The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Sprinkler Identification Number
SIN C5153
Approvals
UL & C-UL Listed. FM & NYC Approved.
(The approvals apply only to the service
conditions indicated in the Design
Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Discharge Coefficient
K = 11.2 GPM/psi1/2 (161,3 LPM/bar1/2)
Temperature Ratings
155°F/68°C, 200°F/93°C & 286°F/121°C
Finishes
Sprinkler: Natural Brass
Physical Characteristics
The Model LD Large Drop Storage
Sprinklers utilize a dezincification
resistant (DZR) bronze frame and a 5
mm bulb. The sprinkler frame orifice is
sealed with a gasketed spring plate
(Belleville Seal) consisting of a
beryllium nickel disc spring that is
sealed on both its inside and outside
edges with a TeflonTM gasket. The
compression screw is bronze, and the
deflector is brass.
Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model LD
11.2 K-factor
Standard Response
Control Mode - Large Drop
Upright Glass Bulb Automatic Sprinkler
No. 3-6.0
General
Description
The Central Model LD, 11.2 K-factor,
Standard Response, Upright Large
Drop Storage Sprinklers are glass
bulb type automatic sprinklers. They
are intended for use with National Fire
Protection Association and Factory
Mutual Research Corporation "large
drop sprinkler" installation criteria for
the protection of high piled storage.
The Model LD Sprinklers can provide
a higher level of protection than
standard spray sprinklers and, in
some cases, they can provide an
economic advantage by eliminating in-
rack sprinklers.
Applications for the Model LD Sprin-
klers are expanding beyond the
current recognized installation
standards. For information regarding
research fire tests which may be
acceptable to an Authority Having
Jurisdiction (e.g., the protection of
class II commodity in a 40 foot freezer
using a double interlock preaction
system), please contact the Technical
Services Department.
Operation: The glass bulb contains a
fluid which expands when exposed to
heat. When the rated temperature is
reached, the fluid expands sufficiently
to shatter the glass bulb, which then
allows the sprinkler to activate and
flow water.
WARNING
The Model LD Large Drop Storage
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the
integrity of these devices.
Technical
Data
CENTRAL LD 2-01
Large Drop
Upright
Sprinklers
OBSOLETE
CENTRAL
WRENCH
FLAT
2" (50.8 mm)
3/4" NPT
2-3/4
(69.9 mm)
ELEVATION VIEW
SPRINKLER
FRAME
DEFLECTOR
GLASS BULB
OPERATING
ELEMENT
GASKETED
SPRING PLATE
(BELLEVILLE
SEAL)
BUTTON
ASSEMBLY
COMPRESSION
SCREW
Figure 2 - Cross Section Model LD,
Large Drop Storage Sprinkler
Figure 1 - Model LD,
Large Drop Storage Sprinkler
Figure 3 - W-Type 3 Sprinkler Wrench (Part #1073)
OBSOLETE
Design
Criteria
The Model LD, 11.2 K-factor Large
Drop Storage Sprinklers are UL and
C-UL Listed and NYC Approved (MEA
466-92-E Vol. III), for use in
accordance with current NFPA 13
Standards for Large Drop Sprinklers.
The Model LD, 11.2 K-factor Large
Drop Storage Sprinklers are FM
Approved as "Control Mode Specific
Application Large Drop Sprinklers" for
use in accordance with the FM Loss
Prevention Data Sheets.
Installation
The Model LD Large Drop Storage
Sprinklers
must be installed in
accordance with the following instruc-
tions.
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The
diameter of the air bubble is approxi-
mately 1/16 inch (1,6 mm) for the
155
°
F/68
°
C to 3/32 inch (2,4 mm) for
the 286
°
F/141
°
C rating.
A leak tight 3/4 inch NPT sprinkler
joint should be obtained with a torque
of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). A
maximum of 30 ft.lbs. (40,7 Nm) of
torque is to be used to install 3/4 inch
NPT sprinklers. Higher levels of
torque may distort the sprinkler inlet
with consequent leakage or impair-
ment of the sprinkler.
Step 1. The Model LD Large Drop
Storage Sprinklers must only be
installed in the upright position.
Step 2. With pipe thread sealant
applied to the pipe threads, wrench
tighten the LD by using only the
W-Type 3 Sprinkler Wrench (Ref.
Fig. 3). The W-Type 3 Sprinkler
Wrench is to be applied to the
sprinkler wrench flats only.
The Model LD Large Drop Stoage
Sprinklers
must be maintained and
serviced in accordance with the
following instructions.
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system it
controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties. All personnel who may be
affected by this action must be
notified.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
shipped or stored where their tem-
peratures will exceed 100°F/38°C and
they must never be painted, plated,
coated or otherwise altered after
leaving the factory. Modified sprinklers
must be replaced. Sprinklers that
have been exposed to corrosive
products of combustion, but have not
operated, should be replaced if they
cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.
Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installa-
tion Section).
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (e.g., NFPA
25), in addition to the standards of any
other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Care &
Maintenance
OBSOLETE
Printed in U.S.A. 2-01
Flow Control
Tyco Fire

