Tyco DV-5A User manual

Page 1 of 18 MAY 2023 TFP1416
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp1416
DV-5AAutomatic Water Control Valve, Single
Interlock Preaction, Dry Pilot Actuation, Fire
Protection System 1 1/2 to 8 Inch (DN40 to DN200)
General
Description
The TYCO DV-5AAutomatic Water
Control Valve Single Interlock Preaction
Dry Pilot Actuation is a diaphragm type
valve that can be used in single inter-
lock preaction fire protection systems.
When properly trimmed, the double
seat design of the DV-5AValve also
provides actuation of fire alarms upon
system operation.
The diaphragm style design of the
DV-5AValve allows external resetting,
providing for easy resetting of a deluge
system without having to open a valve
handhole cover to manually reposition
a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm
chamber resets the valve.
The DV-5Afeatures internal and exter-
nal coating of the valve to provide
corrosion resistance. The external cor-
rosion resistance of the epoxy coating
permits the use of the DV-5Ain cor-
rosive atmospheres associated with
many types of industrial processing
plants and outdoor installations.
The DV-5ASingle Interlock Preaction
Dry Pilot Actuation Valve is offered
with the DV-5AValve and separately
ordered semi-assembled trim as shown
in Figure 5 for ease of installation.
The DV-5ASingle Interlock Preaction
Dry Pilot Actuation Valve is offered
with or without a System Main Control
Valve.
The DV-5ASingle Interlock Preaction
Dry Pilot Actuation Valve utilizes auto-
matic sprinklers and a supplemental
detection system, comprised of dry
pilot lines. Actuation of the detec-
tion system automatically operates
(releases) the DV-5AValve, allowing
water to flow into the sprinkler piping
system and to be discharged from any
sprinklers that may subsequently open.
Available End Connections and Weights — lb (kg)
End Connection Nominal Valve Size
ANSI Inches
(DN)
Inlet Outlet 1 1/2
(40) 2
(50) 3
(80) 4
(100) 6
(150) 165,1
mm 8
(200)
Thread Thread 26
(11,8) 25
(11,3) N/A N/A N/A N/A N/A
Groove Groove 25
(11,3) 25
(11,3) 60
( 27, 2 ) 95
(4 3,1) 177
(80,3) 177
(80,3) 327
(148,3)
Flange Groove N/A N/A 66
(30,0) 106
(48,1) 190
(86,2) N/A 346
(157,0)
Flange Flange N/A N/A 72
(32,7) 116
(52,6) 204
(92,5) N/A 365
(165,6)

TFP1416
Page 2 of 18
Item Description Qty.
Nominal Valve Size ANSI Inch (DN)
1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150)e8 (DN200)
P/N P/N P/N P/N P/N P/N
1Valve Body 1N/R N/R N/R N/R N/R N/R
2Diaphragm 1545000020 545000020 545000030 545000040 545000060 545000080
3Diaphragm Cover 1N/R N/R N/R N/R N/R N/R
4 Hex Bolt, Short 2a545100001 545100001 545100002 545100003 545100004 545100003
5Hex Bolt, Long 2545100011 545100011 545100012 545100013 545100014 545100015
6Lift Washer 2bN/A N/A 545100021 545100022 545100023 545100022
7Hex Nut 2545100031 545100031 545100032 545100033 545100034 545100033
8Hoist Ring 2545100041 545100041 545100041 545100041 545100041 545100041
9Flat Washer 2N/A N/A 545100024 545100025 545100026 545100025
NOTES
a. Hex Bolt, Short, Qty. 6 in 6 and 8 inch (DN150 and DN200) assemblies.
b. Lift Washer not used in 1 1/2 and 2 inch (DN40 and DN50) assemblies.
c. N/R = Not Replaceable.
d. Order replacements parts only via Part Numbers given, do not replace Hex Bolt, Hex
Nut, Lift Washer or Hoist Ring with common hardware parts.
e. Also applicable to metric 165,1 mm size.
