turck PSU67-1P-1S-2L-24150-IOL-F User manual

Instructions for Use
PSU67-1P-1S-2L-24150-IOL-F
Smart switching power
supply in IP65/IP67

Table of Contents
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 2
Table of Contents
1 About these instructions ...................................................................................................................4
1.1 Target groups ...................................................................................................................4
1.2 Explanation of symbols ..................................................................................................4
1.3 Additional documents ....................................................................................................4
1.4 Feedback about these instructions ..............................................................................4
2 Notes on the product .........................................................................................................................5
2.1 Product identification .....................................................................................................5
2.2 Scope of delivery..............................................................................................................5
2.3 Turck service .....................................................................................................................5
3 For your safety.....................................................................................................................................6
3.1 Intended use .....................................................................................................................6
3.2 General safety notes........................................................................................................6
4 Product description ............................................................................................................................7
4.1 Device overview...............................................................................................................7
4.1.1 Block diagram....................................................................................................................................7
4.1.2 Operating elements.........................................................................................................................8
4.1.3 Display elements ..............................................................................................................................8
4.2 Properties and features ..................................................................................................8
4.3 Functional principle ........................................................................................................8
4.4 Functions and operating modes...................................................................................8
4.4.1 User interface.....................................................................................................................................8
4.4.2 AC voltage input...............................................................................................................................8
4.4.3 DC voltage input...............................................................................................................................9
4.4.4 DC voltage outputs..........................................................................................................................9
4.4.5 IO-Link interface............................................................................................................................. 11
5 Installing ............................................................................................................................................ 12
5.1 Special installation instructions: mounting altitude ............................................. 12
6 Connecting ........................................................................................................................................ 13
6.1 Connecting the AC or DC input voltage ................................................................... 13
6.2 Connecting the DC output voltage side................................................................... 14
6.3 Connecting the device to IO-Link .............................................................................. 14
7 Commissioning................................................................................................................................. 15
8 Setting................................................................................................................................................ 16
8.1 Setting the device via LED bar and pushbuttons ................................................... 16
8.1.1 Configuration mode..................................................................................................................... 16
8.1.2 Switching outputs on or off....................................................................................................... 16
8.1.3 Resetting outputs.......................................................................................................................... 16
8.1.4 Activating and deactivating the button lock ...................................................................... 17
8.2 Setting the device via IO-Link..................................................................................... 18
8.2.1 Direct Parameter Page 1 ............................................................................................................. 18
8.2.2 Identification................................................................................................................................... 18
8.2.3 Index 0x02: System commands (according to IO-Link specification)......................... 19
8.2.4 Index 0x0C: Device Access Locks............................................................................................. 19
8.2.5 Parameters....................................................................................................................................... 20

Table of Contents
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 3
9 Operating........................................................................................................................................... 24
9.1 Monitoring mode.......................................................................................................... 24
9.2 LED displays ................................................................................................................... 25
9.3 Process data (cyclic IO-Link data) .............................................................................. 27
9.4 Diagnostic and status messages (acyclic IO-Link data) ......................................... 28
9.5 IO-Link Events................................................................................................................ 31
9.6 IO-Link error codes ....................................................................................................... 32
10 Maintenance ..................................................................................................................................... 33
11 Repair ................................................................................................................................................. 33
11.1 Returning devices ......................................................................................................... 33
12 Disposal.............................................................................................................................................. 33
13 Technical data................................................................................................................................... 34
13.1 AC input .......................................................................................................................... 34
13.2 DC input.......................................................................................................................... 36
13.3 DC output ....................................................................................................................... 36
13.4 Efficiency and power losses ........................................................................................ 37
13.5 IO-Link interface............................................................................................................ 38
13.6 General technical data ................................................................................................. 38
14 Turck branches — contact data .................................................................................................... 42

