/Analog 2 as Reverse control, the
display twinkles the description: “REL2-Hi/ pH(ORP)-mA▲ .
5. When PID continually makes 100% out and exceeds Expiring time, the display twinkles the
description: “Expiring”.
Analog 2 output
current over range
alarm
Control function
on hold
:Measurement mode
:Set-up mode
:Calibration mode
Wash device in
action condition
Measurement unit
Clock
Analog 1 output
current over range
alarm
Temperature
compensation mode
(MTC/ATC)
Temperature value
Measurement value
REL 1 high or
low point alarm
REL 2 high or
low point alarm
17
Table of contents
Other Suntex Transmitter manuals

Suntex
Suntex PC-3310 Installation manual

Suntex
Suntex CT-6300RS User manual

Suntex
Suntex TC-7100 User manual

Suntex
Suntex CT-6110-POL User manual

Suntex
Suntex TC-7310-RS User manual

Suntex
Suntex EC-4110-I User manual

Suntex
Suntex EC-4110 User manual

Suntex
Suntex PC-3310-RS User manual

Suntex
Suntex TC-7310-RS-M User manual

Suntex
Suntex PC-3110-RS User manual
Popular Transmitter manuals by other brands

Labom
Labom COMPACT ECO CA1 0 Series operating instructions

HK Instruments
HK Instruments RHT-MOD Series installation instructions

Rice Lake
Rice Lake SCT-1SX-MODBUS TCP/IP quick start guide

Ascon tecnologic
Ascon tecnologic ATT1 quick start guide

PKP
PKP PUM04 instruction manual

Q5X
Q5X AquaMic QT-AD10A quick start guide