1-1/2 AND 2 INCH
VALVES ONLY
6 AND 8 INCH
VALVES ONLY
79 5
6
3
4
1
75
3
1
1
2
5
9
1
2
3
8
4
7
6
FIGURE 1
DV-5AVALVE ASSEMBLY AND REPLACEMENT PARTS
Nominal
Valve
Size
ANSI
Inches
(DN)
Flange Drilling Specification
Nominal Dimensions in Inches and (mm)
ANSI B16.1a
(Class 125) ISO 7005-2
(PN16)bJIS B 2210
(10K) AS 2129
(Table E)
A B N A B N A B N A B N
3
(80) 6.00
(152,4) 0.75
(19,0) 46.30
(160,0) 0.75
(19,0) 85.90
(150,0) 0.59
(15,0) 85.75
(146,0) 0.71
(18,0) 4
4
(100) 7. 50
(190,5) 0.75
(19,0) 87.0 9
(180,0) 0.75
(19,0) 86.89
(175,0) 0.60
(15,0) 87. 0 0
178,0) 0.71
(18,0) 8
6
(150) 9.50
(241,3) 0.88
(22,2) 89.45
(240,0) 0.91
(23,0) 89.45
(240,0) 0.75
(19,0) 89.25
(235) 0.87
(22,0) 8
8
(200) 11.75
(298,5) 0.88
(22,2) 811.61
(295,0) 0.91
(23,0) 12 11.42
(290,0) 0.75
(19,0) 12 11.50
(292,0) 0.87
(22,0) 8
NOTES:
a. Same drilling as for
ANSI B16.5 (Class 150) and
ANSI B16.42 (Class 150)
b. Same drilling as for
BS 4504 Section 3.2 (PN16) and
DIN 2532 (PN16)
Dim. A
Bolt Circle
Diameter
Dim. B
Bolt Hole
Diameter
Qty. N
Number of
Bolt Holes
TABLE A
FLANGE DRILLING SPECIFICATIONS

TFP1416
Page 3 of 18
Port Port Description Port Sizes, NPT Inch per ANSI B1.20.1
1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150)a8 (DN200)
P1 Diaphragm Chamber Supply 1/2 1/2 1/2 1/2 1/2 1/2
P2 Water Supply Pressure & Alarm Test 1/2 1/2 1/2 1/2 1/2 1/2
P3 Alarm Actuation 3/4 3/4 3/4 3/4 3/4 3/4
P4 Automatic Drain Valve 1/2 1/2 1/2 1/2 1/2 1/2
P5 System Drain 3/4 3/4 3/4 3/4 3/4 3/4
P6 Main Drain 3/4 3/4 1 1/4 222
P7 System Air Supply 1/2 1/2 1/2 1/2 1/2 1/2
NOTES
a. Also applicable to metric 165,1 mm size.
FIGURE 2A
FIGURE 2C
FIGURE 2B
FIGURE 2D
SYSTEM DRAIN CONDITION
WATER SUPPLY SHUT OFF
DRAIN FROM SYSTEM
SET CONDITION
WATER SUPPLY
SYSTEM OPEN TO ATMOSPHERE
ALARM PORT
WATERFLOW
TO ALARM
WATER SUPPLY
PRESSURE &
ALARM TEST
SYSTEM
DRAIN
OPEN
SYSTEM
DRAIN
OPEN
MAIN
DRAIN
CLOSED
MAIN
DRAIN
OPEN
DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
SIDE OF
SHUT-OFF
VALVE
DIAPHRAGM
CHAMBER
DIAPHRAGM
CHAMBER
OPEN TO
ATMOSPHERE
VALVE
WATERWAY
DIAPHRAGM
SEAT
VALVE
WATERWAY
DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
SIDE OF
SHUT-OFF
VALVE
DIAPHRAGM
AUTOMATICALLY
FLEXES TO
ITS SEATED
POSTION
DIAPHRAGM
CHAMBER
OPEN TO
ATMOSPHERE
DIAPHRAGM
RETRACTS
OPENING
VALVE
WATERWAY
VALVE
WATERWAY
DIAPHRAGM
SEAT
VALVE
WATERWAY
OPERATED CONDITION
WATER SUPPLY SHUT OFF
RESIDUAL DRAIN CONDITION
WATERFLOW FROM WATER SUPPLY
WATERFLOW TO SYSTEM
RESIDUAL DRAIN FROM SYSTEM
SYSTEM
AIR
SUPPLY
AUTOMATIC
DRAIN VALVE
OPEN TO
ATMOSPHERE
AUTOMATIC
DRAIN VALVE
CLOSED
FIGURE 2
DV-5AVALVE OPERATION, PREACTION SYSTEMS

TFP1416
Page 4 of 18
Typically, the system designer selects
the detection components for a single
interlock preaction system that will
respond to a fire sooner than the auto-
matic sprinklers. Consequently, the
system will experience a minimal delay
in water delivery over that for a wet pipe
sprinkler system because the system
will have essentially filled with water
before a sprinkler operates. The DV-5A
Single Interlock Preaction Dry Pilot-
Actuation Valve automatically super-
vises the integrity of the overall system.
Supervision is provided by monitoring a
relatively low air pressure in the system
via a low pressure alarm switch so as
to detect leaks in the system that oth-
erwise would result in unwanted water
discharge should the system operate in
a fire condition.
Supervised single interlock preac-
tion systems are generally used to
protect areas where there is danger
of serious water damage that might
result from damaged automatic sprin-
klers or piping. Typically, such areas
include computer rooms, storage
areas for valuable artifacts, libraries,
and archives.
Single interlock preaction systems are
also effectively used to protect proper-
ties where a pre-alarm of a possible fire
condition may allow time for fire extin-
guishment by alternate suppression
means, prior to a sprinkler discharge.
In the event the fire cannot otherwise
be extinguished, the preaction sprinkler
system will then perform as the primary
fire protection system.
NOTICE
The DV-5Asingle interlock preaction
dry pilot actuation valve described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the NATIONAL FIRE PRO-
TECTION ASSOCIATION (NFPA), in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
UL and C-UL Listed
LPCB Approved
FM Approved
Listing and Approvals are based on the
DV-5ASingle Interlock Preaction Dry Pilot
Actuation Valve being trimmed as described
in Figure 5.
DV-5AValve
Components for the 1 1/2 in. to 8 in. (DN40 to
DN200) DV-5AValves are shown in Figure 1.
The DV-5AValves is for vertical installations.
It is rated for use at service pressures of 20
to 300 psi (1,4 to 20,7 bar).
The take-out dimensions are shown in
Figure 3, and flanged connections are
available drilled per ANSI, ISO, AS, and JIS
specications (See Table A). Threaded inlet
and outlet connections are available in NPT
or ISO 7-1. Threaded port connections are
NPT threaded.