About these instructions
Feedback about these instructions
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 4
1 About these instructions
These instructions describe the setup, functions and use of the product and help you to oper-
ate the product according to its intended purpose. Read these instructions carefully before us-
ing the product. This will prevent the risk of personal injury and damage to property. Keep
these instructions safe during the service life of the product. If the product is passed on, pass on
these instructions as well.
1.1 Target groups
These instructions are aimed at qualified personal and must be carefully read by anyone
mounting, commissioning, operating, maintaining, dismantling or disposing of the device.
1.2 Explanation of symbols
The following symbols are used in these instructions:
DANGER
DANGER indicates a hazardous situation with a high level of risk, which, if not
avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation with a medium level of risk, which, if not
avoided, will result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation with a medium level of risk, which, if not
avoided, will result in moderate or minor injury.
NOTICE
CAUTION indicates a situation which, if not avoided, may cause damage to property.
NOTE
NOTE indicates tips, recommendations and important information about special ac-
tion steps and issues. The notes simplify your work and help you to avoid additional
work.
uMANDATORY ACTION
This symbol denotes actions that the user must carry out.
aRESULT OF ACTION
This symbol denotes the relevant results of an action.
1.3 Additional documents
Besides this document, the following material can be found on the Internet at www.turck.com:
nData sheet
nEU declarations of conformity (current version)
nQuick Start Guide
nApprovals
1.4 Feedback about these instructions
We make every effort to ensure that these instructions are as informative and as clear as pos-
sible. If you have any suggestions for improving the design or if some information is missing in
the document, please send your suggestions to [email protected].

Notes on the product
Turck service
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 5
2 Notes on the product
2.1 Product identification
These instructions apply to the following IP65/IP67 power supply series PSU67:
nPSU67-1P-1S-2L-24150-IOL-F (ID 100028305)
2.2 Scope of delivery
The delivery consists of the following:
nIP65/IP67 power supply
nQuick Start Guide
2.3 Turck service
Turck supports you in your projects – from the initial analysis right through to the commission-
ing of your application. The Turck product database at www.turck.com offers you several soft-
ware tools for programming, configuring or commissioning, as well as data sheets and CAD
files in many export formats.
The contact data for Turck branches is provided at [}42].

For your safety
General safety notes
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 6
3 For your safety
The product is designed according to state of the art technology. Residual hazards, however,
still exist. Observe the following safety instructions and warnings in order to prevent danger to
persons and property. Turck accepts no liability for damage caused by failure to observe these
safety instructions.
3.1 Intended use
The power supply unit PSU67-1P-1S-2L-24150-IOL-F is a stand-alone power supply for 1-phase
mains systems for indoor use with IO-Link interface. The device is designed with IP65/IP67 pro-
tection and is suitable for use directly on the machine. The protection class can only be guaran-
teed if all mating connectors are firmly connected.
The switching power supply converts an AC input voltage of 100…240 VAC into a 24 VDC out-
put voltage and makes it available at four current-limited outputs. The four unit's outputs are
protected by internal electronic fuses (eFuse). The unit is suitable for use at altitudes up to 5000
m (16400 ft). Above 2000m (6560ft), the output current and overvoltage category must be re-
duced.
The device must only be used as described in these instructions. Any other use is not in accord-
ance with the intended use. Turck accepts no liability for any resulting damage.
3.2 General safety notes
nThe device must only be fitted, installed, operated, parameterized and maintained by trained
and qualified personnel.
nOnly use the device in compliance with the applicable national and international regula-
tions, standards and laws.
nThe device meets the EMC requirements for the industrial areas. When used in residential
areas, take measures to prevent radio frequency interference.
nThe device is class of protection I equipment according to IEC 61140.
nThe device is designed for pollution degree 3 areas in controlled environments.
nOnly use the device with additional protective devices in the area of personal and machine
protection.
nOperate the device exclusively within the technical specifications.
nDo not connect the negative potential of any output externally to PE.
nDo not use without a proper PE (Protective Earth) connection.

Product description
Device overview
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 7
4 Product description
The 1-phase switching power supply PSU67-1P-1S-2L-24250-IOL-F is designed in IP65/IP67. An
S-coded M12 connector (XD1) is available for connecting the input voltage. The output voltage
side is connected via two L-coded M12 sockets (XD2 and XD3). The device has four internal
eFuses to protect the output voltage.
The IO-Link interface is designed as an A-coded M12 connector (X0). Configuration and dia-
gnostics are performed either via directly on the device via the operator interface (LEDs and
buttons) or via IO-Link.
Mating connectors
nInput voltage (XD1): M12 female connector, S-coded, 3-pin
nOutput voltage (XD2, XD3): M12 male connector, L-coded, 5-pin
nIO-Link (X0): M12 female connector, A-coded, 5-pin
4.1 Device overview
mm [Inch]
M12 × 1
M12 × 1
M12 × 1
M12 × 1
163.7 [6.45]
168.2 [6.62]
182 [7.17] 59 [2.32]
56.3 [2.22]
195.4
[7.69]
183
[7.21]
107
[4.21]
38
[1.50]
20
[0.79]
4.5
[0.18]
Fig.1: Dimensions
4.1.1 Block diagram
XD1
Input L
N
PE
1
3
PE
Fuse
Filter
Recti er
Inrush Current
Limiter
PFC
Power
Converter
Temperature
Shutdown
Output
OVP
Output
Power
Manager IO-Link
Control
LED bar
Status
Set
V+
V-
Data
X0
3
1
4
+
-
+
-
+
-
+
-
XD2
Out 1
Output
1
3
FE
4
2
XD3
Out 3
1
3
FE
4
2
Out 2
Out 4
+
-
Switchable
Output
Fig.2: Block diagram

