SYCLOPE INDIG'O How to use

Installation and starting instructions
References : CEN0000, CEN0001 and CEN0005 Rev : 2
SYCLOPE INDIG’O
®
controller for
semi publics
swimming pool
s
( art
1)

Generals information age 2/28
Installation and starting instructions for SYCLOPE INDIG’O
®
arts of the general documentation
art 1 : Installation and starting instructions
art 2 : rogramming instructions
General details:
SYCLOPE Electronique 20 5
®
Notice of the 01/12/2015 Rev 2
Controller for semi publics swimming pools.
Range INDIG’O
®
art 1 : Installation and starting instructions
Editor:
SYCLOPE Electronique S.A.S.
Z.I. Aéropole pyrénées
Rue du Bruscos
64 230 SAUVAGNON - France –
Tel : (33) 05 59 33 70 36
Fax : (33) 05 59 33 70 37
Email : syclope@syclope.fr
Internet : http://www.syclope.fr
© 2015 by SYCLO E Electronique S.A.S.
Subject to modification
►

Contents age 3/28
Installation and starting instructions for SYCLOPE INDIG’O
®
I.
Generals information ......................................................................................................... 4
1)
Field of applications ........................................................................................................... 4
2)
Use of the document ......................................................................................................... 5
3)
Symbols and signs ............................................................................................................. 5
4)
Storage and transport ........................................................................................................ 6
5)
ackaging ......................................................................................................................... 6
6)
Warranty .......................................................................................................................... 6
II.
Environment and safety procedures .................................................................................... 7
1)
Use of the equipment ........................................................................................................ 7
2)
User obligations ................................................................................................................ 7
3)
Risk prevention ................................................................................................................. 7
4)
Identification and localization of the identification label ........................................................ 8
5)
Disposal and conformity ..................................................................................................... 9
III.
Technical specifications and main functions ........................................................................10
1)
Technical specifications.....................................................................................................10
2)
Mains functions ................................................................................................................11
3)
arameters and measuring ranges ....................................................................................12
IV.
Installation and connections ..............................................................................................13
1)
Requirements of installation ..............................................................................................13
2)
Installation of the wall-mounted controllers........................................................................13
3)
Opening and closing of the transparent door ......................................................................14
4)
Opening and closing of the connections cover ....................................................................14
5)
Identification of electrical connections ...............................................................................15
6)
Changing internal fuse of powered relay output
1Dosage
......................................................16
7)
Connecting of the primary power supply X
1Secteur
.................................................................17
8)
Connecting of the powered relay
1Dosage
............................................................................17
9)
Connecting of the free dry contact relay R
1Alarme
.................................................................17
10)
Connecting of the measuring input I
In1Capteur
or J
1Capteur
........................................................18
11)
Connecting of the analog output I
OUT1
................................................................................18
12)
Connecting the conditional input K
1 ause
.............................................................................19
V.
resentation of the Human/Machine interface ....................................................................20
1)
Keyboard .........................................................................................................................20
2)
ermanent display, pictograms and messages ....................................................................21
3)
Alarms .............................................................................................................................22
VI.
Commissioning .................................................................................................................23
VII.
Maintenance.....................................................................................................................24
VIII.
CE compliance certificate ..................................................................................................25

Generals information age 4/28
Installation and starting instructions for SYCLOPE INDIG’O
®
I. Generals information
1) Field of applications
The SYCLOPE INDIG’O
®
controller you have just purchased is an electronic device especially
developed for water treatment in recreational water. It has been carefully manufactured to satisfy
all the requirements of this kind of application.
It has been developed to match all different configuration and all needs for analysing and controlling
water in semi-public swimming pool, hotels, camping, residential pool, spas…
Designed with an easy to understand interface, the SYCLOPE INDIG’O
®
controller is equipped
with one single measuring input for sensor use in water treatment. The unit permanently analyse
and control the measured parameter and alert the user in case of problem.
The following instructions contain all the information required for the installation, use and maintenance
of your new equipment.
Installation
Technical specifications
Commissioning instructions
Safety tips
If you would like to receive further information or if you encounter any difficulties not described in
this manual, please contact your usual retailer or else directly contact the sales department of
SYCLO E Electronique S.A.S., either at the agency or at the office for your region, or the
technical/quality departments of our establishments. We will do everything to help you and ensure
you benefit from our advice and know-how in the field of measurement and treatment of swimming
pool water.
Contact : technique@syclope.fr

