1 I56-5925-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Model LASS-WSS-NC
Addressable Wall Mount Sounder&Strobe
Xi'an System Sensor Electronics Ltd.
28 Tuanjie South Road
Xi'an Hi-tech Development Zone
710075, China
Tel: (+86) 029 85387800
Fax: (+86)
029 88332959
SPECIFICATION
Item Parameter Description Note
Operating Voltage 24VDC(15 to 32VDC)
Avg. Standby Current <400µA 24VDC, No Communication, No sounding/flashing
Alarm Current <11mA High Volume, 24VDC
<8.5mA Low Volume, 24VDC
Operating Temp -25
℃
to +70
℃
Humidity 10 to 95% R.H. Non-condensing
Ingress Protection IP33C Approved to EN54-3
IP35(With Water-proof box ) ***
Approved Sound
Pressure Level 86±4dB(A) 1m , High Volume, Tone 21 @24V(5.0mA) *Approved to EN54-3
High Volume
90±4dB(A) 1m , 90°,High Volume, Tone 21 @24V(5.0mA) **
92±3dB(A) 1m , 90°,High Volume, Tone 13 @24V(6.0mA) **
91±5dB(A) 1m , 90°,High Volume, Tone 12 @24V(5.7mA) **
95±5dB(A) 1m , 90°,High Volume, Tone 19 @24V(5.5mA) **
Low Volume
86±3dB(A) 1m , 90°,Low Volume, Tone 21 @24V(4.7mA) **
86±4dB(A) 1m , 90°,Low Volume, Tone 13 @24V(5.0mA) **
81±3dB(A) 1m , 90°,Low Volume, Tone 12 @24V(4.7mA) **
84±6dB(A) 1m , 90°,Low Volume, Tone 19 @24V(4.7mA) **
Tone Type 4 See table 1: ‘Sound setting
’ for detailed tones
Flash Pattern 2 See table 2: ‘Flash Pattern’
Flash Intensity >1cd
Height 47mm
Diameter 122mm
Weight 176±6g
Note: * Detailed description see table A
** These volume & tone settings are not approved to EN54-3.
***This ingress protection is not approved to EN54-3.
Meet the following Standards requirements: EN54-3 ,AS ISO 7240.3:2014 Strobe is not approved to EN54-23
B Before installing and using the product, please read the system wiring
and installation manual thoroughly. If the products will be installed in an
existing operational system, inform the operator and local authority that
the system will be temporarily out of service, disconnect power to the
control panel before installing the products.
NOTICE: This manual should be left with the owner/user of this
equipment.
GENERAL
LASS-WSS-NC is an intelligent addressable AV products designed to
alarm light/sound for emergency events, and be able to communicate
with control panel by intelligent protocol.
It is designed specifically for analogue addressable fire alarm system
and only can be connected to control panels with a compatible
proprietary analogue addressable communication protocol. It is
powered from the loop and can be controlled via the communication
protocol(s). The Wall Mount Version is compatible with B501 mounting
base. Up to 99 addresses are available via two rotary selector
switches. The sounders have 2 volume levels (high/low) and 4 tone
sets. The alarm light/sound can be tested on field.
INSTALLATION
It must be installed and wired with B501 mounting base.
1. Verify the product type matches with product drawing.
2. Set the address via two rotary selector switches. Please refer to
“Address setting”.
3. Volume and tone setting are realized by 4 digit DIP switch. On field
testing can be tested via DIP switch.
4. Plug the Sounder base into B501 mounting base.
5. Turn the Sounder base clockwise until it drops into place.
6. Continue turning the Sounder base clockwise to lock it in place.
SETTING
Address setting
Rotary-decade switches are provided for setting the base’s address
whose range is from 1 to 99. (Default address is 01).
Address is set by turning the switches.
Address is calculated as below formula: Address = TENS *10 +
ONES*1. For instance: Address 05 = 0*10 + 5*1.
Tamper-resistant capability
Addressable Base sounder include a tamper-resistant capability that
