
TFP1450
Page 19 of 28
Valve Setting
Procedure
Perform Steps 1 through 20 when ini-
tially setting the TYCO DV-5aValve,
after an operational test of the fire pro-
tection system, or after system opera-
tion due to a fire. Refer to Figure 12 or
13, as applicable, and determine which
type actuation system is being set.
Step 1. Close the System Main Control
Valve (B).
Step 2. Close the Diaphragm Supply
Valve (P) and Air Supply Valve (R).
Step 3. Open the Main Drain Valve (D),
System Drain Valve (E), and all auxil-
iary drains in the system. Close the
auxiliary drain valves and the System
Drain Valve (E) after water ceases to
discharge. Leave the Main Drain Valve
(D) open.
At this time make certain that the
Pressure Gauge Valves and the Alarm
Control Valve (H), as applicable, are
open.
NOTICE
Do not open the Inspector’s Test Con-
nection and auxiliary drains if reset-
ting after a system test; otherwise,
system air pressure will be relieved
unnecessarily.
Step 4. Depress the plunger of the
Automatic Drain Valve (F) to verify that
it is open.
Step 5. Clean the Diaphragm Supply
Strainer (Q) by removing the clean-
out plug and strainer basket. The Dia-
phragm Supply Strainer (Q) may be
flushed out by momentarily opening
the Diaphragm Supply Valve (P).
Step 6. Inspect for and clear all ice
plugs where system piping has been
exposed to freezing conditions and
when there has been a flow of water
into the system.
Step 7. Replace all damaged or oper-
ated sprinklers. Replacement sprinklers
must be of the same type and tempera-
ture rating as those that operated.
NOTICE
In order to prevent the possibility of a
subsequent operation of an overheated
solder type sprinkler, any solder type
sprinklers possibly exposed to a tem-
perature greater than their maximum
rated ambient must also be replaced.
Step 8. Service the air dryer, if appli-
cable, in accordance with the manu-
facturer’s instructions.
Step 9. De-energize the Solenoid Valve
(V).
• For Electric/Electric Actuation, de-
energize the Solenoid Valve (V) via
the Potter RCDS-1 Releasing Circuit
Disable Switch, or equivalent.
• For Electric/Pneumatic Actuation,
de-energize the Solenoid Valve (V) by
resetting the electric detection sys-
tem in accordance with the manufac-
turer's instructions.
Step 10. Operate (open) the Manual
Control Station (M) and then open
the Diaphragm Supply Valve (P). After
unaerated water ceases to discharge
from the Manual Control Station (M)
drain tube, slowly close the operating
lever by pushing it up. Do not close the
hinged cover at this time.
Step 11. After allowing water to flow out
of the Manual Reset Actuator (N) drain
tube until aerated water ceases to dis-
charge, reset the Manual Reset Actua-
tor (N) by pressing the Reset Knob and
hold until water stops flowing from its
drain tube and the pressure builds and
reaches approximately 15 psi (1,0 bar)
on the Diaphragm Gauge (K). Pressure
will then build up in the DV-5aDia-
phragm Chamber.
Step 12. Inspect the actuation device
drain connections. Any leaks must be
corrected before proceeding to the
next step.
• Electric/Electric actuation drain con-
nection to be inspected are from the
Manual Control Station (M) and Sole-
noid Valve (V) shown in Figure 4.
• Electric/Pneumatic actuation drain
connection to be inspected are from
the Manual Control Station (M) and
Dry Pilot Actuator (W) shown in Fig-
ure 5.
Step 13. Verify the ability for the DV-5a
Diaphragm to hold pressure as follows:
• With the diaphragm chamber pres-
surized per Step 11, temporarily
close the Diaphragm Supply Valve
(P), and then observe the Diaphragm
Gauge (K) for a drop in pressure.
• If a drop in pressure is noted, the
DV-5aDiaphragm is to be replaced
and/or any leaks must be corrected
before proceeding to the next step.
• If the Diaphragm Gauge (K) indicates
no drop in pressure, re-open the Dia-
phragm Supply Valve (P) and pro-
ceed to the next step.
Step 14. Open the Air Supply Valve
(S) and allow the system to automati-
cally re-establish its nominal system
air pressure. Observe the Automatic
Drain Valve (F) for leaks. If there are
leaks, determine/correct the cause of
the leakage problem.
• Nominal system air pressure for Elec-
tric/Electric Actuation is typically 15
psi (1,0 bar).
• Nominal system air pressure for
Electric/Pneumatic Actuation is per
Graph B.
Step 15. Open the System Shut-Off
Valve (X), as will be the case when
resetting a system after performing an
operational test.
Step 16. Previously in Step 9 for Elec-
tric/Pneumatic Actuation, the detec-
tion system was reset; however, at this
time for Electric/Electric Actuation, the
Solenoid Valve (V) is disconnected via
the Potter RCDS-1 Releasing Circuit
Switch, or equivalent.
For Electric/Electric Actuation, first
proceed to reset the electric detection
system in accordance with the manu-
facturer's instructions. After setting
the releasing panel, return the Potter
RCDS-1 to "green light - releasing
circuit system normal".
Step 17. Partially open the System
Main Control Valve (B). Slowly close the
Main Drain Valve (D) as soon as water
discharges from the Main Drain Valve
(D). Observe the Automatic Drain Valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem before proceeding.
NOTICE
When the System Main Control Valve
(B) is partially opened, the pressure on
the DV-5aDiaphragm Chamber may
increase. This increase in pressure is
normal, and if the pressure is greater
than 300 psi (20,7 bar), the pressure
is to be relieved by partially and tem-
porarily opening the Manual Control
Station (M); however, do not allow
the pressure as indicated on the Dia-
phragm Gauge (K) to drop below the
supply pressure shown on the Water
Supply Gauge (J), since this action may
result in tripping of the DV-5aValve.
Step 18. Close the hinged cover on the
Manual Control Station (M) and insert a
new break rod in the small hole through
the top of the enclosing box.
Step 19. Fully open the System Main
Control Valve (B).
Step 20. After setting a fire protec-
tion system, notify the proper authori-
ties and advise those responsible for
monitoring proprietary and/or central
station alarms.