Generals information age 5/28
Installation and starting instructions for SYCLOPE INDIG’O
®
2) Use of the document
lease read this entire document before starting to install, adjusting or commissioning your controller
device, in order to ensure the safety of users, the processes and the equipment.
The information provided in this document must be strictly observed. SYCLO E Electronique S.A.S.
declines all responsibility in cases where failure to comply with the instructions of this documents is
observed.
The following symbols and pictograms will be used to facilitate reading and understanding of these
instructions.
● Information
► Action to be taken
Item of a list or catalogue
3) Symbols and signs
Identification of a continue voltage or current
Identification of an alternative voltage or current
rotective ground
Functional ground
Risk of injury or accident. Identify a warning concerning a potentially dangerous risk.
Documentation must be consulted by the user with each time the symbol is notified. If the
instructions are not respected, that presents a risk of death, physical injuries or property
damages.
Electric hazard. Identify a warning statement relative to a mortal electric danger. If the
instructions are not strictly respected, that implies an inevitable risk of physical injuries or
death.
Risk of incorrect operation or damage for the device.
Comment or particular information.
Recyclable element.

Generals information age 6/28
Installation and starting instructions for SYCLOPE INDIG’O
®
4) Storage and transport
It is important to store and transport your SYCLOPE INDIG’O
®
in its original packaging in
order to minimize risk of damage.
Furthermore, the package must be stored in an environment that is protected against humidity
and exposure to chemical products.
Environmental conditions for transport and storage:
Temperature: -10 °C to 70 °C
Air humidity: Maximum of 90% with no condensation
5) ackaging
The controller is delivered without electrical power cable.
The pre-holes of the box are drilled and equipped with according electrical glands in
compliance with I 65 level protection. Cables must be adapted to the electrical glands to
respect the level of protection.
Content of the packaging:
One analyser/controller SYCLOPE INDIG’O
®
Installation and starting instruction notice
rogramming notice
6) Warranty
The warranty is provided according to the terms of our general conditions of sale and delivery as long as
the following conditions are met:
Use of the equipment according to the instructions of this notice
No modifications of the equipment which may modify its behavior and no incorrect manipulation
Respect for the electrical safety conditions
Consumable material is no longer covered by the warranty when in use.

Environment and safety procedures age 7/28
Installation and starting instructions for SYCLOPE INDIG’O
®
II. Environment and safety procedures
lease:
Read this manual carefully before unpacking, installing or commissioning this equipment
Take into account all the hazards and recommended precautionary measures
Failure to respect these procedures can result in serious injury to users or damage the device.
1) Use of the equipment
The SYCLOPE INDIG’O
®
system has been designed to measure and control Chlorine, Bromine, pH,
Redox potential, Ozone, etc… by means of sensors and controls of suitable actuators in the context of
the possible uses described in this manual.
All other uses are considered to be non-conforming and must therefore be forbidden. SYCLO E
Electronique S.A.S. will not be responsible in any case for any damages that result from such
uses.
Any use of sensors or interfaces not-in conformity to the features defined in this handbook
must also be proscribed.
2) User obligations
The user undertakes not to allow its employees to work with the SYCLOPE INDIG’O
®
equipment
described in this manual unless they:
Are aware of the fundamental instructions relating to work safety and prevention of accidents
Are trained in the use of the device and its environment
Have read and understood these instructions, warnings and manipulation rules
3) Risk prevention
The installation and connection of the SYCLOPE INDIG’O
®
equipment should only be
performed by personnel specialized and qualified for this task.
The installation must comply with current safety standards and instructions!
Before switching on the controller or manipulating the relay outputs, remember always to cut
off the primary power supply!
Never open the controller when it is powered on!
Maintenance operations and repairs should only be performed by trained, specialized
personnel!
Take care when choosing the location for installing the equipment according to the
environment!
The SYCLOPE INDIG’O
®
electronic box should not be installed in a hazardous environment
and should be protected against splashing with water or chemical products. It should be
installed in a dry, well-ventilated location, isolated from corrosive vapours.

