Product
Description Technical
Data
Model: ESLO-20 GB
Style: Upright
Wrench: ELO/ESLO/ESFR Combination
Part #1073
Orifice Size: 0.70"
(17.8 mm)
(VELO)
K-Factor: 14.5
(207.35 metric)
Thread Size: 3/4" N.P.T.
(20 mm)
Temperature Rating: 155°F/68°C
200°F/93°C
250°F/121°C
Installation Limitations:
• Unobstructed or non-combustible
obstructed construction consisting of
solid steel or concrete beams*.
• Minimum hydraulic design area of 5
heads or 1500 sq. ft.
(139.5 m
2
)
,
whichever is greater.
• Minimum spacing between upright
sprinklers is 14'
(4.3 m)
.
Approvals: U.L., F.M. M.E.A.
Maximum Working Pressure: 175 psi
(12.1 bar)
Factory Hydro Test: 100% at 500 psi
(34.5 bar)
Standard Finishes:
Sprinkler: brass or chrome plated
Decorative Finishes:
White or Black Painted
Corrosion Resistant Coatings:
White or Black Painted
(U.L. only)
Coatings: wax, lead, wax-over-lead
(FM only)
Escutcheon: brass, chrome plated, white
or black painted
Length: 3 1/8"
(7.94 cm)
Width: 1 3/4"
(4.44 cm)
Weight: 4.8 oz.
(136 grams)
Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
1-98
The Central Model ESLO-20 GB Very
Extra Large Orifice Upright Automatic Glass
Bulb Sprinkler is specifically designed for
Extended Coverage/Ordinary Hazard for all
Groups as defined by NFPA 13. The ESLO-
20 GB is acceptable for installations in
unobstructed and non-combustible
obstructed construction consisting of
solid steel or concrete beams*. The
ESLO-20 GB is Listed for an 18"
(457.2 mm)
commodity clearance from the deflector, as
standard sprinklers are per NFPA 13.
They are intended for use, as all extended
coverage sprinklers are, with hydraulically
designed systems and using the flows and
pressures as shown in this brochure. All
spacing is rounded up to the next higher
category. For example. 17'-6" x 15'-0"
(5.3 x
4.6 m)
spacing would be calculated at the
Listed 18' x 18'
(5.5 x 5.5 m)
flow and
pressure.
The advantage of the ESLO-20 is its
ability to cover large areas, up to 400 square
feet
(37.2 m
2
)
, with pressures that compare
to 1⁄2"
(15 mm)
standard sprinklers spaced at
their maximum of 130 square feet
(12.1 m
2
)
.
For example, the ESLO-20 can cover 18' x
18'
(5.5 x 5.5 m)
spacing or 324 square
feet
(30.1 m
2
)
with less pressure than is
required with 1⁄2"
(15 mm)
sprinklers at 130
square feet
(12.1 m
2
)
. (20.0 vs. 21.3
(1.4 bar
vs. 1.5 bar
)
The Model ESLO-20 GB Sprinkler
incorporates a specially designed deflector
that provides a much greater area of
coverage than most commercial sprinklers.
The Model ESLO-20 GB incorporates the
latest in heat-responsive glass bulb technol-
ogy. The operating mechanism consists of a
3 mm liquid-filled frangible capsule that is
only 2.0 cm
(20 mm)
in length.
Operation: The glass bulb capsule
operating mechanism contains a heat-
sensitive liquid that expands upon applica-
tion of heat. At the rated temperature, the
ESLO-20 GB
ESLO-20 GB
No. 2-3.0
I
M
A
O
P
T
Extended Coverage Ordinary Hazard
Very Extra Large Orifice
Upright Glass Bulb Automatic Sprinkler
*WEB members of open WEB trusses must not
exceed 1"
(25.4 mm)
diameter. Maximum ceiling
slope of 2" per foot
(158 mm/m)
.
Extended
Coverage
Ordinary
Hazard
Upright
Sprinkler
frangible capsule ruptures, thereby releasing
the orifice seal. The sprinkler then dis-
charges water in a pre-designed spray
pattern to control or extinguish the fire.
OBSOLETE
2
Figure 1
ESLO-20 GB Extended Coverage Ordinary Hazard
Upright
2 1/4"(57.2 mm)
Diameter
3 1/8"
(79.4 mm)
2 3/8"
(60.3 mm)
(Ref.)
1" x 3/4"
(25mm x 20mm)
Reducing
Coupling
ESLO .70
Position of Deflector When Located Above Bottom of Beam
Distance Maximum Allowable
From Sprinkler Distance Deflector
to Near Side of Above Bottom of
Beam Beam
Less than 1'
(< 25.4 mm)
0"
1' to less than 1'-6"
(25.4 < 152.4 mm)
0"
1'-6" to less than 2'
(25.4-152.4 <0.6 m)
1"
(25.4mm)
2' to less than 2'-6"
(0.6m < 0.8m)
1"
(25.4mm)
2'-6" to less than 3'
(0.8m < 0.9m)
1"
(25.4mm)
3' to less than 3'-6"
(0.9m < 1.1m)
3"
(76.2mm)
3'-6" to less than 4'
(1.1m < 1.2m)
3"
(76.2mm)
4' to less than 4'-6"
(1.2m < 1.4m)
5"
(127mm)
4'-6" to less than 5'
(1.4m < 1.5m)
7"
(177.8mm)
5' to less than 5'-6"
(1.5m < 1.7m)
7"
(177.8mm)
5'-6" to less than 6'
(1.7m < 1.8m)
7"
(177.8mm)
6' to less than 6'-6"
(1.8m < 2.0m)
9"
(228.6mm)
6'-6" to less than 7'
(2.0m < 2.1m)
11"
(279.4mm)
7' and greater
(< 2.1m)
14"
(355.6mm)
For SI Units: 1" = 25.4mm; 1' = 0.3048m
Beam
Ceiling
Not to Exceed Maximum
Specified for type of Construction
Distance from Near
Side of Beam
Maximum Distance Deflector
Above Bottom of Beam
OBSOLETE
3
Design
Data
Design Requirements — Commercial Extended Coverage Applications
Ordinary Hazard, Density 0.15 GPM/ft2- NFPA 13 1991 and later
Temperature Rating 155°F/68°C, 200°F/93°C and 250°F/121°C
Caution: Minimum spacing between upright sprinklers is 14'
(4.3m)
.
Design Requirements — Commercial Extended Coverage Applications
Ordinary Hazard, Density 0.21 GPM/ft2- NFPA 13 1989 or earlier
Temperature Rating 155°F/68°C, 200°F/93°C and 250°F/121°C
Design Requirements — Commercial Extended Coverage Applications
Ordinary Hazard, Density 0.20 GPM/ft2- NFPA 13 1991 and later
Temperature Rating 155°F/68°C, 200°F/93°C and 250°F/121°C
Design Requirements — Commercial Extended Coverage Applications
Ordinary Hazard, Density 0.19 GPM/ft2- NFPA 13 1989 or earlier
Temperature Rating 155°F/68°C, 200°F/93°C and 250°F/121°C
Design Requirements — Commercial Extended Coverage Applications
Ordinary Hazard, Density 0.16 GPM/ft2- NFPA 13 1989 or earlier
Temperature Rating 155°F/68°C, 200°F/93°C and 250°F/121°C
Maximum Minimum Design Minimum Design
Spacing Between Location From Flow per Sprinkler Pressure per Sprinkler
Sprinklers Any Wall GPM
(Lpm)
psi
(bar)
18 x 18 feet (324 sq. ft.) 9 feet 48.6 11.2
5.5 x 5.5 m(30.1m
2
) (2.7m) (184.2) (0.8 )
20 x 20 feet (400 sq. ft.) 10 feet 60.0 17.1
6.1 x 6.1 m(37.2m
2
) (3.0m) (227.4) (1.2)
Installation
All Central Model ESLO-20 GB
Upright Automatic Glass Bulb Sprin-
klers must be installed according to
current NFPA 13 Standards and
these installation instructions. Devia-
tions from these requirements and
standards or any alteration to the
sprinkler itself will void any warranty
made by Central Sprinkler Company.
In addition, installation must also
meet local government provisions,
codes, and standards as applicable.
The system piping must be properly
sized to ensure the minimum required
flow rate at the sprinkler. Check for
the proper model, style, orifice size,
and temperature rating prior to
installation. Install sprinklers after the
piping is in place to avoid mechanical
damage; replace any damaged units.
Wet pipe systems must be
protected from freezing.
Upon completion of the installation,
the system must be tested per
recognized standards.
In the event of a thread leak,
remove the unit, apply new pipe joint
compound or tape, and reinstall.
Installation Sequence
Step 1. The sprinkler must be
installed in the upright position.
Step 2. Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply only to the male threads.
Step 3. Hand tighten the sprinkler
into the fitting. Use a Central
Sprinkler Wrench, to tighten the unit
into the fitting. A leak-tight joint
requires only 7 to 14 ft.-lbs.
(9.5 to 19.0
Nm)
of torque; a tangential force of 14
to 28 lbs.
(62.3 to 124.5 N)
delivered
through a 6"
(150 mm)
handle will
deliver adequate torque. Torque
levels over 21 ft.-lbs.
(28.6 Nm)
may
distort the orifice seal, resulting in
leakage.
The sprinkler shall be oriented so
the frame arms are parallel with the
branch line pipe for upright sprinklers.
*Teflon is a trademark of the DuPont Corp.
Maximum Minimum Design Minimum Design
Spacing Between Location From Flow per Sprinkler Pressure per Sprinkler
Sprinklers Any Wall GPM
(Lpm)
psi
(bar)
18 x 18 feet (324 sq. ft.) 9 feet 51.8 12.8
5.5 x 5.5 m(30.1m
2
) (2.7m) (196.3) (0.9)
20 x 20 feet (400 sq. ft.) 10 feet 64.0 19.5
6.1 x 6.1 m(37.2m
2
) (3.0m) (242.6) (1.3)
Maximum Minimum Design Minimum Design
Spacing Between Location From Flow per Sprinkler Pressure per Sprinkler
Sprinklers Any Wall GPM
(Lpm)
psi
(bar)
18 x 18 feet (324 sq. ft.) 9 feet 61.6 18.0
5.5 x 5.5 m(30.1m
2
) (2.7m) (233.5) (0.8)
20 x 20 feet (400 sq. ft.) 10 feet 76.0 27.5
6.1 x 6.1 m(37.2m
2
) (3.0m) (288.0) (1.9)
Maximum Minimum Design Minimum Design
Spacing Between Location From Flow per Sprinkler Pressure per Sprinkler
Sprinklers Any Wall GPM
(Lpm)
psi
(bar)
18 x 18 feet (324 sq. ft.) 9 feet 64.8 20.0
5.5 x 5.5 m(30.1m
2
) (2.7m) (245.6) (1.4)
20 x 20 feet (400 sq. ft.) 10 feet 80.0 30.4
6.1 x 6.1 m(37.2m
2
) (3.0m) (303.2) (2.1)
Maximum Minimum Design Minimum Design
Spacing Between Location From Flow per Sprinkler Pressure per Sprinkler
Sprinklers Any Wall GPM
(Lpm)
psi
(bar)
18 x 18 feet (324 sq. ft.) 9 feet 68.0 22.0
5.5 x 5.5 m(30.1m
2
) (2.7m) (257.7) (1.5)
20 x 20 feet (400 sq. ft.) 10 feet 84.0 33.6
6.1 x 6.1 m(37.2m
2
) (3.0m) (318.4) (2.3)
OBSOLETE
©1998 Central Sprinkler Company
Printed in U.S.A. ESLO-20 GB.1
operated. Replace any sprinkler
exhibiting corrosion or damage;
always use new sprinklers of the
same type and temperature rating as
replacements.
Because the discharge pattern is
critical to protection of life and
property, nothing should be hung or
attached to the sprinkler unit that
would disrupt the pattern. Such
obstructions must be removed. In the
event that construction has altered
the original configuration, the system
must be investigated and the protec-
tion level maintained.
Do not attempt to replace sprinklers
without first removing the fire protec-
tion system from service. Be certain
to secure permission from all authori-
ties having jurisdiction, and notify all
personnel who may be affected
during system shutdown. A fire
watch during maintenance periods is
a wise precaution.
To remove the system from service
mode, first refer to the system
operating guide and valve instruction.
Drain water and relieve pressure in
the pipes. Remove the existing unit
and install the replacement, using
only the special sprinkler wrench. Be
certain to match model, style, orifice,
and temperature rating.
A fire protection system that has
been shut off after an activation
should be returned to service immedi-
ately. Inspect the entire system for
damage and replace or repair as
necessary. Sprinklers that did not
operate but were subjected to corro-
sive elements of combustion or
excessive temperatures should be
inspected, and replaced if need be.
The
Authority Having Jurisdiction
will
detail minimum replacement require-
ments and regulations.
Guarantee: Central Sprinkler Com-
pany will repair and/or replace any
products found to be defective in
material or workmanship within a
period of one year from the date of
shipment. Please refer to the current
Price List for further details of the
warranty.
Central Sprinkler Company
451 N. Cannon Avenue, Lansdale, PA 19446
Phone (215) 362-0700
FAX (215) 362-5385
Ordering
Information
Ordering Information: When
placing an order, indicate the full
product name. Please specify the
quantity, model, style, orifice size,
temperature rating, type of finish or
coating, and sprinkler wrench.
Availability and Service: Central
sprinklers, valves, accessories, and
other products are available through-
out the U.S. and Canada, and
internationally, through a network of
Central Sprinkler distribution centers.
You may write directly to Central
Sprinkler Company, or call (215) 362-
0700 for the distributor nearest you.
Patents: The ESLO-20 GB
Optima™ sprinklers are protected
under U.S. Patent No. 5,366,022.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 m
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa
= 0.0689 bar
= 0.0703 kg/cm2
1 U.S. gallon = 3.785 dm3
= 3.785 liters
Conversions are approximate.
Care &
Maintenance
Sprinklers must be handled care-
fully. They must not be transported
or stored where ambient temperature
may exceed 100°F/38°C. For best
results, store them in a dry, cool
location in the original shipping
package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such manner
must be replaced.
The owner is responsible for the
proper operating condition of all fire
protection devices and accessories.
The NFPA standard 25 entitled,
“Inspection, Testing and Maintenance
of Water-Based Fire Protection
Systems”
, contains guidelines and
minimum maintenance requirements.
Furthermore, the local
Authority
Having Jurisdiction
may have addi-
tional regulations and requirements
for maintenance, testing, and inspec-
tion that must be obeyed.
It is advisable to have sprinkler
systems inspected regularly by a
qualified inspection service. Length of
time between such inspections can
vary due to accessibility, ambient
atmosphere, water supply, and site
activity.
Do not attempt to reassemble or
otherwise reuse a sprinkler that has
OBSOLETE

