INSTALLATION
The Pulsar ESFR-25 Pendent Sprinklers are to be in-
stalled in accordance with the following instructions:
NOTE
Damage to the fusible Link Assembly during installation
can be avoided by handling the sprinkler by the frame
arms only (i.e., do not apply pressure to the fusible Link
Assembly), and by using the appropriate sprinkler
wrench. Damaged sprinklers must be replaced.
A leak tight 1 inch NPT sprinkler joint should be obtained
withatorqueof20to30ft.lbs.(26,8to40,2Nm).Higher
levels of torque may distort the sprinkler inlet with conse-
quent leakage or impairment of the sprinkler.
1. The Pulsar ESFR-25 Sprinkler must be installed in the
pendent position.
2. With pipe thread sealant applied, hand tighten the sprinkler
into the sprinkler fitting. Do not apply pressure to the Link
Assembly, and handle the Pulsar ESFR-25 Sprinkler only
by the Frame arms.
3. Wrench tighten the Pulsar ESFR-25 Sprinkler using only
the W-Type 1 Sprinkler Wrench (Ref. Figure 2) and by fully
engaging (seating) the wrench with the sprinkler wrench
flats.
4. After installation, inspect the Link Assembly of each Pulsar
ESFR-25 Sprinkler for damage. In particular, verify that the
Link Assembly and Hook are positioned as illustrated in
Figure 1, and that the Link Assembly has not been bent,
creased, or forced out of its normal position in any way.
Damaged sprinklers must be replaced.
CARE AND MAINTENANCE
The Pulsar ESFR-25 must be maintained and serviced in
accordance with the following instructions:
NOTE
Before closing a fire protection system main control valve
for maintenance work on the fire protection system which
it controls, permission to shut down the affected fire pro-
tection systems must be obtained from the proper authori-
ties and all personnel who may be affected by this action
must be notified.
Sprinklers which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.
Automatic sprinklers must never be shipped or stored
where their temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified or over-heated
sprinklers must be replaced.
Care must be exercised to avoid damage - before, dur-
ing, and after installation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or the like, must be
replaced.
The owner is responsible for the inspection, testing, and
maintainance of their fire protection system and devices
in compliance with this document, as well as with the ap-
plicable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.
It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.
LIMITED WARRANTY
Products manufactured by Tyco Fire Products are war-
ranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty
is given for products or components manufactured by
companies not affiliated by ownership with Tyco Fire Prod-
ucts or for products and components which have been
subject to misuse, improper installation, corrosion, or
which have not been installed, maintained, modified or re-
paired in accordance with applicable Standards of the Na-
tional Fire Protection Association, and/or the standards of
any other Authorities Having Jurisdiction. Materials found
by Tyco Fire Products to be defective shall be either re-
paired or replaced, at Tyco Fire Products’ sole option.
Tyco Fire Poducts neither assumes, nor authorizes any
person to assume for it, any other obligation in connec-
tion with the sale of products or parts of products. Tyco
Fire Products shall not be responsible for sprinkler sys-
tem design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI-
ABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UN-
DER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR IM-
PLIED, INCLUDING WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE.
STAR SPRINKLER
1-4.1.11 Page 3
FIGURE 2
W-TYPE 1 SPRINKLER WRENCH
"FITTING SIDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH