TCS US5182 User manual

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com 202305
|Installation Manual
Air Handling Unit Controller
US5182

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
2 3
Introduction ...........................................................................................................................................3
Mounting........................................................................................................................................................................... 3
Communication............................................................................................................................................................... 3
Device Terminations ....................................................................................................................................................... 3
Configuration................................................................................................................................................................... 3
US5182 Wiring Connections................................................................................................................4
Power................................................................................................................................................................................. 5
Digital Inputs .................................................................................................................................................................... 5
Analog Inputs ................................................................................................................................................................... 6
Analog Voltage Inputs .................................................................................................................................................... 6
Temperature Inputs......................................................................................................................................................... 7
Digital Outputs................................................................................................................................................................. 7
Analog Outputs................................................................................................................................................................ 8
RS-485 Port ...................................................................................................................................................................... 8
Ethernet Port .................................................................................................................................................................... 9
USB Port ............................................................................................................................................................................ 9
Contents

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
3
Introduction
Congratulations on choosing the TCS US5182 Air Handling Unit Controller! The US5182 is a sophisticated, multi-function
HVAC controller for air systems which provides numerous conguration choices.
This manual includes all the information necessary to properly install and wire your US5182. It includes a breakdown of
the input and output wiring/connections for each type of connection.
After installing the US5182, refer to the US5182 Quick Setup Guide for instructions on the basic setup of the device via
the interactive LCD screen. Refer to the US5182 Conguration Guide for instructions on conguring devices commonly
connected to this controller.
If you have questions regarding your US5182, do not hesitate to contact TCS Technical Support at 800.288.9383, ext. 2.
Our Technical Support Department hours are Monday – Friday, 7:00 a.m. to 7:00 p.m. (CST).
Mounting
Select a location that allows for easy access to the US5182’s removable screw terminal blocks and connection ports.
Using the four screw holes in the base of the device, mount the US5182 directly to a at vertical or horizontal surface in an
enclosure that is located away from excessive dust, heat, moisture, or direct sunlight.
Communication
The US5182 has three modes of communication: BACnet MS/TP, BACnet IP, and TCSbus. The communication mode
is congured through the Start-up Wizard on the control’s LCD interface (see the US5182 Quick Setup Guide). The RS-
485 port has a three-wire terminal connection for BACnet MS/TP or TCSbus. The Ethernet port provides the BACnet IP
protocol which integrates with networked systems.
Device Terminations
The US5182 has a total of six different input/output termination types, which include:
• Six digital inputs
• Six analog inputs
• Two analog voltage inputs
• Six temperature inputs
• Eight digital outputs
• Six analog outputs
The US5182 also includes:
• One RS-485 port
• One USB-C port
• One Ethernet port
The US5182 has removable screw terminal blocks that are accessible from the side, making physical connections easier
in the eld. The device terminations allow for specic congurations, as indicated in this manual. Wiring methods and
details are outlined in each section.
Conguration
You can congure the US5182 by connecting it directly to a PC running TCS Insight software or other BACnet software
platform via a USB-A to USB-C cable. If the US5182 will be used as a stand-alone device, all conguration should be
completed before installation. If the device is to be wired for communications, be sure to identify the US5182 with a
unique MS/TP or IP address (see the US5182 Quick Setup Guide).
Installation

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
4 5
Installation
US5182 Wiring Connections
Make wiring connections using a small screwdriver. The terminal blocks are removable, which may simplify the
installation.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
Power
RS-485
Ethernet
POE
Digital
Inputs
Digital
Outputs
Analog
Outputs
USB-C
Analog
Inputs
Temperature
Inputs
Analog
Voltage
Inputs

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
5
Installation
Digital Inputs
Digital inputs are used to receive status signals such as lter status, fan status, etc. Use unpowered dry contacts only with
18AWG two-wire twisted, stranded, shielded, or unshielded wire.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
Power
The US5182 is powered from a 24 VAC +20/–5% transformer. If wiring for communications, dedicated power must be
used to power the device, rather than power from the HVAC equipment. Several TCS controllers may be powered from the
same transformer, provided that the transformer has enough power.
Connect the power source using 18AWG two-wire twisted, stranded, shielded, or unshielded wire.
NOTE: Do not connect to 120VAC. When multiple TCS devices are using a single transformer, the polarity of the power
wiring must be maintained. All TCS devices are half-wave rectified and have common return paths.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
+24VAC (R)
–24VAC (C)
POWER
+
–