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product

Tyco Fire Product Star LD-2 User manual

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BVR-2 User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Tyco Fire Product CENTRAL Royal Flush A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Royal Flush A User manual

Tyco Fire Product Star TFP1 User manual

Tyco Fire Product

Tyco Fire Product Star TFP1 User manual

Tyco Fire Product ESFR-22 User manual

Tyco Fire Product

Tyco Fire Product ESFR-22 User manual

Tyco Fire Product Gem ISSUE D QUARTZOID User manual

Tyco Fire Product

Tyco Fire Product Gem ISSUE D QUARTZOID User manual

Tyco Fire Product Gem F895 User manual

Tyco Fire Product

Tyco Fire Product Gem F895 User manual

Tyco Fire Product Star PH-5 User manual

Tyco Fire Product

Tyco Fire Product Star PH-5 User manual

Tyco Fire Product CENTRAL BVR User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BVR User manual

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product

Tyco Fire Product DS-2 Series User manual

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Optima User manual

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product Gem AQUARIUS F990 User manual

Tyco Fire Product

Tyco Fire Product Gem AQUARIUS F990 User manual

Tyco Fire Product Gem G102 User manual

Tyco Fire Product

Tyco Fire Product Gem G102 User manual

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product

Tyco Fire Product Gem FR-1 User manual

Tyco Fire Product Star Galaxy SG-RES User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SG-RES User manual

Tyco Fire Product CC1 User manual

Tyco Fire Product

Tyco Fire Product CC1 User manual

Tyco Fire Product CENTRAL ELO-231TM User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231TM User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product CENTRAL S176 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL S176 User manual

Tyco Fire Product Star SuperNova S120 User manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S120 User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Reliable RFC30 LL manual

Reliable

Reliable RFC30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.