E6581172①
1
1.Introduction
Thank you for purchasing the Toshiba industrial inverter “TOSVERT VF-A7/P7”.
This manual functionally describes the light-load high-speed operation of our "TOSVERT VF-A7/P7" for
industrial use.
2.Function
This parameter provides a function of more raising the speed of motor during light load to improve the
operating efficiency of machine.
It is effectively applicable to elevators and conveyers under constant-torque loads with alternated light and
heavy loads.
3.Related parameter
List of parameters for adjusting light-load high-speed operation
Vector control
Title Communi
cation No Function Adjustment
range
Min. unit (panel/
communication)
Default
setting
Write during
running Speed
control
Torque
control
Position
control
V/f
Constant
0330 Light-load high-speed operation 0〜10 *1 −0 Disabled ●/●− − ●
0331 Light-load high-speed operation
switching lower limit frequency 30.0〜 [Hz] 0.01/0.01 40.0 Enabled ●/●− − ●
0332 Light-load high-speed operation
load waiting time 0.0〜10.0 [s] 0.1/0.1 1.0 Enabled ●/●− − ●
0333 Light-load high-speed operation
load detection time 0.0〜10.0 [s] 0.1/0.1 1.0 Enabled ●/●− − ●
0334 Light-load high-speed operation
heavy load detection time 0.0〜10.0 [s] 0.1/0.1 2.0 Enabled ●/●− − ●
0335 Switching load torque current
during forward run 0〜250 [%] 1 50 Enabled ●/●− − ●
0336 Heavy load torque during
acceleration in forward direction 0〜250 [%] 1 150 Enabled ●/●− − ●
0337 Heavy load torque during fixed
speed in forward direction 0〜250 [%] 1 100 Enabled ●/●− − ●
0338 Switching load torque current
during reverse run 0〜250 [%] 1 50 Enabled ●/●− − ●
0339 Heavy load torque during
acceleration in reverse direction 0〜250 [%] 1 150 Enabled ●/●− − ●
0340 Heavy load torque during fixed
speed in reverse direction 0〜250 [%] 1 100 Enabled ●/●− − ●
0341 Automatic light-load high-speed
operation frequency 30.0〜 [Hz] 0.01/0.01 80.0 Enabled ●/●− − ●
0342 Light-load detection mode *2 0〜255 1/1 0 Disabled ●/●− − ●
Sensorless vector/vector with sensor (●: Valid,−: Invalid)
*1 F330= 0: Disabled light-load high-speed operation
1: User interface (torque current)
2: Continuous automatic mode (torque current)
3: Continuous preset-speed mode (torque current)
4: Enabled-terminal effective automatic mode (torque current)
5: Enabled-terminal effective preset-speed mode (torque current)
6: User interface (torque) *2
7: Continuous automatic mode (torque) *2
8: Continuous preset-speed mode (torque) *2
9: Enabled-terminal effective automatic mode (torque) *2
10: Enabled-terminal effective preset-speed mode (torque) *2
*2 These are not before CPU version V312.