Operation principle
Microprocessor regulator ST-22. 24, 30, 80 is constructed for the purpose of
a central heating boiler regulation – a boiler equipped with a ventilator and a
central heating pump. Its aim is to sustain the setup temperature by means of a
ventilator usage. When the controller works during the ignition function whilst
the boiler temperature is lower than 20oC, then for switching on the controller
(ventilator) press – it will result in lighting an indicator meaning manual
work. The function will be active till the water temperature reaches the setup
temperature. Another press of the button results in deactivation of this function.
After having reached the setup temperature, the controller starts working in the
sustain function. In this function the controller steers blows of the ventilator
varying their frequency according to a client’s setup and the kind of fuel.
Controller functions
Revolutions regulation function (this function can be started by pressing the
“Opcje” button – the indicator “Reg. obrotów” lights up. This function controls the
speed of the ventilator revolutions. The range of regulation is between 1 – 6 or,
depending on the program 1 – 10 (it can be called gear shift). The higher gear,
the quicker rotates the ventilator turbine. 1 is the lowest gear and 6 or 10 is the
highest. The speed of the ventilator rotations depends on the revolutions
regulation function setup. The function prevents from douting of the fire inside
the boiler. The gear shift of the ventilator can be proceeded by the
buttons. After having reached the setup temperature, the boiler starts operation
in the sustain mode. For the proper boiler work the client sets up two parameters
(the ventilator work and the ventilator pause).
Ventilator work function (“Praca przedm.”) is the time (in seconds) in which
the ventilator works. This option is used for setup of the ventilator operation time
during the sustain mode.
Ventilator pause function (“Przerwa przedm.”) is the time (in minutes) of the
ventilator stoppage between its blows.
Functions, that are setup in these two menus are used for boiler operation
regulation during the sustain mode.