Note: PN16 flanges are pressure rated to
16 bar.
Valve Trim
The maximum pressure rating for the single
interlock preaction dry pilot actuation trim
is 250 psi (17,2 bar).
When the system pressure is greater than
175 psi (12,1 bar), provision is to be made
to replace the standard order 300 psi (20,7
bar) water pressure gauges with separately
ordered 600 psi (41,4 bar) water pressure
gauges.
If the addition of an alarm control Valve is
desired or required by the local AHJ, the
alarm control valve noted as Item H in Figure
8 is to be a separately ordered electronically
supervised normally open valve.
External trim connections are NPT threaded.
EMEA trim is provided with NPT x ISO 7-1
thread adapters.
Pressure Loss
See Graph A
Detection System
See the Dry Pilot Actuation subsection.
System Air Pressure Requirements
The supervisory air (nitrogen) pressure is to
be 10 ± 2 psi (0,69 ±0,07 bar). The use of
a higher supervisory pressure is subject to
approval by the authority having jurisdiction,
and it should be understood that the use of
a higher supervisory pressure may increase
water delivery time. The use of a lower
supervisory pressure may prevent clearing
the alarm of the supervisory low pressure
switch (Item T - Figure 8), which is factory
set to alarm at 5 ± 1 psi (0,34 ± 0,07 bar) on
decreasing pressure. The supervisory air
supply pressure of 10 ± 2 psi (0,69 ± 0,07 bar)
can be provided by any of the following
methods. Refer to the applicable data sheet
for laboratory approval information.
• Model G16AC812 (self contained)
Automatic Supervisory Air Supply
described in Technical Data Sheet
TFP1620.
8 Inch (DN200)
6 Inch (DN150)
4 Inch (DN100)
3 Inch (DN80)
2 Inch (DN50)
1-1/2 Inch (DN40)
22-3/8"
(569 mm)
16-3/4"
(425 mm)
13-3/4"
(349 mm)
10-3/16"
(260 mm)
10-3/16"
(260 mm)
27-7/16"
(697 mm)
DIMENSIONS SHOWN
ARE APPLICABLE TO
ALL END CONNECTION
CONFIGURATIONS
AVAILABLE PER
VALVE SIZE
FIGURE 3
DV-5AVALVE
TAKE-OUT DIMENSIONS

TFP1416
Page 5 of 18
• A maximum 200 psi (13,8 bar) plant
air supply in combination with the
Model AMD-1 Air Maintenance Device
described in Technical Data Sheet
TFP1221.
• A maximum 3000 psi (206,9 bar)
nitrogen cylinder in combination
with the Model AMD-3 Nitrogen
Maintenance Device described in
Technical Data Sheet TFP1241.
Note: The dew point of the air or nitrogen
supply for a system exposed to freezing
conditions must be maintained below the
lowest ambient temperature to which the
system piping will be exposed. Introduction
of moisture into the system piping can cre-
ate ice build-up that could prevent proper
operation of the system.
The supervisory low pressure switch (Item
T - Figure 8) is factory set at 5 ± 1 psi (0,34 ±
0,07 bar) on decreasing pressure. The pres-
sure relief valve (Item S - Figure 8) is factory
set to fully open at 25 ± 2 psi (1,72 ± 0,14 bar)
and it begins to crack open at a pressure of
about 18 psi (1,24 bar).
Materials of
Construction
Valve Body
Epoxy coated ductile iron per ASTM
A536-77, Grade 65-45-12
Diaphragm Cover
Epoxy coated ductile iron per ASTM
A536-77, Grade 65-45-12
Diaphragm
Polyester fabric reinforced, TEFLON
coated, EPDM rubber per ASTM D2000
Diaphragm Cover Fasteners
Aluminum zinc coated steel
Common Hardware Trim
•
Common hardware pipe ttings are
galvanized or black as required and
are malleable per ASME B16.3.
•
Common hardware pipe nipples are
galvanized or black as required and
are Schedule 40 per ASTM A53 or
A135.
•
Common hardware compression
ttings are brass per ASTM B16.
•
Common hardware tubing is Type L
copper per ASTM B88.
3 INCH (DN80)
2 INCH (DN50)
4 INCH (DN100)
8 INCH (DN200)
1-1/2 INCH (DN40)
6 INCH (DN150), 165,1 mm
200 400 1000 3000200060010050
50002000 3000 1000070001000600400200
4000
15000
9.0
8.0
4.0
6.0
5.0
7.0
3.0
2.0
1.0
0.7
0.9
0.8
0.5
0.4
0.6
0.3
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0,06895 BAR)
FLOW RATE IN LITERS PER MINUTE (LPM)
(1 GPM = 3,785 LPM)
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)
FLOW RATE IN GALLONS PER MINUTE (GPM)
0,022
0,080
0,030
0,040
0,060
0,050
0,070
0,100
0,090
0,200
0,300
0,400
0,500
0,600
GRAPH A
DV-5AVALVE
NOMINAL PRESSURE LOSS VERSUS FLOW

TFP1416
Page 6 of 18
Operation
The TYCO DV-5AValve is a diaphragm
style valve that depends upon water
pressure in the diaphragm chamber,
see Figure 2A, to hold the diaphragm
closed against the water supply
pressure.
