manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco Fire Product
  6. •
  7. Irrigation System
  8. •
  9. Tyco Fire Product CENTRAL ESLO User manual

Tyco Fire Product CENTRAL ESLO User manual

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Gem F938 User manual

Tyco Fire Product

Tyco Fire Product Gem F938 User manual

Tyco Fire Product Gem TFP1 User manual

Tyco Fire Product

Tyco Fire Product Gem TFP1 User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product CENTRAL ELO LH User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO LH User manual

Tyco Fire Product Star Luminous S178 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S178 User manual

Tyco Fire Product Gem DS-1 Series User manual

Tyco Fire Product

Tyco Fire Product Gem DS-1 Series User manual

Tyco Fire Product TY-QRF User manual

Tyco Fire Product

Tyco Fire Product TY-QRF User manual

Tyco Fire Product CENTRAL K25-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K25-1 User manual

Tyco Fire Product Star Galaxy SG User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SG User manual

Tyco Fire Product CENTRAL S170 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL S170 User manual

Tyco Fire Product Gem RFII Series User manual

Tyco Fire Product

Tyco Fire Product Gem RFII Series User manual

Tyco Fire Product Star Pulsar S195 User manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S195 User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product Gem F892QR User manual

Tyco Fire Product

Tyco Fire Product Gem F892QR User manual

Tyco Fire Product CENTRAL TY-B Series User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B Series User manual

Tyco Fire Product CENTRAL H-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H-1 User manual

Tyco Fire Product RAPID RESPONSE LFII Series User manual

Tyco Fire Product

Tyco Fire Product RAPID RESPONSE LFII Series User manual

Tyco Fire Product EC-17 User manual

Tyco Fire Product

Tyco Fire Product EC-17 User manual

Tyco Fire Product CENTRAL A-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A-1 User manual

Tyco Fire Product CENTRAL Omega HEC-12 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Omega HEC-12 User manual

Tyco Fire Product Star PH-5 User manual

Tyco Fire Product

Tyco Fire Product Star PH-5 User manual

Tyco Fire Product Gem F892 User manual

Tyco Fire Product

Tyco Fire Product Gem F892 User manual

Tyco Fire Product Gem STAINLESS STEEL QUARTZOID User manual

Tyco Fire Product

Tyco Fire Product Gem STAINLESS STEEL QUARTZOID User manual

Tyco Fire Product CENTRAL WS User manual

Tyco Fire Product

Tyco Fire Product CENTRAL WS User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Reliable RFC30 LL manual