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
6 7
Installation
Analog Voltage Inputs
Connect analog voltage inputs using 18AWG two-wire twisted, stranded, shielded wire.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
Analog Inputs
Connect 4 – 20mA analog inputs to the US5182 using 18AWG two-wire twisted, stranded, shielded wire. The inputs can be
two-wire or self-powered.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
Two-wire 4 – 20mA
Unpowered Inputs
Two-wire 4 – 20mA
Powered Inputs
+P (24VDC)
AI1
AI2
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
+
–
+
–
+24V
+24V
+P (24VDC)
AI1
AI2
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
+
–
+
–
0 – 10VDC Input
GND
AV2 (0-10V)
+
–
+24V
12VDC
AV1 (0-5V)
0 – 5VDC Input
+
–
+24V
GND
12VDC
AV2 (0-10V)
AV1 (0-5V)

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
7
Installation
Temperature Inputs
Connect PtRTD 1000Ω temperature inputs using 18AWG two-wire twisted, stranded, shielded wire, maximum 250 ft.
length.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
TEMPERATURE (RTD) INPUTS
Red
Black
Digital Outputs
Connect 24VAC coil relays to these ports. Make connections using 18AWG two-wire twisted, stranded, shielded, or
unshielded wire.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
XFMR

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
8 9
Installation
Analog Outputs
Connect 4 – 20mA, analog output devices using 18 – 22AWG two-wire twisted, stranded, shielded, or unshielded wire.
Connected actuators, motors, or drives must be powered separately from the US5182. If you desire a 2 – 10VDC output,
use an included 500Ω resistor.
NOTE: AO5 and AO6 can be configured as voltage or current outputs via Ubiquity Cloud or TCS Insight software.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
+
–
+
–
*
* = Optional
500ΩResistor
* = Optional 500Ω
Resistor
RS-485 Port
For communication wiring, use 22AWG three-wire twisted, stranded, shielded wire. The communication wiring must be
installed separately from other wiring whether they are power, sensor, or other communication wiring. This will minimize
interference throughout the network.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
A (–)
B (+)
RS-485
REF

2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
9
Installation
USB Port
The USB-C port is used to congure the US5182 via a laptop running TCS Insight conguration software version 2.5.0.7
or later, which can be downloaded from the TCS website.Earlier versions of Insight will not allow you to configure the
US5182.
Connect a USB-A to USB-C cable (NOT a mini-USB or micro-USB cable) between the US5182 and the PC.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
USB
Ethernet Port
The Power Over Ethernet (POE) port can be used to provide power to the device and for LAN communications. Use a Cat 5
or greater cable to make connections.
NOTE: Providing power via the Ethernet port while providing power via the 24VAC Power port will not harm the device.
SERVICE
ECONOMIZER
POWER
OCC
LINK
COM
COM
COM
COM
W1
W2
Y1
Y2
G
DO6
DO7
DO8
GND
AO1
AO2
GND
GND
AO3
AO4
AO5
AO6
A
B
RS-485
REF
ETHERNET
USB
MIXED
AIR
OUTDOOR
AIR
DISCH
HOT
DISCH
RETURN
SPACE
+24VAC (R)
-24VAC (C)
POWER
GND
DI1
DI2
GND
DI3
DI4
GND
DI5
DI6
+P (24VDC)
AI1
AI2
GND
GND
GND
GND
+P (24VDC)
+P (24VDC)
AI3
AI4
AI5
AI6
12VDC
AV1 (0-5V)
AV2 (0-10V)
AIR HANDLING UNIT CONTROLLER
BACK
ENTER
SCROLL
TEMPERATURE (RTD) INPUTS
US5182
tcsbasys.com
ETHERNET
Cat 5 Ethernet Cable
USB Cable
USB-A
USB-C
Other manuals for US5182
2
Table of contents
Other TCS Controllers manuals
Popular Controllers manuals by other brands

Bosch
Bosch ME 200 Installation instructions for contractors

Eaton
Eaton DCF 800 TWIN Installation and Maintenance

Mitsubishi Electric
Mitsubishi Electric Q173CPU Programming manual

Micha Solar
Micha Solar MSR2-30 product manual

GM-Racing
GM-Racing GENIUS RACE 80R instruction manual

Titan Controls
Titan Controls Helios 6 instruction manual