Environment and safety procedures age 8/28
Installation and starting instructions for SYCLOPE INDIG’O
®
Make sure that the chemical sensors used with this device correspond well to the chemicals
used. Refer to the individual technical note of each sensor. Chemistry of water is very complex,
in case of doubt, contact immediately our engineering service or your approved
installer/reseller.
Chemical sensors are sensitive elements using consumable parts. They must be supervised,
maintained and calibrated regularly using specific calibrator systems not-provided with this
equipment. In the event of defect, a surplus possible hazard of chemical injections can be
noted. In the doubt, a service contract must be taken near your reseller/installer or failing this
near our engineering services.
Contact your approved installer/reseller or our business service
for more information.
4) Identification and localization of the identification label
Label of the manufacturer articular risks. Read the notice
Model of the product roduct which can be recycled
Reference of the product Limitation of dangerous substances
Range of power supply EC certified
Values of the maximum current Country of origin
Classify protection Manufacturer square code
Identification of the manufacturer
Serial number
Identification label
1
2
3
9
4
5
6
8
1
1
1
2
7
1
4
1
0
1
3
INDIG’O
Ref
:
CEN
000
X
90
-
240VAC
50/
60Hz
www.syclo e.fr
Fabriqué en France
5,2
-
0,1
A
IP65
S/N: 13044217
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4

Environment and safety procedures age 9/28
Installation and starting instructions for SYCLOPE INDIG’O
®
5) Disposal and conformity
The recyclable packaging of the SYCLOPE INDIG’O
®
equipment must be disposed of according to
current regulations.
Elements such as paper, cardboard, plastic or any other recyclable elements must be taken
to a suitable sorting center.
According to European directive 2002/96/EC, this symbol means that as of 12 August 2005
electrical appliances cannot be thrown out together with household or industrial
waste. According to current regulations, consumers within the European Union are required,
as of this date, to return their used devices to the manufacturer, who will take care of
disposing them at no extra expense.
According to European directive 2002/95/EC, this symbol means that the SYCLOPE
INDIG’O
®
controller is designed in compliance with the restrictions on hazardous substances
According to low-voltage directive (2006/95/EC) and the electromagnetic compatibility
directive (2004/108/EC), this symbol means that the device has been designed in
compliance with the previously cited directives

Technical specifications and main functions age 10/28
Installation and starting instructions for SYCLOPE INDIG’O
®
III. Technical specifications and main functions
1) Technical specifications
General characteristics
Type Features(s) Marker (s)
Consumption 5 W Max. (Without equipment connected on 1) -
ower supply 90-240 VAC 50 or 60Hz X1 Secteur
Electric protection Fuse 160 mA. Rearmament by power supply cut-off. F6
Working T°C -5 °C to 45 °C (23 °F to 113 °F) -
Storage T°C -10 °C to 70 °C (10 °F to 158 °F) -
Humidity Max. 90% without condensation -
Enclosure material ABS or olycarbonate (US and Canada) -
Dimensions
Length : 188 mm (7,4 inch)
Width : 160 mm (6,3 inch)
Height : 106 mm (4,2 inch)
-
Weight 800 g -
rotection class I 65 -
Display LCD Screen 128x128 with back-light (White/Blue) -
Inputs
Measuring input
1x powered (24V) analog input 4…20 mA
Or
1x potentiometric input for pH or Redox (OR )
Iin1 Capteur
J1 Capteur
Conditional input 1x flow switch input (NO or NC) K1 ause
Outputs
Relays outputs 1x powered relay output max. 2A/250 VAC
1x Free potential dry contacts
1 Dosage
R1 Alarme
Analog output 1x 0/4…20mA outputs Max 500 Ω Iout1
Electrical protection for
powered relay output Quick-fuse 5A Glass 5x20mm. F2