When the DV-5Avalve is set for service,
the diaphragm chamber is pressurized
through the trim connections from the
inlet side of the system’s main control
valve.
Opening the dry pilot actuation trips the
Model MRA-1 manual reset actuator.
Tripping the MRA-1 releases water from
the DV-5Adiaphragm chamber faster
than it can be replenished through a
1/8 in. (3,2 mm) restriction located in
the diaphragm chamber supply con-
nection. Release of water through the
MRA-1 results in a rapid pressure drop
in the DV-5adiaphragm chamber. The
force differential applied through the
diaphragm to hold the diaphragm in
the set position is then reduced below
the valve trip point. The water supply
pressure then forces the diaphragm
open permitting water to flow into the
system piping, as well as through the
alarm port to actuate the system alarms
(See Figure 2B).
Upon opening of the DV-5Avalve, the
Model MRA-1 manual reset actuator
opens to constantly vent the DV-5Adia-
phragm chamber to hydraulically latch
the DV-5Ain the tripped position until
manually reset.
In standby mode, the integrity of the
system piping is supervised by a low
pressure alarm switch.
See the Dry Pilot Actuation sections for
additional information.
Dry Pilot
Actuation
The dry pilot actuation trim forms a part
of the laboratory approval of the DV-5A
valves and is necessary for their proper
operation.
With reference to Figure 4, the dry pilot
actuation trim provides for installation
of a detection system consisting of pilot
sprinklers (heat detectors) and manual
control stations interconnected with
a minimum length of 56 ft (17,1 m) of
1/2 in. (DN15) steel pipe equivalent to
207 in.3(3400 cm3). The dry pilot line,
which is to be pressurized with air or
nitrogen, is connected to the dry pilot
line connection.
Dimensions are provided in Figure 7.
Pilot sprinklers are to be minimum 5.6
K-factor (80 K-factor) orifice approved
automatic sprinklers. Manual control
stations are to be the Model MC-1
described in Technical Data Sheet
TFP1382.
Note: For single interlock preaction
systems with dry pilot actuation, the
system designer typically selects dry pilot
sprinklers that will operate sooner than the
automatic sprinklers chosen for use on the
sprinkler piping.
Provision must be made for installing
a 5.6 K-factor (80 K-factor) inspector's
test connection at the most remote
location on the dry pilot line.
The dry pilot actuation trim is provided
with a Model DP-1 dry pilot actuator,
which is described in Technical Data
Sheet TFP1380. The actuator is rated
for use at a maximum pilot service
pressure of 50 psi (3,4 bar) and a
maximum water supply service pres-
sure of 250 psi (17,2 bar).
Graph B shows the minimum pilot line
service pressure as a function of the
water supply pressure. The pressure in
the dry pilot actuation system must be
automatically maintained using one of
the following maintenance devices, as
appropriate.
SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY
AUTOMATIC
SUPERVISORY
AIR/NITROGEN
SUPPLY
8 TO 12 PSI
SUPERVISORY
LOW PRESSURE
ALARM SWITCH
INSPECTOR'S
TEST CONNECTION
(AT MOST REMOTE
LOCATION FROM
DV-5A VALVE)
SYSTEM DRAIN VALVE
(NORMALLY CLOSED)
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
LOCAL
MANUAL
CONTROL
STATION
MAIN
CONTROL VALVE
(NORMALLY
OPEN)
WATER
SUPPLY
DRAIN
DIAPHRAGM CHAMBER
PRESSURE GAUGE
AUTOMATIC
AIR/NITROGEN
MAINTENANCE
DEVICE
DRAIN
WATER SUPPLY
PRESSURE
GAUGE
MANUAL RESET
ACTUATOR
RESTRICTION DRAIN
DRAIN
DRAIN
WATERFLOW
PRESSURE
ALARM
SWITCH
DRY PILOT SPRINKLER
DETECTION SYSTEM
(MINIMUM 1/2" PIPE AND
AUTOMATIC SPRINKLERS)
LOW
PRESSURE
ALARM
SWITCH
DRY PILOT
ACTUATOR
REMOTE
MANUAL
CONTROL
STATION
(WHEN
SPECIFIED)
DRAIN
DRAIN
DV-5A
VALVE
SYSTEM AIR
PRESSURE
GAUGE
WATER SUPPLY SHUT-OFF
(NORMALLY OPEN)
DIAPHRAGM
CHAMBER SUPPLY
CONTROL VALVE
(NORMALLY OPEN)
DIAPHRAGM CHAMBER
SUPPLY CONNECTION
FIGURE 4
DV-5AVALVE - SINGLE INTERLOCK PREACTION DRY PILOT ACTUATION SCHEMATIC DIAGRAM

TFP1416
Page 7 of 18
NOTES:
The dew point of the pilot line air pressure must be maintained
below the lowest ambient temperature to which the dry pilot
actuation system will be exposed. Accumulation of water in the
pilot line connection to the Actuator will lower the air pressure
at which the actuator will open and possibly prevent proper
operation. Also, introduction of moisture into the pilot lines
exposed to freezing temperatures can create an ice buildup
that could prevent proper operation of the Actuator.
An air dryer must be installed where the moisture content
of the air supply is not properly controlled at less than the
required value.
