DN Item Description At Shipment
01 Filter Display Delay Timer
0000: None 0001: 150H
According to Type
0002:2500H 0003: 5000H
0004:10000H
02 Dirty Filter State 0000: Standard 0000: Standard
0001:High Degree of Dirt
03
Central Control Address
(Shown as Group # on
Central Control)
0000: No.1 Unit to 0064: No.64 Unit 0099: Unfixed
0099: Unfixed
04 Specific Indoor Unit
Priority 0000:No
Priority 0001: Priority
05 Fan Control Heating 0001: Default 0009: Fan Off Thermo Off 0001:
* Must have wired remote Change DN-32 to 0001 before use of DN-05
06 Heating SuctionTemp Shift
0000: No Shift 0001: +1*C (+1.8*F)
0002: +2*C (3.6*F)0002: + 2*C (+3.6F) to 0010: +10*C (+18*F)
( Up to +6 Recommended)
OC Preparing Indication
Selection 0000: Preparing indicated 0001: No Indication 0000: Preparing indicated
0D Existence of AUTO Mode
0000: Provided
0001: Not Provided
0001: Not Provided (Automatic selection from connected outdoor unit)
0E FS Box 0000: Only 1 indoor unit on FS 0001: More than 1 indoor unit 0000: Standard
0F Cooling Only 0000: Heat Pump 0000: Heat Pump
0001: Cooling Only (No Display of (AUTO) (HEAT) )
10 Unit Type
0001: 4-Way Air Discharge Cassette 0004: Standard Ducted
Depending on Model
0005: Slim Duct 0006: High Static Ducted
0007: Under Ceiling 0008: High Wall
0014: Compact 4 Way
11 Indoor Unit Capacity 0000: Unfixed 0001 to 0034 According to Capacity
See Page 50 SHRM Quick Reference
12 Line Address 0000: No.1 Unit to 0030: No. 30 Unit 0099: Unfixed
13 Indoor Unit Address 0001: No.1 Unit to 0064: No.64 Unit 0099: Unfixed
14 Group Address 0000: Individual 0001: Header in Group 0099: Unfixed
0002: Follower in Group
19
(Air direction adjustment)
0000: No louver 0001: Swing only
According to Type
0002: (1-Way Air discharge Cassette type, Under Ceiling type)
0003: (2-Way Air discharge Cassette type)
0004: (4-Way Air discharge Cassette type)
1E
Temp Range C/H 0000: 0 degree to 0010: 10 degree 0003: 3 Degree
(Dead Band Heat
Cool/Cool Heat) (Cool / Heat are reversed with +/- (data value) / 2 against the set temperature)
Auto Switch Control Point ( Ts +/- 1.5 )
DN CODES
9
Carrier Confidential and Proprietary Information– Not for Further Distribution