Reliable

Reliable RFC30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

5-97ESLO
Technical
Data
Product
Description
The Central Model ESLO Very Extra
Large Orifice Recessed Pendent and
Pendent Automatic Glass Bulb Sprinklers
are specifically designed for Extended
Coverage/Light Hazard for all Groups as
defined by NFPA 13. They are Listed as
Quick Response, up to 18'x18' spacing,
and as Standard Response, above 18'x18'
spacing. Maximum ceiling slope of 2" per
foot. The ESLO is Listed for smooth flat
horizontal ceilings as are all Extended
Coverage Light Hazard Sprinklers.
The ESLO provides the maximum in
design flexibility as it has a minimum
separation of only 9'-0" and is Listed for
flows and pressures associated with
16'x16', 18'x18' and 20'x20' spacing.
They are intended for use, as all ex-
tended coverage sprinklers are, with
hydraulically designed systems and using
the flows and pressures as shown in this
brochure. For the purpose of determining
the correct flow and pressure to use in the
hydraulic calculations, all spacing is
rounded up to the next higher category.
For example, 17'-6"x15'-0" spacing would
be calculated at the Listed 18'x18' flow and
pressure.
The advantage of the ESLO is the ability
to cover large areas, up to 400 square
feet, with pressures that compare to 1⁄2"
standard sprinklers spaced at their
maximum of 225 square feet. For ex-
ample, the ESLO can cover 20'x20'
spacing or 400 square feet with less
pressure than is required with 1⁄2" sprin-
klers at 225 square feet. (7.6 vs. 16.1)
The Model ESLO Sprinkler incorporates
a specially designed deflector that pro-
vides a much greater area of coverage
than standard commercial sprinklers.
The two (2) piece recessed escutcheon
assembly provides for 3⁄4" of field adjust-
ment.
Quick Response
Extended
Coverage Light
Hazard Recessed
Pendent and
Pendent
Sprinkler
Quick Response
Extended Coverage Light Hazard
Very Extra Large Orifice
Recessed Pendent and Pendent
Glass Bulb Automatic Sprinkler
ESLO
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Model: ESLO
Style: Recessed Pendent, Pendent
Escutcheon: Model ELO (2-piece)
Recessed
Escutcheon Part #'s:
850 - Brush Brass 853 - White
851 - Bright Chrome 848 - Off White
852 - Bright Brass 849 - Black
Note: In the recessed position, only the
Model ELO (2-piece) Recessed Escutcheon
may be used. Substitution of other
“recessed” escutcheons may impair the
operating sensitivity and distribution
pattern.
Wrench
Pendent: Part #1073
ELO/ESLO/ESFR Combination
Recessed Pendent: Part #1093
ESLO Offset
Orifice Size: 0.70"
(17.8 mm)
(VELO)
K-Factor: 14.5
(207.35)
Thread Size: 3⁄4" N.P.T.
(19.1 mm)
Temperature Rating:
155°F/68°C
200°F/93°C (Available as Standard Response Only)
250°F/121°C (Available as Standard Response Only)
Approvals: U.L., cUL
Maximum Working Pressure: 175 psi
Factory Hydro Test: 100% at 500 psi
Standard Finishes:
Sprinkler: brass or chrome plated
Decorative Finishes: white or black
painted
Escutcheon: brass, chrome plated,
white or black painted
Length: 23⁄4"
(70 cm)
Width: 11⁄2"
(3.80 cm)
Weight: 4.2 oz.
(120 grams)
I
M
A
O
P
T
No. 3-4.5
OBSOLETE
2
Installation Diagrams
ESLO Extended Coverage Light Hazard Recessed Pendent
Note: Central's Model 65 or 401 escutcheon may be used. When using Central's Model 65
escutcheon, the face of the R.C. is to protrude 1/8" ±1/16" beyond the finished ceiling line.
Installation Diagrams
ESLO Extended Coverage Light Hazard Pendent
2 3/4"
1 1/2" Dia.
Face of
Reducing
Coupling
Finished
Ceiling LIne
1" x 3/4" Reducing
Coupling
Model ELO (2-piece)
Recessed Escutcheon
3 1/4" Diameter
2 1/4" Dia. Min.
2 3/4" Dia. Max.
3/8" Min.
3/4" Nominal
1 1/8" Max.
OBSOLETE
3
Design
Data
Design Requirements — Light Hazard Extended Coverage Applications
Density .1 GPM/ft2- NFPA 13 All Editions
Temperature Rating 155°F/68°C, 200°F/93°C, and 250°F/121°C Temperatures
Maximum Minimum Design Minimum Design
Spacing Between Location From Flow per Sprinkler Pressure per Sprinkler
Sprinklers Any Wall
(gpm) (psi)
*16 x 16 feet (256 sq. ft.) 8 feet 38.4 gpm 7 psi
*18 x 18 feet (324 sq. ft.) 9 feet 38.4 gpm 7 psi
**20 x 20 feet (400 sq. ft.) 10 feet 40.0 gpm 7.6 psi
*Teflon is a trademark of the DuPont Corp.
Care &
Maintenance
Sprinklers must be handled care-
fully. They must not be transported
or stored where ambient temperature
may exceed 100°F/38°C. For best
results, store them in a dry, cool
location in the original shipping
package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such manner
must be replaced.
The owner is responsible for the
proper operating condition of all fire
protection devices and accessories.
The NFPA standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
Systems”
, contains guidelines and
minimum maintenance requirements.
Furthermore, the local
Authority
Having Jurisdiction
may have addi-
tional regulations and requirements
for maintenance, testing, and inspec-
tion that must be obeyed.
It is advisable to have sprinkler
systems inspected regularly by a
qualified inspection service. Length of
time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
activity.
Do not attempt to reassemble or
otherwise reuse a sprinkler that has
operated. Replace any sprinkler