It is recommended that an AMD-3 Nitrogen Maintenance
Device be utilized in dry pilot actuation system applica-
tions where the dew point must be maintained below -20°F
(-29°C). Refer to Technical Data Sheet TFP1241.
• Model AMD-1 air maintenance
device (pressure reducing type), refer
to Technical Data Sheet TFP1221
• Model AMD-2 air maintenance device
(compressor control type), refer to
Technical Data Sheet TFP1231
• Model AMD-3 nitrogen maintenance
device (high pressure reducing
type), refer to Technical Data Sheet
TFP1241
Supervision of the pressure in the dry
pilot actuation system and an alarm
that separately indicates operation of
the detection system is provided by
a low pressure alarm switch set as
follows:
• Low pressure alarm setting at
approximately 6 psi (0,4 bar) below
the minimum pilot line service pres-
sure requirement shown in Graph B
• Fire alarm setting at approximately
15 psi (1,0 bar) below the minimum
pilot line service pressure require-
ment shown in Graph B
The dry pilot air pressure relief valve
provided in the trim is factory set to
relieve at a pressure of approximately
45 psi (3,1 bar); however, it may be
field adjusted to a lower pressure, if
required.
The dry pilot line is to be provided with
low point drains to enable draining of
condensate.
Note: At a minimum, it is recommended
thatinternally galvanized pipe and castiron
fittings be used for dry pilot lines.
Installation
The TYCO DV-5ASingle Interlock Pre-
action Dry Pilot Actuation Valve is to
be installed in accordance with this
section.
NOTICE
DV-5AAutomatic Water Control Valves
are designed to be used in freshwa-
ter systems. When the supply is from
an alternative source such as brackish
water, saltwater, or contains additives
such as foam, the limited warranty is
reduced to one year from the time of
installation. An increase in frequency of
inspections is required when the valve
is exposed to such supplies and other
corrosive conditions or chemicals that
could impact valve materials or the
operation of the assembly. The system
and all components must be designed
accordingly for the increased demand.
It is required to thoroughly flush the
valve and trim assembly with freshwa-
ter and reset to the set condition after
each operation.
Proper operation of the DV-5Asingle
interlock preaction dry pilot actua-
tion valve depends upon their trim
being installed in accordance with the
instructions given in this technical data
sheet. Failure to follow the appropriate
trim diagram may prevent the DV-5A
valve from functioning properly, as well
as void approvals and the manufactur-
er’s warranties.
The DV-5Avalve must be installed in a
readily visible and accessible location.
The DV-5Avalve, associated trim, and
wet pilot lines must be maintained at
a minimum temperature of 40°F (4°C).
Heat tracing of the DV-5Avalve or its
associated trim is not permitted. Heat
tracing can result in the formation of
hardened mineral deposits that are
capable of preventing proper operation.
Always open the system control valves
slowly to avoid a sudden rush of water
entering the system.
The DV-5Avalve is to be installed in
accordance with the following criteria:
Step 1. All nipples, fittings, and devices
must be clean and free of scale and
burrs before installation. Use pipe
thread sealant sparingly on male pipe
threads only.
Step 2. The DV-5Asingle interlock pre-
action dry pilot actuation valve must be
trimmed in accordance with the trim
illustrations shown in Figure 5.
Note:If the addition of an alarm control
valve is desired or required by the local
AHJ, the alarm control valve noted as
Item H in Figure 8 is to be a separately
orderedelectronicallysupervised normally
open valve.
Step 3. Care must be taken to ensure
that check valves, strainers, globe
valves, etc. are installed with the flow
arrows in the proper direction.
Step 4. Drain tubing to the drip funnel
must be installed with smooth bends
that will not restrict flow.
Step 5. The main drain and drip funnel
drain may be interconnected provided
a check valve is located at least 12 in.
(300 mm) below the drip funnel.
Step 6. Suitable provision must be
made for disposal of drain water. Drain-
age water must be directed such that
it will not cause accidental damage to
property or danger to persons.
WATER SUPPLY PRESSURE IN PSI
100
RANGE OF ACTUATOR OPENING PRESSURE
MINIMUM SYSTEM AIR PRESSURE
AIR PRESSURE IN PSI
20 60
15
0
30
45
140 180
250
200
GRAPH B
DV-5AVALVE SINGLE INTERLOCK PREACTION SYSTEM
DRY PILOT LINE AIR PRESSURE REQUIREMENTS

TFP1416
Page 8 of 18
Step 7. Connect the diaphragm supply
valve to the inlet side of the system
main control valve in order to facilitate
setting of the DV-5Avalve (See Figure
8).
Step 8. An inspector’s test connection,
as described in the dry pilot actuation
section, must be provided for dry pilot
actuation systems.
Step 9. An air maintenance device,
as described in the dry pilot actuation
section, must be provided for dry pilot
actuation.
Step 10. A desiccant dryer, when
specified for dry pilot actuation, is to
be installed between a drip leg and the
air maintenance device.
Step 11. The low pressure alarm switch
for dry pilot actuation is to be adjusted
as follows:
• Low pressure alarm setting at
approximately 6 psi (0,4 bar) below
the minimum pilot line service pres-
sure requirement shown in Graph B
•
Fire alarm setting at approximately
15 psi (1,0 bar) below the minimum
pilot line service pressure require-
ment shown in Graph B
Step 12. Unused pressure alarm switch
connections must be plugged.
Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C5 are described in Figure 6.
