
13.2.2 5 psec/c Range; (Continued)
Log 1 c and 9 c dial readings for 10 psec/c and
2 psec/c sweeps. Difference between readings, as
before, ust be 8.00 ± 0.05, for each sweep rate.
13.2.3 Troubleshooting:
13.2.3.1 Excessive Ti ing Error: Exa ine Delaying Sweep display closely,
and see if direct display error corresponds to error indicated by
Helidial. If not, try replacing Delay Pickoff tubes, starting
with V I95, V I96 and V228. If error is confir ed^try tube
replace ent in Delaying Sweep generator, starting with V I90,
V I50, andV180. Ti ing co ponents are probably OK, unless
50 psec or 5 psec/c sweeps cannot be brought in with C190D
and Cl90F respectively.
13.2.3.1.1 Excessive Display Error, 2 usec/c : If 2 psec/c ti ing
is O.K. according to the Delay Ti e Multiplier and
* using the Main Sweep Delayed ode, but the Delaying
Sweep display itself indicates excessive error (± 2 to 4%),
C240 ay have been is-set (Step 11 .4.2.1). Try setting
C240 to correct the delaying sweep display error, then
repeat step 11.4, but without readjusting C240 again, if
possible. A co pro ise adjust ent ay be necessary
to keep both sweeps within display tolerance.
13.2.3.2 Excessive Sweep-Start Delay: Sweep-start delay involves Delay
Pickoff, Trigger-Gate and Main Sweep Gating Multivibrator
circuits as well as Delaying Sweep Trigger and Sweep circuits. It
is only partially co pensated for in the Main Sweep Delayed ode
by the vertical a plifier delay syste . Try changing oldest tubes
in these circuits first. If trigger-pickoff syste in vertical a plifier
is suspect, try triggering Delaying Sweep externally directly fro
180 (A). Recalibrate sections affected by tube changes before
proceeding. Failure of C197 (in V195 grid divider circuit) will
cause both non-linearity of fast sweeps and excessive "sweep
start delay". Failure of co pensating capacitor in any ulti
vibrator grid divider circuit will slow down action and add to delay.
13.3 LINEARITY CHECK: Check linearity at 50 psec/c and 5 psec/c as in 12.5.3.
Maxi u linearity error, 2 s all divisions on Helidial (.02). Log axi u error,
and point at which it occurs for each Sweep rate in Cal Record.
13.3.1 Troubleshooting: Linearity proble s ay be caused in either sweep generator
or delay pickoff circuits. Try replacing V I90, V I50 or V I80 in generator;
V I95, V I96 or V228 in pickoff circuit first. Check C197 (to grid of V I95)
and C l87 (to grid circuit, V150B) for possible open.
13.4 JITTER CHECK: Set up as for Pickoff Drift (Step 12.4.1), with Main Sweep Ti e/C
1000 ti es faster than Delaying Sweep. Adjust Delaying Sweep Stability and Triggering
Level controls for ini u jitter of Main Sweep Delayed display. Jitter at 1.00 c
delay should not exceed 2 ; at 9.00 c , 4 . Log actual jitter if within spec.
Otherwise, proceed with 13.4.1.
13.4.1 Troubleshooting: Try replacing Main Sweep and Delaying Sweep Holdoff tubes
7V54, V I50, V I40); re-check for excessive power-supply ripple. Try replace
ent of Delay Pickoff tubes. Repeat calibration sections involving any tubes
replaced. If tube replace ent fails to correct jitter, check R195, R208 and R209
for excessive noise; try replacing V37, V43, V190, V180, V155, and/or
Delaying Sweep trigger tubes.
(Revised 5-62) C LIBR TION ND M INTEN NCE PROCEDURE 3-61