Product description
Functions and operating modes
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 8
4.1.2 Operating elements
The device has the following operating elements:
nButtons for requesting the device settings and for configuring the device [Voltage Set] and
[Ó] [Ô].
nButtons for switching the outputs [OUT1…OUT4] on and off.
4.1.3 Display elements
The device has an LED bar (monitoring mode [}24]) to display:
nTotal output power (in %)
nChannel LEDs (OUT1…OUT4)
nOperating states (status LED)
4.2 Properties and features
nDegree of protection IP65/IP67
n1-phase AC input, M12, S-coded
n24 VDC output voltage, settable up to 28 VDC
nfour current limited outputs, 2 × M12, L-coded
nFuse protection by four separate eFuses, adjustable up to 12 A
nIO-Link interface
nWide temperature range
nLED status display
nHigh efficiency, > 95 %
nOperator interface (LEDs and buttons)
4.3 Functional principle
The device converts an AC input voltage of 100…240 VAC into a 24 VDC output voltage and
makes it available at four current-limited outputs. The unit's outputs are protected by internal
electronic fuses (eFuse).
4.4 Functions and operating modes
4.4.1 User interface
Output level control
The buttons [Voltage Set] and [Ó] [Ô] are used to configure output voltage and trip current in
the configuration mode [}16]. After commissioning the power supply, the device is in monit-
oring mode (normal operation) for monitoring the output power.
Output control
The output LEDs (OUT1…OUT4) indicate the operating states of the corresponding outputs.
The respective output is switched on and off via the associated button.
4.4.2 AC voltage input
The voltage input is designed for a 1-phase AC voltage of 100…240 VAC (nominal range).
Inrush current limitation
The power supply is equipped with an active inrush current limiting circuit, which limits the in-
put inrush current to a very low value after switching on. The inrush current is usually lower
than the permanent input current.

Product description
Functions and operating modes
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 9
AC, 100 V AC, 120 V AC, 230 V
Inrush current Typ. 2.18 Apeak Typ. 2.6 Apeak Typ. 6 Apeak
The charging current in the EMI suppression capacitors is neglected in the first microseconds
after switch-on.
250 ms/DIVOutput voltage
Input voltage
Input current 5 A/DIV
Fig.3: Typical switch-on behavior at nominal load and 25 °C ambient temperature
Input protection
The unit is designed, tested and approved for branch circuits up to 32 A (IEC) and 20 A (UL)
without additional protective device.
If an external fuse is used, use B or C characteristic circuit breakers with at least 6 A to avoid a
nuisance tripping of the circuit breaker.
4.4.3 DC voltage input
The DC voltage input is designed for a DC voltage range of 110...300 VDC (nominal range) for
use with a battery or similar DC power source.
4.4.4 DC voltage outputs
The DC voltage outputs OUT1…OUT4 provide a stabilized and galvanically isolated 24 VDC
output voltage (PELV/ES1). The negative potential of the outputs is permanently connected to
PE in the device. The outputs are electronically protected against open-circuit, overload and
short-circuit and can supply any type of loads, including unlimited inductive and capacitive
loads.
When connecting capacitors with capacitance >20 mF to an output, this output may be
switched off after switching on the device or the output or connecting the load. All outputs are
individually current limited. In the event of an overload, the individual output switches off and
must be reset manually via the associated button or via IO-Link. The output can be reset at the
earliest 5 s after it has been switched off.
The outputs of the device are switched on in the delivery state. The outputs are not switched
off in a safety-related manner.
The sum of the configured output power of all outputs can exceed the total output power. In
this case, the outputs switch off one after the other in reverse order (OUT4, OUT 3, …) until the
total output power is within the permissible range again The lower output in each case remains
switched on to prevent voltage dips and to output current continuously.