Products
Ordering Information: When placing
an order, indicate the full product name.
Please specify the quantity, model,
style, orifice size, temperature rating,
type of finish or coating, and sprinkler
wrench. Refer to price list for complete
listing of Part Numbers.
Teflon is a trademark of the DuPont Corp.
Ordering
Information
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and
workmanship when paid for and
properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by Tyco Fire
Products. No warranty is given for
products or components manufac-
tured by companies not affiliated by
ownership with Tyco Fire Products or
for products and components which
have been subject to misuse, im-
proper installation, corrosion, or which
have not been installed, maintained,
modified or repaired in accordance
with applicable Standards of the
National Fire Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction.
Materials found by Tyco Fire Products
to be defective shall be either repaired
or replaced, at Tyco Fire Products'
sole option. Tyco Fire Products
neither assumes, nor authorizes any
person to assume for it, any other
obligation in connection with the sale
of products or parts of products. Tyco
Fire Products shall not be responsible
for sprinkler system design errors or
inaccurate or incomplete information
supplied by Buyer or Buyer's repre-
sentatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING
BUT NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE
POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO
FIRE PRODUCTS' LIABILITY
EXCEED AN AMOUNT EQUAL TO
THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WAR-
RANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR
PURPOSE.
Limited
Warranty
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Gem A User manual

Tyco Fire Product

Tyco Fire Product Gem A User manual

Tyco Fire Product TFR MAX User manual

Tyco Fire Product

Tyco Fire Product TFR MAX User manual

Tyco Fire Product Gem DS-1 Series User manual

Tyco Fire Product

Tyco Fire Product Gem DS-1 Series User manual

Tyco Fire Product Star SG S180 User manual

Tyco Fire Product

Tyco Fire Product Star SG S180 User manual

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product

Tyco Fire Product CENTRAL RFII Series User manual

Tyco Fire Product CENTRAL Royal Flush A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Royal Flush A User manual

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 BVQR User manual

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product Star Quasar Q User manual

Tyco Fire Product

Tyco Fire Product Star Quasar Q User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product CC1 User manual

Tyco Fire Product

Tyco Fire Product CC1 User manual

Tyco Fire Product Star SG-R User manual

Tyco Fire Product

Tyco Fire Product Star SG-R User manual

Tyco Fire Product Star E User manual

Tyco Fire Product

Tyco Fire Product Star E User manual

Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product

Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product Gem F916 User manual

Tyco Fire Product

Tyco Fire Product Gem F916 User manual

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K11 ECOH User manual

Tyco Fire Product TY-QRF User manual

Tyco Fire Product

Tyco Fire Product TY-QRF User manual

Tyco Fire Product Gem F917 User manual

Tyco Fire Product

Tyco Fire Product Gem F917 User manual

Tyco Fire Product Gem TFP1 User manual

Tyco Fire Product

Tyco Fire Product Gem TFP1 User manual

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product CENTRAL K25-1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL K25-1 User manual

Tyco Fire Product Gem F898 User manual

Tyco Fire Product

Tyco Fire Product Gem F898 User manual

Popular Irrigation System manuals by other brands

Galcon 9001D Operation and installation instructions

Galcon

Galcon 9001D Operation and installation instructions

Senju Sprinkler SS8464 Installation

Senju Sprinkler

Senju Sprinkler SS8464 Installation

Rain Bird 500 series Operation & maintenance manual

Rain Bird

Rain Bird 500 series Operation & maintenance manual

Viking MICROFAST VK353 Technical data

Viking

Viking MICROFAST VK353 Technical data

Tyco Fire Protection Products CC2 manual

Tyco Fire Protection Products

Tyco Fire Protection Products CC2 manual

Johnson Controls tyco ILLUSION manual

Johnson Controls

Johnson Controls tyco ILLUSION manual

Viking VK572 Technical data

Viking

Viking VK572 Technical data

Orbit 58322 Assembly and operating instructions

Orbit

Orbit 58322 Assembly and operating instructions

IrriGreen Irrigreen2 installation manual

IrriGreen

IrriGreen Irrigreen2 installation manual

Viking FREEDOM VK494 Technical data

Viking

Viking FREEDOM VK494 Technical data

Johnson Controls tyco TY-FRB Series manual

Johnson Controls

Johnson Controls tyco TY-FRB Series manual

Hunter Professional PGP Ultra Series quick start guide

Hunter

Hunter Professional PGP Ultra Series quick start guide

CloudRain CloudRain Controller user manual

CloudRain

CloudRain CloudRain Controller user manual

Hills Heritage Hoist 6-Line product manual

Hills

Hills Heritage Hoist 6-Line product manual

Nelson SRNV100 operating instructions

Nelson

Nelson SRNV100 operating instructions

Holman EzyOneX Quick setup guide

Holman

Holman EzyOneX Quick setup guide

K-Line Irrigation G-Set Installation and user manual

K-Line Irrigation

K-Line Irrigation G-Set Installation and user manual

Reliable G VELO Pendent Bulletin

Reliable

Reliable G VELO Pendent Bulletin

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.