Technical specifications and main functions age 11/28
Installation and starting instructions for SYCLOPE INDIG’O
®
2) Mains functions
Mains functions
Function Specification(s) Remarque(s)
Analyse Analyse of one single parameter arameters depend of version
Control 1x powered (24V) analog input 4…20 mA WM control with proportional regulation
or On/Off hysteresis regulation
Alarms 1x Free potential dry contacts Set in real values
Low, high or overdosing alarm
Conditional input Flow switch Control of injections with an external flow
switch.
Maintenance Assistance during maintenance Test function with control of each output
Clear message displayed with pictures

Technical specifications and main functions age 12/28
Installation and starting instructions for SYCLOPE INDIG’O
®
3) arameters and measuring ranges
Reference Type arameter Range
CEN0000 4-20 mA powered analog input
Free chlorine
Active chlorine
Total chlorine
Chlorine dioxide
BCDMH Bromine
DBDMH Bromine
Free bromine
Ozone
Turbidity
0 to 1 /2 / 10 / 20 ppm
0 to 1 /2 / 10 / 20 ppm
0 to 1 /2 / 10 / 20 ppm
0 to 1 /2 / 10 / 20 ppm
0 to 1 /2 / 10 / 20 ppm
0 to 1 /2 / 10 / 20 ppm
0 to 1 /2 / 10 / 20 ppm
0 to 1 /2 ppm
0 to 50 / 100 / 200/ 500 / 1000 NTU
CEN0001 otentiometric input (pH) pH 0 to 14 pH
CEN0005 otentiometric input (Redox) Redox (OR ) 0 to 1000 mV

Installation and connections age 13/28
Installation and starting instructions for SYCLOPE INDIG’O
®
IV. Installation and connections
1) Requirements of installation
To guarantee user safety and ensure correct operation of your SYCLOPE UNIS’EAU
®
please
observe the following installation instructions:
Install the controller in a dry location
The controller must be protected against rain, frost and direct sunlight
The room temperature must range between 0°C and 50°C, with no condensation.
Choose an installation location free from vibration, on a suitable support and with no
deformation
If these instructions are not observed:
The controller is at risk of being damaged
The measurements can be disrupted
The warranty is not applicable!
2) Installation of the wall-mounted controllers
Before performing the installation and electrical connections, remember to turn off the power!
The rating of I 65 is only guaranteed when the closing cover and the glass of the electric box
are closed and when the cable glands match the diameters of your cables and are correctly
sealed
► Drilling three holes (∅ 5-mm) according to the following drilling plan
► Insert the 5-mm plugs using a hammer
► Insert the upper screw (top screw) first without completely tightening it
► Insert the lower screws and tighten them
► Check the correct and accurate fixing to the wall.

Installation and connections age 14/28
Installation and starting instructions for SYCLOPE INDIG’O
®
3) Opening and closing of the transparent door
To ensure the I 65 protection class, the transparent door must be closed after usage and
being sure of the O-ring quality each time.
The controller box is equipped with an automatic lock system which must be understood to manipulate
it.
For opening the transparent door:
For opening and locking transparent door:
4) Opening and closing of the connections cover
To ensure I 65 protection class, the connection cover must be closed after usage and the O-
ring must be checked each time.
Use a specific screwdriver to remove the two screws for opening the cover.
Door locked
Raise the lock and pull
forward it.
Door opened
ass the fingers behind
the lock and bring the
door with the inch
ress on the lock with the
palm of the
hand
Door locked