Product description
Functions and operating modes
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 10
Power budget
exceeded
Lowest prio
CH4
CH3
CH2
Total output
power
High prio
CH1
without
load
Fig.4: Tripping of the channel with the lowest priority when the total output power is exceeded
The outputs then start automatically one after the other at intervals of 150 ms in the sequence
OUT1…OUT4.
50 ms/DIV
CH4
CH3
CH2
Turn
on
CH1
Start-up
delay 2 s
Fig.5: Sequential start of outputs
Hold-up time
The hold-up time is the time during which a power supply’s output voltage remains within spe-
cification following the loss of input power. The hold-up time is output load dependent. At no
load, the hold-up time can be up to several seconds. The status LED is on during this time.
100 VAC, 120 VAC, 230 VAC Output load
Hold-up time Typ. 75 ms
Min. 56 ms
150 W
Typ. 44 ms
Min. 29 ms
300 W

Product description
Functions and operating modes
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 11
UIn/VAC
t/ms
0
20
40
60
80
85 100 150 200 250 264
24 V, 150 W
typ.
24 V, 150 W
min.
24 V, 300 W
typ.
24 V, 300 W
min.
Fig.6: Hold-up time vs. input voltage
-5 %
L1
Output
voltage
Hold-up time
Input
voltage
Fig.7: Shutdown behavior
Support of short-term peak loads
The device designed to support loads with a higher short-term power demand (peak loads).
Temporary peak loads cause an increased power demand for a short time, which is controlled
internally in the device by an output power manager. If the average load exceeds the sum of all
output powers, the output voltage collapses.
To avoid a collapse of the output voltage, observe the following rules:
nThe power demand of the short-time load pulse must be below 200 % of the nominal output
power.
nThe duration of the load pulse must be shorter than the max. permissible duration for the
additional power.
nThe average power should be lower than the rated output power.
nThe RMS output current must be lower than the specified continuous output current. Con-
tinuous increased RMS current may cause thermal shutdown of the device.
4.4.5 IO-Link interface
The devices (PSU67-…-IOL) have an IO-Link interface V1.1 for connection to IO-Link masters.
The device can be parameterized via IO-Link using the associated IODD. In addition, device-in-
ternal measurement data and diagnostics are made available via IO-Link. The IODDs are avail-
able for download free of charge at www.turck.com.
The devices can also be operated without active IO-Link communication. Settings made via IO-
Link during commissioning for example, are stored in the EEPROM of the device and are avail-
able even if the IO-Link communication fails.

Installing
Special installation instructions: mounting altitude
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 12
5 Installing
The housing of the device ensure IP65 and IP67 protection when all mating connectors are
firmly connected.
CAUTION
Sharp edges on the back of the device
Risk of injury
Mount the devices on a sufficiently large, even surface so that all sharp edges
are covered.
Mount the device vertically with the connection level facing downwards on a flat surface
using two M4 screws each at the upper and lower mounting holes.
Other mounting orientations: Reduce the output current, s. „General technical data”.
Do not obstruct airflow. Do not cover ventilation fins.
Observe the minimum installation clearances: 50 mm on top and bottom, 10 mm on the
front and 10 mm left and right side.
Device cooling
The device uses convection cooling. An external fan is not necessary.
5.1 Special installation instructions: mounting altitude
The device is generally designed for altitudes up to 5000 m (16400 ft). The devices may only be
used as described in these instructions. Above 2000 m (6560 ft), the output current and over-
voltage category must be reduced.
When using the device in TN, TT and IT networks the following applies:
nTN, TT mains systems with earthed neutral and IT star mains systems with insulation monit-
oring: Use in zones of overvoltage category III up to an altitude of 2000 m (6560 ft), use in
zones of overvoltage category II up to an altitude of 5000 m (16400 ft)
nTN, TT, IT delta mains systems or IT star mains systems without insulation monitoring: Use in
zones of overvoltage category II up to 2000 m (6560 ft)

Connecting
Connecting the AC or DC input voltage
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 13
6 Connecting
6.1 Connecting the AC or DC input voltage
The device has a 3-pin, S-coded M12 connector for the connection of the AC or respectively the
DC input voltage. The maximum tightening torque is 0.8 Nm.
1 = L
3 = N
PE = PE
3
PE
1
Fig.8: Pin assignment, M12 connector AC or DC input voltage (XD1)
Connecting the AC input voltage
Connect the AC input voltage to the device according to the pin assignment.
Connecting the DC input voltage
Connect the battery or a similar DC power source to the device according to the pin as-
signment.
PSU67
Load
Battery
DC
AC
L
N
+
+
-
-
PE
Fig.9: DC input
Connect the PE terminal to a ground wire or to the machine ground.
NOTICE
Incorrect choice of DC voltage source
Malfunction or damage to the device
Do not use a DC link of a frequency converter as a DC source.

