TCS UbiquiSTAT User manual

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com 202211
|Quick Setup Guide
UbiquiSTAT
Commercial BACnet Controller

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
2 3
Introduction
Congratulations on choosing the UbiquiSTAT™ room controller! The UbiqiSTAT series of controllers are feature rich,
multifunction touchscreen devices providing extensive controls across a wide range of HVAC applications.
This guide will explain the initial setup of the UbiquiSTAT and guide you step-by-step through the built-in Startup Wizard,
with which you can enter the basic conguration settings.
Refer to the UbiquiSTAT Installation Manual for instructions on installing, powering, and wiring the unit into your system.
Refer to the UbiquiSTAT Conguration Guide for instructions on conguring the device, the communications network,
and other devices that may be connected to this controller. Refer to the UbiquiSTAT BACnet Explorer Guide for advanced
information on using the built-in BACnet Explorer to edit the device’s BACnet programming objects directly.
If you have any questions regarding your UbiquiSTAT room controller, do not hesitate to contact TCS Technical Support at
800-288-9383, ext. 2. Our Technical Support Department hours are Monday – Friday, 7:00 a.m. to 7:00 p.m. (CST).
Setting Up the UbiquiSTAT
Complete the mounting, power, and RS-485 network wiring before setting up the UbiquiSTAT, as the face of the controller
is not powered until the UbiquiSTAT is assembled (refer to the UbiquiSTAT Installation Manual for more information.)
Use the Startup Wizard when setting up the UbiquiSTAT for the rst time or after resetting it to factory defaults. All
controls are disabled until after completing the Startup Wizard.
The Startup Wizard will guide you through the following settings:
• Display Settings: Select temperature measurement (Fahrenheit or Celsius), clock type (12-hour or 24-hour), and
display backlight preference (low, medium, or high).
• Date & Time: Set to the current time.
• Thermostat Type: Select whether the thermostat is controlling a conventional or heat pump HVAC system.
• System Mode: Select between automatic, heating, cooling, or fan plus recirculation.
• Occupied Fan Mode: Determine the status of the HVAC system’s fan when the room is occupied.
• Communication Mode: Wired models allow for selecting between TCSbus or BACnet MS/TP communication modes.
Wireless models allow additional selections for BACnet Wi-Fi or none, for use in stand-alone situations.
• Network Address: This must be unique for each controller on the RS-485 network. The valid address range is from 1
– 127. If you desire an address value of 0, you can enter this after completing the Startup Wizard.
• Baud Rate: Select the desired baud rate for your network. The baud rate defaults to 9,600 bps for TCSbus, and 38,400
bps for BACnet MS/TP. All controllers on the network must use the same baud rate.
• Device Instance: This number must be unique across the entire BACnet network. The initial value shown is a
combination of the TCS BACnet vendor ID (496) and the previously entered network address. This is done in an
attempt to create a unique value. However, we encourage users to create their own numbering system for all
controllers on the BACnet network.
• Wi-Fi Conguration: If BACnet Wi-Fi is available on your UbiquiSTAT, a series of screens will allow you to congure
your UbiquiSTAT to the desired Wi-Fi network.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
3
Using the Startup Wizard
After applying power to the UbiquiSTAT and assembling it for the rst time, you will see the INITIAL SETUP screen
directing to you touch the screen in order to continue.
STEP 2 On the WELCOME screen, press the NEXT button
to advance you to the next screen.
STEP 3 On the DISPLAY SETTINGS screen, select the
desired Temperature UNITS (Fahrenheit or
Celsius), CLOCK conguration (12-hour or 24-
hour), and BACKLIGHT setting (Low, Medium,
or High). Press the NEXT button to save the
settings and advance you to the next screen.
STEP 4 On the SET DATE screen, advance the settings
to reect the current date (MONTH, DAY, YEAR).
Press the NEXT button to save the settings and
advance you to the next screen.
STEP 1 Touch the INITIAL SETUP screen. This will
advance you to the next screen.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
4 5
STEP 5 On the SET TIME screen, advance the settings to
reect the current time (HOUR, MINUTE, AM or
PM). Press the NEXT button to save the settings
and advance you to the next screen.
STEP 6 On the THERMOSTAT TYPE screen, select
whether the UbiquiSTAT is controlling a
CONVENTIONAL equipment or a HEAT PUMP.
Press the NEXT button to save the settings and
advance you to the next screen.
STEP 7 On the SYSTEM MODE screen, select among
AUTO, HEAT, COOL, OFF, or OFF + FAN
RECIRCULATION. Press the NEXT button to save
the settings and advance you to the next screen.
System Mode: Conventional HVAC System
System Mode: Heat Pump System