prevents its removal from the B501 base and the removal of installed
detector without the use of a tool.
Figure 1
Figure 2
I56
-
5925
-
000
A5665-002
ONES
DIP switch for
tone setting
COMM+
COMM-
TENS
RA
Remote
Annunciator
B501
Mounting Base
Wall Mount
Sounder&
Strobe
A5665-006
2 I56-5925-000
When B501 mounting base enables tamper
-
resista
nt function,
special
tools must be used to disassemble addressable base. Please refer to
below figure: use straight screwdriver to break specific position, then
insert the screwdriver and maintain in its position. Then you can
disassemble the Sounder base by turning anticlockwise
Figure 3
Synchronization
When addressable base send out a fire alarm, control panel can send
out a certain signal to synchronize all the addressable AV in same
loop to send out fire alarm signal.
Note: Please dispose electronic waste following national or local regulations
after being scrapped or replaced. Do not discard.
Table 2: Flash Pattern
Flash Pattern Description
Evacuate flash pattern
Synchronized with Tone
21, 19 or 13
Alert flash pattern
Synchronized with Tone 12
THREE-YEAR LIMITED WARRANTY
Xi’an System Sensor warrants its enclosed product to be free from
defects in materials and workmanship under normal use and service
for a period of three years from date of manufacture. Xi’an System
Sensor makes no other express warranty for the enclosed product. No
agent, representative, dealer, or employee of the Company has the
authority to increase or alter the obligations or limitations of this
Warranty. The Company’s obligation of this Warranty shall be limited
to the replacement of any part of the product which is found to be
defective in materials or workmanship under normal use and service
during the three year period commencin g with the date of
manufacture. After phoning Xi’an System Sensor for a Return
Authorization Number and faxing a copy of the filled CUSTOMER
RETURNS with authorized RA# to Xi’an System Sensor, send
Defective units with a copy of the form postage prepaid to: Xi’an
S y s t e m S e n s o r
Electronics, Ltd./ 28 Tuan Jie South Road/ Xi’an National Hi-tech
Industrial Development Zone, 710075/ China. Please include a note
describing the malfunction and suspected cause of failure. The Company
shall not be obligated to replace units which are found to be defective
because of damage, unreasonable use, modifications, or alterations
occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s
negligence or fault. Some states do not allow the exclusion or
limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you
specific legal rights, and you may also have other rights which vary
from state to state.
Figure
5 System wiring diagram
Table 1: Sound setting
Bit:1, 2, 3, 4
(0 = off/1 =
on/X=random)
Description
Tone
setting
0 0 X X
Tone 21(second stage: tone 12)
400HZ
1200HZ
1 Sec
4 Sec
0 1 X X
Tone 13(second stage: tone 12)
500HZ
1200HZ
0.25 Sec 3.75 Sec
1 0 X X
Tone 12(second stage: tone 13)
Off
420HZ
0.625 Sec 0.625 Sec
1 1 X X
Tone 19(second stage: tone 12)
4 Sec
1 Sec
Off
950HZ
Volume
setting X X 1 X High volume
X X 0 X Low volume
Test
setting
please set
to 0 under
normal use
X X X 1 Field testing on
X X X 0 Field testing off
Table A
Operational Performance: Tone 21
(High Volume)
Sound Pressure Level
dBA
400HZ
1200HZ
1 Sec
4 Sec
LASS-WSS-NC
1m
Horizontal
15Vdc
15°
83.7
45° 85.1
75° 90.4
105°
90.5
135°
86.4
165°
84.4
32Vdc
15°
83.8
45°
85.2
75°
90.4
105° 90.7
135°
86.3
165°
84.7
Vertical
15Vdc
15°
82.9
45°
85.7
75°
90.4
105°
90.5
135° 87.0
165° 83.2
32Vdc
15°
83.2
45°
85
.9
75°
90.5
105°
90.6
135°
87.0
165°
83.2
Ver. D
A5665
-
007
A5665-005
1 Sec
4 Sec
1.25 Sec