Installation and connections age 15/28
Installation and starting instructions for SYCLOPE INDIG’O
®
5) Identification of electrical connections
Electrical installation must be performed in accordance with current standards by authorized
personnel!
A 30 mA differential circuit breaker must be installed!
A breaker circuit of maximum 6A must be installed near the controller and easily accessible to
stop the main power. It must be identified as a circuit-breaker for the controller!
Before performing the connections, remember to turn off the power!
Reference : CEN0000 with 4-20 mA analog input
References : CEN0001 and CEN0005 with pH or OR entry
Internal protection:
INDIG’O controller is protected against short-circuits by an automatic restart fuse of 160mA
and against surges by a varistor of 275V.
1
owered relay output 1 is protected by a glass quick-fuse of 5A max. 250V.
Reference Name
FUS5X20R5000 Quick-fuse 5A 5x20 Glass
In case of fuse burned, check that the card is not burnt out. In this case, complete electronic
card must be changed!
In case of varistor destroyed, please return the controller to our technical after-sales
department for repairing!

Installation and connections age 16/28
Installation and starting instructions for SYCLOPE INDIG’O
®
6) Changing internal fuse of powered relay output
1Dosage
Before changing the fuse, be sure power supply is disconnected!
Use only an original fuse. Don’t replace it by another one with higher protection value!
► Open the transparent door and unscrew the 4 screws of the front face with a compatible
screwdriver.
► Disconnect the flat cable between the 2 electronic plates
► Localise the fuse on the bottom electronic card
► Remove the protection cover on the fuse
► Change the fuse and replace the protection cover
► Reconnect the flat cable between electronic cards and replace the 4 screws to fix the front
face
► Do not screw them hardly because the electronic box is made in plastic material
F2

Installation and connections age 17/28
Installation and starting instructions for SYCLOPE INDIG’O
®
7) Connecting of the primary power supply X
1Secteur
The SYCLOPE UNIS’EAU
®
controller is equipped with a switching power supply. It is
therefore able to be supplied by AC voltage comprised between 90V to 240V - 50/60Hz.
► Use a 3-point 1.5 mm
2
cable to wire the power supply
► Strip the 3 wires on 7 mm
► ass the 3-point cable through a cable gland
► Wire the live cable L and the neutral cable N to the terminal block X
secteur
► Wire the ground cable PE to the terminal block X
secteur
► Tighten the cable gland to ensure tightness when done
The SYCLOPE INDIG’O
®
controller does not have its own independent power switch. It is
directly powered when connected to the main power supply.
8) Connecting of the powered relay
1Dosage
The powered relay (Entry voltage = output voltage) is used to control the measured parameter driving
a dosing pump or a solenoid valve for example.
► Strip the 3 wires of the dosing unit on 7 mm
► ass the 3-point cable through a cable gland
► Wire the live cable on 26 and the neutral cable on the 27 to the terminal block P
Dosage
► Wire the ground cable PE to the terminal block P
Dosage
► Tighten the cable gland to ensure tightness when done
9) Connecting of the free dry contact relay R
1Alarme
The free dry contact relay is used to send alarms.
► Strip the 2 wires of the alarm unit on 7 mm
► ass the 2 wires cable through a cable gland
► Wire on 22 the common point on the terminal block R
Alarme
► If you want a NC function (Normally closed), wire on 23 the other point on R
Alarme
► If you want a NO function (Normally opened), wire on 22 the other point R
Alarme
► Tighten the cable gland to ensure tightness when done