Connecting
Connecting the device to IO-Link
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 14
6.2 Connecting the DC output voltage side
The device has two 5-pin, L-coded M12 connectors to connect the DC output side. The max-
imum tightening torque is 0.6 Nm.
Connect the DC output side according to the pin assignment shown below.
v
3
1
2
4
5
1 = 24 VDC (V1)
2 = GND (V2)
3 = GND (V1)
4 = 24 VDC (V2)
5 = PE
Fig.10: Pin assignment, M12 connector, DC output voltage (XD2, XD3)
Notes on connecting loads
Only connect return voltages < 35 V from a load to the outputs.
Do not connect outputs or devices in parallel.
6.3 Connecting the device to IO-Link
The device has a 5-pin, A-coded M12 connector for the connection to IO-Link. The maximum
tightening torque is 0.6 Nm.
Connect the device to IO-Link according to the pin assignment shown below.
2
35
4
11 = 24 VDC
2 = n.c.
3 = GND
4 = C/Q (IO-Link)
5 = n.c.
Fig.11: Pin assignment, IO-Link interface (X0)

Commissioning
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 15
7 Commissioning
After connecting the wires and by switching on the AC input voltage, the device automatically
goes into operation.

Setting
Setting the device via LED bar and pushbuttons
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 16
8 Setting
8.1 Setting the device via LED bar and pushbuttons
The device has an LED bar and three buttons for monitoring output power and channel output
current (monitoring mode [}24]) and for configuring output voltage and trip current. In con-
figuration mode, the output voltage and trigger current can be set to monitor the current of
the outputs OUT1…OUT4.
In addition, a button lock can be set up and the outputs of the device can be switched on or off
independently.
8.1.1 Configuration mode
Output voltage setting
The output voltage is set for both outputs.
Press [Voltage Set] for 3 s.
aThe device changes to the start mode "Set output voltage", all LEDs flash briefly. The ac-
tual setting is indicated by a green LED on the LED bar.
Press [Ó] and [Ô] buttons to set the value for the output voltage.
aThe set value is displayed via the LED bar. All orange LEDs are off. The setting becomes
effective immediately.
Without further pressing the buttons, the LED bar will return from any other mode to normal
mode after 15 s.
Setting the tripping current
The tripping current is set separately for the outputs OUT1…OUT4.
Press and hold the [Voltage Set] button for 3 s to switch to configuration mode.
aAll LEDs flash briefly and the actual setting is indicated by a green LED on the LED bar
Press the [Voltage Set] key 1 × to select the output for which the trigger current is to be
set. The orange channel LED (OUT1…OUT4) indicates for which output the trigger cur-
rent is set.
Press [Ó] and [Ô] buttons to set the setpoint (1…12 A) (Example: 20 %-LED = 3 A).
aThe setting becomes effective immediately.
Without further pressing the buttons, the LED bar will return from any other mode to normal
mode after 15 s.
8.1.2 Switching outputs on or off
The outputs can be switched on or off independently of each other. In the delivery state, all
outputs of the device are switched off.
Press and hold the button on the output channel (OUT1…OUT4) for 1 s to switch a chan-
nel on or off manually.
8.1.3 Resetting outputs
In case of an error at the output:
Press and hold the button on the output (OUT1…OUT4) for longer than 1 s to reset the
output.

Setting
Setting the device via LED bar and pushbuttons
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 17
8.1.4 Activating and deactivating the button lock
Activate button lock
Hold [Ó] and [Ô] buttons simultaneously for 3 s.
aAll LEDs flash for 5 s to indicate that the key lock status has changed. The display returns
to normal operation.
Check button lock
Press and hold the [Voltage Set] key for 3 s.
aIf the button lock is activated, all LEDs flicker for 5 s.
Remove button lock
Hold [Ó] and [Ô] buttons simultaneously for 3 s.
aAll LEDs flash for 5 s to indicate that the key lock status has changed. The display returns
to normal operation.