Other System Sensor Security System manuals

System Sensor CH1224 User manual

System Sensor

System Sensor CH1224 User manual

System Sensor SpectrAlert Advance P2R User manual

System Sensor

System Sensor SpectrAlert Advance P2R User manual

System Sensor APA151 User manual

System Sensor

System Sensor APA151 User manual

System Sensor PS24LO User manual

System Sensor

System Sensor PS24LO User manual

System Sensor SpectrAlert S900RLFIRE User manual

System Sensor

System Sensor SpectrAlert S900RLFIRE User manual

System Sensor FL0111E User manual

System Sensor

System Sensor FL0111E User manual

System Sensor L-Series User manual

System Sensor

System Sensor L-Series User manual

System Sensor SpectrAlert S1224MCW User manual

System Sensor

System Sensor SpectrAlert S1224MCW User manual

System Sensor 2012/24AUS User manual

System Sensor

System Sensor 2012/24AUS User manual

System Sensor APA151 User manual

System Sensor

System Sensor APA151 User manual

System Sensor ExitPoint PF24VA User manual

System Sensor

System Sensor ExitPoint PF24VA User manual

System Sensor ECO 2000 Technical specifications

System Sensor

System Sensor ECO 2000 Technical specifications

System Sensor SpectrAlert Series User manual

System Sensor

System Sensor SpectrAlert Series User manual

System Sensor PS24LO User manual

System Sensor

System Sensor PS24LO User manual

System Sensor P4RLA User manual

System Sensor

System Sensor P4RLA User manual

System Sensor APA451 User manual

System Sensor

System Sensor APA451 User manual

System Sensor CO1224A User manual

System Sensor

System Sensor CO1224A User manual

System Sensor B200SR-LF User manual

System Sensor

System Sensor B200SR-LF User manual

System Sensor P2R User manual

System Sensor

System Sensor P2R User manual

System Sensor SpectrAlert S1224MCW User manual

System Sensor

System Sensor SpectrAlert S1224MCW User manual

System Sensor SSM24-6 Technical specifications

System Sensor

System Sensor SSM24-6 Technical specifications

System Sensor ExitPoint PF24V User manual

System Sensor

System Sensor ExitPoint PF24V User manual

Popular Security System manuals by other brands

CAP CT-SMZW2008-ES user manual

CAP

CAP CT-SMZW2008-ES user manual

MOOSE Z950 user guide

MOOSE

MOOSE Z950 user guide

Assa Abloy Yale SAA5015 quick start guide

Assa Abloy

Assa Abloy Yale SAA5015 quick start guide

Citadel XR1 G3 operating instructions

Citadel

Citadel XR1 G3 operating instructions

BEK Spyder protect quick start guide

BEK

BEK Spyder protect quick start guide

Juniper JSA3800 How to set up

Juniper

Juniper JSA3800 How to set up

Algo 8180 manual

Algo

Algo 8180 manual

EverAccess EFM-AL-1A user manual

EverAccess

EverAccess EFM-AL-1A user manual

HAI Omni Pro II installation manual

HAI

HAI Omni Pro II installation manual

INTERVOX Residencia 3 installation manual

INTERVOX

INTERVOX Residencia 3 installation manual

Kidde KN-COPE-DCA user guide

Kidde

Kidde KN-COPE-DCA user guide

PNI House PTZ1500 user manual

PNI

PNI House PTZ1500 user manual

ADT ACCORD XPC installation manual

ADT

ADT ACCORD XPC installation manual

GE Concord Ultra User instructions

GE

GE Concord Ultra User instructions

Commax CDS-481L user manual

Commax

Commax CDS-481L user manual

SANJIANG JB-FSD-9082 quick start guide

SANJIANG

SANJIANG JB-FSD-9082 quick start guide

Price PARC Node manual

Price

Price PARC Node manual

SenseAir eSENSE II FAI Disp installation manual

SenseAir

SenseAir eSENSE II FAI Disp installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.