3. When ordering pre-assembled "DV-5AValve with Galvanized Trim" or pre-assembled "DV-5AValve with Galvanized Trim and Buttery Valve", Items A1
through A9 are provided, as applicably related to valve size.
4. When ordering DV-5ATrim separately from the DV-5AValve, Items A1 through A9 are separately ordered, as applicably related to valve size. Water
Pressure Gauges for EMEA valve trim are also separately ordered.
Assemble in order
from A to M
C8
C9
C3
C4
C7
C5
C7
C6
C2
C1
P1
P2
P3
P6
P7 P4
P5
1-1/2" (DN40) AND 2" (DN50)
VALVES ONLY
A1
A5
A4
A5
A6
A3
A2
A2
A7
A9
A8
L
E
D
C
A
B
G
H
F
M
J
K
FIGURE 5
DV-5AVALVE SINGLE INTERLOCK PREACTION
DRY PILOT ACTUATION TRIM
SEMI-ASSEMBLED

TFP1416
Page 9 of 18
Notes:
1. Port Connections P1
through P7 are described
in Figure 2.
2. External Trim Connec-
tions C1 through C5 are
described in Figure 8.
3. When ordering pre-assem-
bled "DV-5A Valve with
Galvanized Trim" or pre-
assembled "DV-5A Valve
with Galvanized Trim and
Buttery Valve", Items A1
through A9 are provided,
as applicably related to
valve size.
4. When ordering DV-5A Trim
separately from the DV-5A
Valve, Items A1 through
A9 are separately ordered,
as applicably related to
valve size. Water Pressure
Gauges for EMEA valve
trim are also separately
ordered.
ITEM QT Y. DESCRIPTION CH 1 1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150)b8 IN. (DN200)
1 3 1/4" GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 DP-1 DRY PILOT ACTUATOR 522801001 522801001 522801001 522801001 522801001 522801001
6 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
7 1 1/4" PRESSURE RELIEF VALVE 923431020 923431020 923431020 923431020 923431020 923431020
8 1 1/4" PRESSURE RELIEF VALVE, 25 PSI 923431019 923431019 923431019 923431019 923431019 923431019
9 2 1/2" BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
10 2 1/2" GLOBE VALVE 460471005 460471005 460471005 460471005 460471005 460471005
11 1 1/2" SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
12 1 1/2" SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007
13 11/2" Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
14 1 3/4" ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
15 1ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
16 1DRIP FUNNEL BRACKET CONNECTOR 922111005 922111005 9221110 0 5 9 221110 05 9 221110 05 922111005
17 1 DRIP FUNNEL BRACKET 922111003 922111003 9221110 0 3 9 221110 03 9 221110 03 92211100 3
18 1DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
19 1 COMP. FITTING 90° 1/2" MNPT x 1/2" OD TUBE ✓——————
20 2 COMP. FITTING 90° 1/2" FNPT x 1/2" OD TUBE ✓——————
21 2 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
22 2 FLARE FITTING 3/4" NPT x 3/4" TUBE 545100063 545100063 545100063 545100063 545100063 545100063
23 3PIPE PLUG ✓1/4" 1/4" 1/4" 1/4" 1/4" 1/4"
24 1PIPE PLUG ✓1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
25 1PIPE PLUG ✓3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
C1
C8
C9
C4
C7
C3
C7
C5
C6
C2
P1
P6
P7
P2
P3
P4
P5
1-1/2" (DN40) AND 2" (DN50)
VALVES ONLY
A5
A4
A5
A6
A1
A2
A3
A2
A7 A9
A8
2
11
19
15
35
58
57 22
14
44
3
31
41
16
13
39
29
39
9
26
39
22
52
26
33 37
123
27
51
21
40
9
39
29
21
46
6
48
59
39
50
38
5
42
20
1
38
36 31
38
31
32
10
38
32
7
18
17
23
4
31
20
56
53
34
12
32
36
1
38
23
38
38
10
38
24
41
28 54
29
30
55 29
45
49
38
60
60
43
61
62
59
33
8
34
25
47
FIGURE 6 (1 OF 2)
DV-5AVALVE — SINGLE INTERLOCK PREACTION DRY PILOT ACTUATION TRIM
EXPLODED VIEW

TFP1416
Page 10 of 18
ITEM QT Y. DESCRIPTION CH 1 1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150)b8 IN. (DN200)
26 2UNION ✓1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
27 1STREET ELBOW ✓1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90°
28 1ELBOW ✓1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45°
29 4ELBOW ✓1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90°
30 1CROSS ✓1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
31 4TEE ✓1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
32 3REDUCING TEE ✓1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2"