Installation and connections age 18/28
Installation and starting instructions for SYCLOPE INDIG’O
®
10) Connecting of the measuring input I
In1Capteur
or J
1Capteur
The type of measuring input you have on the SYCLOPE INDIG’O
®
depend of the ordered reference.
It can be a powered (24V) 4-20 mA analog input or a potentiometric input for connecting a ph or an
OR sensor.
The 4-20 mA analog input I
In capteur
is powered and should not be supply!
The potentiometric input could only receive pH or OR sensor designed for this kind of input.
Inputs I
In capteur
and J
Capteur
are galvanically isolated.
No claim will be accepted in case of failure of the sensor by a wrong connection!
For the 4-20 mA version
► Strip the 2 wires coming from the sensor on 7 mm
► ass the 2 wires cable through a cable gland
► Wire on the (+) and on 2 the (-) from the sensor (respect polarity) on terminal block I
In capteur
► Tighten the cable gland to ensure tightness when done
For the pH or OR version
► Strip carefully the coaxial cable and separate the shield cable to obtain 2 distinct wires
► ass the 2-points coaxial cable through a free cable gland
► Wire the shield part to R (1) and the hot wire to P (2) on terminal block J
Capteur
► Tighten the cable gland to ensure tightness when done
11) Connecting of the analog output I
OUT1
The analog output I
OUT
is used to send the measured value to a recorder or a LC by a 0/4-20 mA
signal.
► Strip the 2 wires coming from the LC on 7 mm
► ass the 2 wires cable through a cable gland
► Wire on 4 (+) and 5 (-) (respect polarity) on the terminal block I
OUT
.
► Tighten the cable gland to ensure tightness when done

Installation and connections age 19/28
Installation and starting instructions for SYCLOPE INDIG’O
®
12) Connecting the conditional input K
1 ause
Controller SYCLOPE INDIG’O
®
is equipped with a conditional input K
Pause
that stop the dosing when
the flow in the measuring housing is not correct. This input could be programmed as a NO or NC function
to match different type of flow switch.
It is necessary to stop dosing when the flow is not correct in the measuring housing.
The K
Pause
input is designed to receive a dry contact (NO or NC) or a N N signal from an
inductive flow switch.
Connecting of a dry contact
► Strip the 2 wires coming from the flow switch on 7 mm
► ass the 2 wires cable through a cable gland
► Wire on 24 (+) and 25 (-) the cable from the flow switch
► Tighten the cable gland to ensure tightness when done
Connecting of a N N contact coming from an inductive flow switch
► Strip the 3 wires coming from the flow switch on 7 mm
► ass the 3 wires cable through a cable gland
► Wire on 0 (+12V) the brown wire of the flow switch ( ower supply)
► Wire on 8 (0V) the blue wire of the flow switch (Ground GND)
► Wire on 25 (-) the black wire of the flow switch (Signal)
► rogram the way of the K
Pause
in NC in the Configuration Menu (See programming instructions)

resentation of the Human/Machine interface age 20/28
Installation and starting instructions for SYCLOPE INDIG’O
®
V. Presentation of the Human/Machine interface
1) Keyboard
Display 128x128
Key “Menu” : Allow to go in the different menu or to valid a setting
Key “START/STO ” : Allow to start or stop the control. Allow also to acquit the alarms
Key “Esc” : Allow to return at the permanent display
Arrow key “TO ”: Allow to increment a value or change a setting
Arrow key “BOTTOM”: Allow to decrement a value or change a setting
Other manuals for INDIG'O
1
Table of contents
Other SYCLOPE Controllers manuals

SYCLOPE
SYCLOPE TERE'O User manual

SYCLOPE
SYCLOPE TRACE'O User manual

SYCLOPE
SYCLOPE DOUBLEAU Installation manual

SYCLOPE
SYCLOPE ODISEA Installation manual

SYCLOPE
SYCLOPE ALTICE'O Use and care manual

SYCLOPE
SYCLOPE INDIG'O Installation manual

SYCLOPE
SYCLOPE UNIS'EAU How to use

SYCLOPE
SYCLOPE TERE'O Touch CU/PT Guide

SYCLOPE
SYCLOPE EVASION Installation manual