Early Suppression Fast Response
Pendent Sprinklers ,
Pulsar™ ESFR-25™, K=25.2
GENERAL DESCRIPTION
The Star Pulsar ESFR-25 Pendent Sprinklers (Ref. Figure
1) are “Early Suppression Fast Response Sprinklers” hav-
ing a nominal K-factor of 25.2. They are suppression
mode sprinklers, and their use is especially advanta-
geous as a means of eliminating the use of in-rack sprin-
klers, when protecting high-piled storage.
The Pulsar ESFR-25 is primarily designed for use with
storage heights of most encapsulated or non-encapsu-
lated common materials including cartoned unexpanded
plastics of up to 40 ft. (12,2 m) and with ceiling heights of
up to 45 ft. (13,7 m). In addition, the protection of some
storage arrangements of roll paper and rubber tires can
be considered as well.
The Pulsar ESFR-25 provides the system designer with
hydraulic and sprinkler placement options not presently
available to the traditional ESFR sprinklers having a nomi-
nal K-Factor of 14.0. In particular, the Pulsar ESFR-25
has been designed to operate at substantially lower end
head pressures, as compared to ESFR sprinklers having
a nominal K-Factor of 14.0. This feature offers flexibility
when sizing the system piping, as well as possibly reduc-
ing or eliminating the need for a system fire pump. Also,
the Pulsar ESFR-25 permits use of a maximum deflector-
to ceiling distance of 18 inches (460 mm) versus 14
inches (360 mm); and, a storage arrangement of up to 40
ft. (12,2 m) with a ceiling height of up to 45 ft. (13,7 m)
does not require in-rack sprinklers as do ESFR sprinklers
having a nominal K-Factor of 14.0.
The Pulsar ESFR-25 Pendent Sprinkler is also Listed by
Underwriters Laboratories Inc. (UL) and by UL for use in
Canada (C-UL) as a “Specific Application Early Suppres-
sion Fast Response Sprinkler” as indicated under the UL
and C-UL Specific Application Design Criteria section.
The specific application listing provides for reduced pres-
sure design for the protection of certain commodities.
Applications for the Pulsar ESFR-25 Sprinklers are ex-
panding beyond the current recognized installation stand-
ards. For information regarding research fire tests which
may be acceptable to an Authority Having Jurisdiction
(e.g., flammable liquids, exposed plastics, and aerosols),
please contact the Technical Services Department.
WARNINGS
The Pulsar ESFR-25 Sprinklers described herein must be
installed and maintained in compliance with this docu-
ment, as well as with the applicable standards of the Na-
tional Fire Protection Association, in addition to the stand-
ards of any other authorities having jurisdiction (e.g.,
Factory Mutual Research Corporation). Failure to do so
may impair the integrity of these devices.
The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.
OPERATION
The fusible link (heat collector) assembly is comprised of
two link halves which are joined together by a thin layer
of solder. When the rated temperature is reached, the sol-
der melts and the two link halves separate, which then al-
lows the sprinkler to activate and flow water.
SIN S8010
Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500 3-01
1-4.1.11
TYCO FIRE PRODUCTS
OBSOLETE
TECHNICAL DATA
Approvals
UL and C-UL Listed. FM Approved.
(Listings and approvals only apply to the service condi-
tions in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1 inch NPT or ISO 7-R1
Discharge Coefficient
K = 25.2 GPM/psi1/2 (362,9 LPM/bar1/2)
Temperature Ratings
165°F/74°C or 214°F/101°C
Finish
Natural Brass
Physical Characteristics (Ref. Figure 1)
The Pulsar ESFR-25 utilizes a dezincification resistant
bronze alloy frame. The strut and hook are monel; the but-
ton, deflector, and compression screw are bronze. The
gasketed spring plate consists of a beryllium nickel disc
spring that is sealed on both its inside and outside edges
with a Teflon