33 2REDUCING TEE ✓1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4"
34 2REDUCING TEE ✓3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4"
35 1REDUCING TEE ✓3/4" x 3/4" x 3/4" 3/4" x 3/4" x 3/4"
1 1/4" x 1 1/4" x 3/4"
2" x 2" x 3/4" 2" x 2" x 3/4" 2" x 2" x 3/4"
36 2PIPE NIPPLE ✓1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE
37 1PIPE NIPPLE ✓1/4" x 1 1/2" 1/4" x 1 1/2" 1/4" x 1 1/2" 1/4" x 1 1/2" 1/4" x 1 1/2" 1/4" x 1 1/2"
38 9PIPE NIPPLE ✓1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE
39 5PIPE NIPPLE ✓1/2" x 1 1/2" 1/2" x 1 1/2" 1/2" x 1 1/2" 1/2" x 1 1/2" 1/2" x 1 1/2" 1/2" x 1 1/2"
40 1PIPE NIPPLE ✓1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2"
41 2PIPE NIPPLE ✓1/2" x 2 1/2" 1/2" x 2 1/2" 1/2" x 2 1/2" 1/2" x 2 1/2" 1/2" x 2 1/2" 1/2" x 2 1/2"
42 1PIPE NIPPLE ✓1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3"
43 1PIPE NIPPLE ✓1/2" x 4 1/2" 1/2" x 4 1/2" 1/2" x 4 1/2" 1/2" x 4 1/2" 1/2" x 4 1/2" 1/2" x 4 1/2"
44 1PIPE NIPPLE ✓1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5"
45 1PIPE NIPPLE ✓1/2" x 8 1/2" 1/2" x 8 1/2" 1/2" x 8 1/2" 1/2" x 8 1/2" 1/2" x 8 1/2" 1/2" x 8 1/2"
46 1PIPE NIPPLE ✓3/4" x 1 1/2" 3/4" x 1 1/2" 3/4" x 1 1/2" 3/4" x 1 1/2" 3/4" x 1 1/2" 3/4" x 1 1/2"
47 1PIPE NIPPLE ✓3/4" x 4 1/2" 3/4" x 4 1/2" 3/4" x 4 1/2" 3/4" x 4 1/2" 3/4" x 4 1/2" 3/4" x 4 1/2"
48 1TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
49 1TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
50 1TUBING, DP-1 DRAIN 535000520 535000520 535000530 535000540 535000560 535000580
51 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
52 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
53 1PIPE NIPPLE ✓1/2" x 3 1/2" 1/2" x 3 1/2" 1/2" x 4 1/2" 1/2" x 5 1/2" 1/2" x 5 1/2" 1/2" x 6 3/4"
54 1PIPE NIPPLE ✓1/2" x 5" 1/2" x 5" 1/2" x 5 1/2" 1/2" x 5 1/2" 1/2" x 5 1/2" 1/2" x 6 1/2"
55 1PIPE NIPPLE ✓1/2" x 5" 1/2" x 5" 1/2" x 4 1/2" 1/2" x 5" 1/2" x 7 1/2" 1/2" x 9 1/2"
56 1PIPE NIPPLE ✓3/4" x 5" 3/4" x 5" 3/4" x 6" 3/4" x 7" 3/4" x 9" 3/4" x 11 1/2"
57 1PIPE NIPPLE ✓3/4" x 4 1/2" 3/4" x 4 1/2" 1 1/4" x 3 1/4" 2" x 3" 2" x 3" 2" x 3"
58 1PIPE NIPPLE ✓3/4" x 6 1/2" 3/4" x 6 1/2" 1 1/4" x 5 1/2" 2" x 5" 2" x 6" 2" x 8"
59
2WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
(AMER/APAC) 923431005 923431005 923431005 923431005 923431005 923431005
2WATER PRESSURE GAUGE, 20 bar / 2000 kPa
(EMEA) 025500013 025500013 025500013 025500013 025500013 025500013
60 2AIR PRESSURE GAUGE, 80 PSI / 550 kPa
RETARDED TO 250PSI / 1750 kPa 923431012 923431012 923431012 923431012 923431012 923431012
61 1LABEL 545003004 545003004 545003004 545003004 545003004 545003004
62 1 LABEL WIRE — — — — — —
A1 1DV-5AVALVE SEE ORDERING PROCEDURE, SEPARATE DV-5A VALVES WITHOUT TRIM, FOR PART NUMBERS
A2
1WATERFLOW PRESSURE ALARM SWITCH,
DOUBLE CONTACTS (APAC) 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102
1WATERFLOW PRESSURE ALARM SWITCH,
SINGLE CONTACTS (EMEA) 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101
1WATERFLOW PRESSURE ALARM SWITCH,
DOUBLE CONTACTS (AMER) 25710 25710 25710 25710 25710 25710
A3
1LOW AIR PRESSURE ALARM SWITCH, DOUBLE
CONTACTS (APAC) 25730 or 100402 25730 or 100402 25730 or 100402 25730 or 100402 25730 or 100402 25730 or 100402
1LOW AIR PRESSURE ALARM SWITCH, DOUBLE
CONTACTS (AMER) 25730 25730 25730 25730 25730 25730
1LOW AIR PRESSURE ALARM SWITCH, DOUBLE
CONTACTS (EMEA) 0262 or 100401 0262 or 100401 0262 or 100401 0262 or 100401 0262 or 100401 0262 or 100401
A4 1 BUTTERFLY VALVE, G x G 51024A 51021A — — — —
1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
A5 2FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
1FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A6 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
A7 1INVERTED FLARE SHUT-OFF VALVEa545100100 545100100 545100099 545100100 545100100 545100100
A8 1 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A9 1TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080
NOTES
a. Not VdS Approved
b. Also applicable to metric 165,1mm size.
CH - Common Hardware - See Materials of Construction section for specications.