Setting
Setting the device via IO-Link
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 18
8.2 Setting the device via IO-Link
8.2.1 Direct Parameter Page 1
ISDU
Index
Hex.
(dec.)
Sub
index
Object name Access
Read (R)
Write (W)
Length in
byte
Meaning
0x00
(0)
Direct Parameter Page 1 R 16
0x02 Master cycle time R 1
0x03 Min. cycle time R 1
0x04 M sequence capability R 1
0x05 IO-Link version ID R 1 17
0x06 Process data input length R 1
0x07 Process data output length R 1
0x08 Vendor ID R 2 ID for Turck:
0x013D
0x09
0x0A Device ID R 3 E. g.: PSU67-3P-1S-2L-24250-IOL-F:
2228224 (0x220000)
0x0B
0x0C
0x10 Standard command R/W 1 129: application reset
130: restore factory settings
8.2.2 Identification
ISDU
Index
Hex.
(dec.)
Object name Access
Read (R)
Write (W)
Length in
byte
Meaning
0x10
(16)
Vendor name R 16 Turck
0x11
(17)
Vendor text R 32 www.turck.com
0x12
(18)
Product name R 32 PSU67-…
0x13
(19)
Product ID R 16 ID of the device
0x14
(20)
Product text R 32 IP67 Power Supply
0x15
(21)
Serial number R 16 Sequential serial number
0x16
(22)
Hardware revision R 8 Hardware revision of the device, e. g. V1.0
0x17
(23)
Firmware revision R/W 16 Firmware revision of the device, e. g. V1.0.7.0
0x18
(24)
Application Specific Tag R/W 32 Default "***"
Field for customer or application specific data

Setting
Setting the device via IO-Link
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 19
ISDU
Index
Hex.
(dec.)
Object name Access
Read (R)
Write (W)
Length in
byte
Meaning
0x19
(36)
Function Tag R/W 32 Default "***"
Field for the application specific device func-
tion
0x1A
(26)
Location Tag R/W 32 Default "***"
Field for the application-specific installation
location of the device
8.2.3 Index 0x02: System commands (according to IO-Link specification)
Command
129 Application reset
130 Restore factory settings
8.2.4 Index 0x0C: Device Access Locks
Default values are shown in bold.
Sub index
Hex. (dec.)
Object name Bit offset Data
type
Meaning
1 Parameter (write) access lock 0 BOOL Not implemented
2 Data storage lock 1 0: not activated (default)
1: activated
3 Local parameterization lock 2 Not implemented
4 Local user interface lock 3 Not implemented

Setting
Setting the device via IO-Link
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com V01.00 | 2023/06 | 20
8.2.5 Parameters
Parameter overview
Index
Hex.
(dec.)
Sub
index
Parameter name Data type Length
in bit
Unit Access
Read (R)
Write (W)
0x65
(101)
0 Standby BOOL 8 RW
0x67
(103)
0 Configuration setting UINT8 8 RW
0x68
(104)
0 PSU total output current pre-alarm level UINT16 16 2-8 A/bit RW
0x69
(105)
0 Output Voltage Setpoint UINT16 16 2-8 V/Bit RW
0x6A
(106)
0 eFuses channel on/off Set of
BOOL
8 - RW
0x6C
(108)
0 eFuse trip value Ch1 UINT16 16 2-8 A/bit RW
1 …
2
3 eFuse trip value CH4
0x6D
(109)
0 eFuses pre-alarm level Ch1 UINT8 8 2-7/Bit
(0.78 %/ Bit)
RW
1 …
2
3 eFuses pre-alarm level Ch4
Standby — index 0x65 (101)
This parameter can be used to actively set the device to the ”standby” state.
Format Length
BOOL 1 bit
Default values are shown in bold.
Value Meaning
0 False PSU normal operation
1 True PSU standby
Power supply in standby mode, all outputs are switched off
Table of contents
Other turck Power Supply manuals

turck
turck PSU67-3P-1H2-1H0-24250 User manual

turck
turck PSU67-3P-1S-2L-24250-F User manual

turck
turck PSU67-3P-1H2-1H0-24250 User manual

turck
turck PSU67-3P-1S-2L-24250-IOL-F User manual

turck
turck PSM24-N.1 User manual

turck
turck IM82-24-5,0-3P User manual

turck
turck PSU67-3P-1S-2L-24250-IOL-F User manual

turck
turck PSD24EX User manual

turck
turck IM82-24-10-3P User manual

turck
turck PSU67-1P-1M-2M5-24150-IOL-F User manual