gasket, and the two halves of the fusible
link assembly are nickel.
Patents
U.S.A. Patent Number 4,580,729, 5,829,532, and
6,059,044 are applicable to the Pulsar ESFR-25. Other
patents are pending.
DESIGN CRITERIA
ULandC-ULListingCriteria
The Pulsar ESFR-25 (SIN S8010) Sprinklers are UL and
C-UL Listed as “Early Suppression Fast Response Sprin-
klers” for installation per NFPA 13 or other applicable
NFPA standards.
UL and C-UL Specific Application Listing Criteria
The Pulsar ESFR-25 (SIN S8010) Sprinklers are UL and
C-UL Listed as “Specific Application Early Suppression
Fast Response Sprinklers” for use in in accordance with
NFPA 13 to protect single-, double-, and multiple row rack
storage and palletized and solid pile storage (no open
containers or solid shelves) of Class I, II, III, and IV com-
modities encapsulated or unencapsulated and cartoned
Group A unexpanded plastics when installed with the fol-
lowing storage and ceiling heights and minimum design
pressures:
Maximum Maximum Minimum
Storage Ceiling Flowing
Height, Height, Pressure,
Ft. (m) Ft. (m) psi (bar)
40 (12,2) 45 (13,7) 40 (2,7)
35 (10,7) 40 (12,2) 25 (1,7)
30(9,1) 35(10,7) 20(1,4)
25 (7,6) 30 (9,1) 15 (1,0)
When applying the specific application listing criteria, the
Pulsar ESFR-25 Sprinklers should be installed using the
same installation obstruction and construction criteria, as
well as deflector-to ceiling distances, as is applicable for
Early Suppression Fast Response Sprinklers having a
nominal K-Factor of 25.2 per NFPA 13.
FM Approval Criteria
The Pulsar ESFR-25 (SIN S8010) Sprinklers are FM Ap-
proved as “Early Suppression Fast Response Sprinklers”
for installation per the applicable FM Loss Prevention
Data Sheets.
STAR SPRINKLER
Page 2 1-4.1.11
FIGURE 1
PULSAR ESFR-25 PENDENT SPRINKLER
1" NPT
(BOTH SIDES)
WRENCH FLAT
(96.8 mm)
3-13/16"
9/16" (14.3 mm)
NOMINAL MAKE-IN
2" (50.8 mm)
TEMPERATURE
RATING
ASSEMBLY
LINK
HOOK

DuPont Registered Trademark
OBSOLETE
INSTALLATION
The Pulsar ESFR-25 Pendent Sprinklers are to be in-
stalled in accordance with the following instructions:
NOTE
Damage to the fusible Link Assembly during installation
can be avoided by handling the sprinkler by the frame
arms only (i.e., do not apply pressure to the fusible Link
Assembly), and by using the appropriate sprinkler
wrench. Damaged sprinklers must be replaced.
A leak tight 1 inch NPT sprinkler joint should be obtained
withatorqueof20to30ft.lbs.(26,8to40,2Nm).Higher
levels of torque may distort the sprinkler inlet with conse-
quent leakage or impairment of the sprinkler.
1. The Pulsar ESFR-25 Sprinkler must be installed in the
pendent position.
2. With pipe thread sealant applied, hand tighten the sprinkler
into the sprinkler fitting. Do not apply pressure to the Link
Assembly, and handle the Pulsar ESFR-25 Sprinkler only
by the Frame arms.
3. Wrench tighten the Pulsar ESFR-25 Sprinkler using only
the W-Type 1 Sprinkler Wrench (Ref. Figure 2) and by fully
engaging (seating) the wrench with the sprinkler wrench
flats.
4. After installation, inspect the Link Assembly of each Pulsar
ESFR-25 Sprinkler for damage. In particular, verify that the
Link Assembly and Hook are positioned as illustrated in
Figure 1, and that the Link Assembly has not been bent,
creased, or forced out of its normal position in any way.
Damaged sprinklers must be replaced.
CARE AND MAINTENANCE
The Pulsar ESFR-25 must be maintained and serviced in
accordance with the following instructions:
NOTE
Before closing a fire protection system main control valve
for maintenance work on the fire protection system which
it controls, permission to shut down the affected fire pro-
tection systems must be obtained from the proper authori-
ties and all personnel who may be affected by this action
must be notified.
Sprinklers which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.
Automatic sprinklers must never be shipped or stored
where their temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified or over-heated
sprinklers must be replaced.
Care must be exercised to avoid damage - before, dur-
ing, and after installation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or the like, must be
replaced.
The owner is responsible for the inspection, testing, and
maintainance of their fire protection system and devices
in compliance with this document, as well as with the ap-
plicable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.
It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.
LIMITED WARRANTY
Products manufactured by Tyco Fire Products are war-
ranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty
is given for products or components manufactured by
companies not affiliated by ownership with Tyco Fire Prod-
ucts or for products and components which have been
subject to misuse, improper installation, corrosion, or
which have not been installed, maintained, modified or re-
paired in accordance with applicable Standards of the Na-
tional Fire Protection Association, and/or the standards of
any other Authorities Having Jurisdiction. Materials found
by Tyco Fire Products to be defective shall be either re-
paired or replaced, at Tyco Fire Products’ sole option.
Tyco Fire Poducts neither assumes, nor authorizes any
person to assume for it, any other obligation in connec-
tion with the sale of products or parts of products. Tyco
Fire Products shall not be responsible for sprinkler sys-
tem design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI-
ABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UN-
DER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR IM-
PLIED, INCLUDING WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE.
STAR SPRINKLER
1-4.1.11 Page 3
FIGURE 2
W-TYPE 1 SPRINKLER WRENCH
"FITTING SIDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH
OBSOLETE
ORDERING PROCEDURE
Please Specify:
Pulsar ESFR-25 Pendent Sprinkler (#8010)
W-Type 1 Sprinkler Wrench (#2949)
Refer to Price List for for complete listing of Part Num-
bers with respect to temperature ratings, etc.
STAR SPRINKLER
Page 4 1-4.1.11
7071 S. 13th Street • Suite 103
Oak Creek, WI 53154
www.starsprinkler.com
PRINTED IN U.S.A. 3-01
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product CENTRAL ESLO-20 GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESLO-20 GB User manual