exhibiting corrosion or damage;
always use new sprinklers of the
same type and temperature rating as
replacements.
Because the discharge pattern is
critical to protection of life and
property, nothing should be hung or
attached to the sprinkler unit that
would disrupt the pattern. Such
obstructions must be removed. In the
event that construction has altered
the original configuration, the system
must be investigated and the protec-
tion level maintained.
Installation
The Model ESLO incorporates the
latest in heat-responsive glass bulb
technology. The operating mecha-
nism consists of a 3 mm liquid-filled
frangible capsule that is only 2.0 cm
in length.
Operation: The glass bulb capsule
operating mechanism contains a
heat-sensitive liquid that expands
upon application of heat. At the rated
temperature, the frangible capsule
ruptures, thereby releasing the orifice
seal. The sprinkler then discharges
water in a pre-designed spray pattern
to control the fire.
All Central Model ESLO Recessed
Pendent and Pendent Automatic
Sprinklers must be installed accord-
ing to the current NFPA 13 Standard
and these installation instructions.
Deviations from these requirements
and standards or any alteration to the
sprinkler itself will void any warranty
made by Central Sprinkler Company.
In addition, installation must also
meet local government provisions,
codes, and standards as applicable.
The system piping must be properly
sized to ensure the minimum required
flow rate at the sprinkler. Check for
the proper model, style, orifice size,
and temperature rating prior to
installation. Install sprinklers after the
piping is in place to avoid mechanical
damage; replace any damaged units.
Wet pipe systems must be
protected from freezing.
Upon completion of the installation,
the system must be tested per
recognized standards.
In the event of a thread leak,
remove the unit, apply new pipe joint
compound or tape, and reinstall.
Installation Sequence
Step 1. For Pendent and Recessed
Pendent sprinklers, the face of the
sprinkler fitting should be installed a
nominal 3⁄4" (±3⁄8") behind the ceiling
line. Adjustments are made via the
push-on escutcheon.
Step 2. Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply only to the male threads.
Step 3. Hand tighten the sprinkler
into the fitting. Use a Central
Sprinkler Wrench, to tighten the unit
into the fitting. A leak-tight joint
requires only 7 to 14 ft.-lbs. of torque;
a tangential force of 14 to 28 lbs.
delivered through a 6" handle will
deliver adequate torque. Torque
levels over 21 ft.-lbs. may distort the
orifice seal, resulting in leakage.
* Listed as Quick Response.
** Listed as Standard Response Only.
≠
Recessed Pendent Sprinkler is Listed as Standard Response Only.
Caution: Minimum spacing between pendent and recessed
pendent sprinklers is 9'-0".
OBSOLETE
©1997 Central Sprinkler Company
Printed in U.S.A. ESLO.1DC
Central Sprinkler Company
451 N. Cannon Avenue, Lansdale, PA 19446
Phone (215) 362-0700
FAX (215) 362-5385
Ordering Information: When
placing an order, indicate the full
product name. Please specify the
quantity, model, style, orifice size,
temperature rating, type of finish or
coating, and sprinkler wrench.
Availability and Service: Central
sprinklers, valves, accessories, and
other products are available through-
out the U.S. and Canada, and
internationally, through a network of
Central Sprinkler distribution centers.
You may write directly to Central
Sprinkler Company, or call (215) 362-
0700 for the distributor nearest you.
Patents: Patents are pending.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 M
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa
= 0.0689 bar
= 0.0703 kg/cm2
1 U.S. gallon = 3.785 dm3
= 3.785 liters
Conversions are approximate.
OPTIMA™ is a registered trademark of
Central Sprinkler Company.
Ordering
Information
Do not attempt to replace sprinklers
without first removing the fire protec-
tion system from service. Be certain
to secure permission from all authori-
ties having jurisdiction, and notify all
personnel who may be affected
during system shutdown. A fire
watch during maintenance periods is
a wise precaution.
To remove the system from service
mode, first refer to the system
operating guide and valve instruction.
Drain water and relieve pressure in
the pipes. Remove the existing unit
and install the replacement, using
only the special sprinkler wrench. Be
certain to match model, style, orifice,
and temperature rating.
A fire protection system that has
been shut off after an activation
should be returned to service immedi-
ately. Inspect the entire system for
damage and replace or repair as
necessary. Sprinklers that did not
operate but were subjected to corro-
sive elements of combustion or
excessive temperatures should be
inspected, and replaced if need be.
The
Authority Having Jurisdiction
will
detail minimum replacement require-
ments and regulations.
Guarantee: Central Sprinkler Com-
pany will repair and/or replace any
products found to be defective in
material or workmanship within a
period of one year from the date of
shipment. Please refer to the current
Price List for further details of the
warranty.
OBSOLETE