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
5
STEP 9 On the COMMUNICATION MODE screen, select
among TCSbus, BACnet MS/TP, BACnet Wi-
Fi, or NONE (the BACnet Wi-Fi option is only
available on wireless UbiquiSTATs).
If you selected TCSbus or BACnet MS/TP,
pressing the NEXT button will save the settings
and advance you to STEP 10.
If you selected BACnet Wi-Fi, pressing the NEXT
button will save the settings and advance you to
STEP 12.
If you selected NONE, pressing the NEXT button
will save the settings, exit the Startup Wizard, and
return you to the HOME screen. (Communication
Mode can be gured at a later time.)
Communication Mode (Wi-Fi Models)
Communication Mode (Wired Models)
STEP 8 On the FAN MODE screen, select among
AUTO, ON, AUTO + RECIRCULATION, or COOL
(conventional only). Press the NEXT button to
save the settings and advance you to the next
screen.
Fan Mode (Conventional HVAC System)
Fan Mode (Heat Pump HVAC System)

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
6 7
STEP 12 In the DEVICE INSTANCE NUMBER screen, use
the keypad to enter a unique instance number
or network address for the UbiquiSTAT. This
number must be unique across the entire
network.
If you selected BACnet MS/TP in STEP 9,
pressing the NEXT button will save the settings,
exit the Startup Wizard, and return you to the
HOME screen.
If you selected BACnet Wi-Fi in STEP 9, pressing
the NEXT button will save the settings and
advance you to the AVAILABLE WI-FI NETWORKS
screen.
STEP 11 On the BAUD RATE screen, select the
communication speed your network requires.
The baud rate choices are 9,600, 19,200, 38,400,
57,600, 76,800, and 115,200 bps.
If you selected TCSbus in STEP 9, pressing
the NEXT button will save the settings, exit the
Startup Wizard, and return you to the HOME
screen.
If you selected BACnet MS/TP or BACnet Wi-Fi
in STEP 9, pressing the NEXT button will save
the settings and advance you to the DEVICE
INSTANCE NUMBER screen. We recommend that
TCSbus networks be set to 9,600 baud and that
BACnet MS /TP networks be set to 38,400 baud.
STEP 13 On the AVAILABLE WI-FI NETWORKS screen,
press the CONNECT button which corresponds
to your desired Wi-Fi network. (The <and >
buttons will allow you to scroll through the list of
available networks.) If the desired network does
not show up, press the Scan button to scan for
other available networks. Pressing the CONNECT
button will advance you to the next screen
STEP 10 If you selected TCSbus or BACnet MS/TP in
STEP 9, you will see the NETWORK ADDRESS
screen. Use the keypad to enter a unique network
address for the UbiquiSTAT. This number must
be unique across the entire network. Press the
NEXT button to save the settings and advance
you to the next step.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
7
STEP 14 On the ENTER WI-FI PASSPHRASE screen, use
the keypad to enter the selected network’s
passphrase. Press the SAVE button to save the
passphrase. You will then be prompted with a
message advising you that the previous Wi-Fi
settings will be erased. Press the OK button to
conrm your changes.
STEP 15 After pressing the OK button in the previous
screen, you will see the CONNECTION STATUS
screen. When the UbiquiSTAT has successfully
connected to the network, a DONE button will
appear. Press the DONE button to exit the Startup
Wizard and return you to the HOME screen.
Restoring to Factory Defaults
To restore the UbiquiSTAT to factory default settings, perform the steps outlined in this section. This procedure will reset
all programming changes and cannot be undone.
STEP 1 On the HOME screen, Press the SETTINGS
button in the main menu.

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
8
STEP 2 On the SETTINGS screen, press the ADVANCED
button to advance you to the next screen.
STEP 3 On the ADVANCED (1/2) screen, press the >
button to advance you to the ADVANCED (2/2)
Screen.
STEP 4 On the ADVANCED (2/2) screen, press the
FACTORY DEFAULTS button. You will then be
prompted with a warning message advising you
that loading the factory defaults will reset any
programming changes you have made. Press
the LOAD button to conrm your desire to reset
the UbiquiSTAT (this cannot be undone). You will
then return to the “INITIAL SETUP” screen.
Other manuals for UbiquiSTAT
2
Table of contents
Other TCS Controllers manuals
Popular Controllers manuals by other brands

Spirax Sarco
Spirax Sarco LC2610 Installation and maintenance instructions

Omron
Omron CS CS1W-ETN21 Quick start manual

GEM
GEM 639 eSyStep operating instructions

Leviton
Leviton intellect ZL057-D0Z quick start guide

VLT
VLT MCD 500 operating instructions

Heatit Controls
Heatit Controls Z-PUSH WALL CONTROLLER Installer manual

Fisher
Fisher FIELDVUE DVC6200 HW1 instruction manual

Chauvet
Chauvet RLC-737 user guide

visiplex
visiplex VNS2210 Quick installation guide

Mountz
Mountz ECT Series operating instructions

Precision Digital Corporation
Precision Digital Corporation ProtEX-MAX PD8-6210 instruction manual

Samson
Samson TROVIS 5572 Mounting and operating instructions