Tyco Fire Product TY-QRF User manual

Tyco Fire Product

Tyco Fire Product TY-QRF User manual

Tyco Fire Product Star Pulsar S160 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S160 User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S176 User manual

Tyco Fire Product CENTRAL S170 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL S170 User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product SIN S3230 User manual

Tyco Fire Product

Tyco Fire Product SIN S3230 User manual

Tyco Fire Product Gem F890 User manual

Tyco Fire Product

Tyco Fire Product Gem F890 User manual

Tyco Fire Product CENTRAL Omega HEC-12EC PRO User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega HEC-12EC PRO User manual

Tyco Fire Product CENTRAL BV4-QREC User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV4-QREC User manual

Tyco Fire Product Star TFP1 User manual

Tyco Fire Product

Tyco Fire Product Star TFP1 User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product TFR MAX User manual

Tyco Fire Product

Tyco Fire Product TFR MAX User manual

Tyco Fire Product Gem F978 User manual

Tyco Fire Product

Tyco Fire Product Gem F978 User manual

Tyco Fire Product Star SuperNova S120 User manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S120 User manual

Tyco Fire Product SIN S3244 User manual

Tyco Fire Product

Tyco Fire Product SIN S3244 User manual

Tyco Fire Product CENTRAL Omega HEC-12 PRO Prohibitor User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega HEC-12 PRO Prohibitor User manual

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product Gem F685 User manual

Tyco Fire Product

Tyco Fire Product Gem F685 User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Tyco Fire Product CENTRAL ESFR-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-1 User manual

Popular Irrigation System manuals by other brands

Reliable F3QR80 Series manual

Reliable

Reliable F3QR80 Series manual

Toro 570Z Specifications

Toro

Toro 570Z Specifications

Toro TR50XT Series Instruction guide

Toro

Toro TR50XT Series Instruction guide

Autopot 80 Pot System Set-up guidelines

Autopot

Autopot 80 Pot System Set-up guidelines

K-Rain ProSport 14003 Setting instructions

K-Rain

K-Rain ProSport 14003 Setting instructions

sunjoe AQUAJOE AJ-IST39BM manual

sunjoe

sunjoe AQUAJOE AJ-IST39BM manual

Tyco TY-B Series quick start guide

Tyco

Tyco TY-B Series quick start guide

Reliable JL-17 quick start guide

Reliable

Reliable JL-17 quick start guide

Gardena AquaContour automatic 1559 operating instructions

Gardena

Gardena AquaContour automatic 1559 operating instructions

Johnson Controls tyco DS-1 Series manual

Johnson Controls

Johnson Controls tyco DS-1 Series manual

SNOWJOE AQUAJOE SJI-OMS16 manual

SNOWJOE

SNOWJOE AQUAJOE SJI-OMS16 manual

Melnor 4501 User instructions

Melnor

Melnor 4501 User instructions

Tyco RFIII manual

Tyco

Tyco RFIII manual

CENTRAL ELO LH manual

CENTRAL

CENTRAL ELO LH manual

Senju Sprinkler RC-RES manual

Senju Sprinkler

Senju Sprinkler RC-RES manual

Viking MicrofastHP VK340 Technical data

Viking

Viking MicrofastHP VK340 Technical data

Nelson F44AAB quick start guide

Nelson

Nelson F44AAB quick start guide

Eden 94113-EDAMZ quick start guide

Eden

Eden 94113-EDAMZ quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.