FIGURE 6 (2 OF 2)
DV-5AVALVE — SINGLE INTERLOCK PREACTION DRY PILOT ACTUATION TRIM
EXPLODED VIEW

TFP1416
Page 11 of 18
Nominal
Valve
Size
ANSI
Inches
(DN)
Inches
(mm)
A B C D E F G H J
1 1/2
(40) 2.8
(71) 9.7
(246) 9.8
(249) 17.9
(455) 19.3
(490) 7.4
(188) 10.2
(259) 8.02
(204) 1.2
(31)
2
(50) 2.8
(71) 9.7
(246) 9.8
(249) 17.9
(455) 19.3
(490) 7.4
(188) 10.2
(259) 8.09
(205) 2.9
(74)
3
(80) 4.0
(102) 11.3
(287) 11.5
(292) 17.9
(455) 21.1
(536) 6.2
(158) 13.8
(351) 3.79
(96) 3.6
(91)
4
(100) 4.5
(114) 12.3
(312) 12.6
(320) 17.9
(455) 22.6
(574) 5.5
(140) 16.8
(427) 4.54
(115) 4.3
(109)
63
(150) 5.7
(145) 14.0
(356) 14.5
(368) 18.3
(465) 25.4
(645) 3.8
(97) 22.4
(569) 5.83
(148) 5.7
(145)
8
(200) 6.8
(174) 16.7
(424) 16.7
(424) 19.5
(495) 29.2
(742) 3.4
(86) 27. 5
(699) 5.24
(133) 6.7
(170)
NOTES
1. Dimensions based on drain valves being open.
2. Dimensions do not provide installation clearance.
3. Also applicable to metric 165,1 mm size.
HF
E
C
G
DB
J
A
FIGURE 7
DV-5AVALVE
SINGLE INTERLOCK PREACTION DRY PILOT ACTUATION TRIM
NOMINAL DIMENSIONS

TFP1416
Page 12 of 18
Step 10. After allowing water to flow
out of the manual reset actuator (N)
drain tube until aerated water ceases
to discharge, reset the manual reset
actuator (N) by pressing the reset knob
and hold until water stops flowing from
its drain tube and the pressure builds
and reaches approximately 15 psi (1,0
bar) on the diaphragm gauge (K). Pres-
sure will then build up in the DV-5adia-
phragm chamber.
Note: After relieving trapped air, check
the manual reset actuator (N) to make sure
there is no water draining from its drain
tube. If water is draining, reset the manual
reset actuator (N) as previously instructed.
Step 11. Verify the ability for the DV-5A
diaphragm to hold pressure as follows:
•
With the diaphragm chamber pres-
surized per Step 10, temporarily
close the diaphragm supply valve
(P), and then observe the diaphragm
gauge (K) for a drop in pressure.
•
If a drop in pressure is noted, the
DV-5Adiaphragm is to be replaced
and/or any leaks must be corrected
before proceeding to the next step.
•
If the diaphragm gauge (K) indicates
no drop in pressure, re-open the
diaphragm supply valve (P) and
proceed to the next step.
Step 12. Open the supervisory air
supply valve (S) to reestablish supervi-
sory system air pressure at nominally
10 psi (0,68 bar).
Step 13. Partially open the system
main control valve (B). Slowly close the
main drain valve (D) as soon as water
discharges from the main drain valve
(D). Observe the automatic drain valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem before proceeding.
NOTICE
When the system main control valve
(B) is partially opened, the pressure
on the DV-5Adiaphragm chamber may
increase. This increase in pressure is
normal, and if the pressure is greater
than 300 psi (20,7 bar), the pressure is
to be relieved by partially and temporar-
ily opening the manual control station
(M); however, do not allow the pressure
as indicated on the diaphragm gauge
(K) to drop below the supply pressure
shown on the water supply gauge (J),
since this action may result in tripping
of the DV-5Avalve.
Valve Setting
Procedure
Perform Steps 1 through 16 when ini-
tially setting the TYCO DV-5AValve,
after an operational test of the fire pro-
tection system, or after system opera-
tion due to a fire. See Figure 8.
Step 1. Close the system main control
valve (B).
Step 2. Close the diaphragm supply
valve (P) and close the dry pilot air
supply valve (W).
Step 3. Close the supervisory air
supply valve (S).
Step 4. Open the main drain valve (D),
system drain valve (E), and all auxiliary
drains in the system. Close the auxiliary
drain valves and the system drain valve
(E) after water ceases to discharge.
Leave the main drain valve (D) open.
At this time make certain that the pres-
sure gauge valves and the alarm control
valve (H), as applicable, are open.
Step 5. Depress the plunger of the
automatic drain valve (F) to verify that
it is open.
Step 6. Clean the diaphragm supply
strainer (Q) by removing the clean-
out plug and strainer basket. The dia-
phragm supply strainer (Q) may be
flushed out by momentarily opening
the diaphragm supply valve (P).
Step 7. Replace any operated sprin-
klers on the system piping, as
applicable.
Step 8. Reset the automatic actuation
system. Replace operated pilot sprin-
klers and/or reset the remote manual
control stations. Reestablish dry pilot
pneumatic pressure.
NOTICE
In order to prevent the possibility of a
subsequent operation of an overheated
solder type pilot sprinkler, any solder
type pilot sprinklers that were possibly
exposed to a temperature greater than
their maximum rated ambient must be
replaced.
Step 9. Operate (open) the manual
control station (M) and then open
the diaphragm supply valve (P). After
unaerated water ceases to discharge
from the manual control station (M)
drain tube, slowly close the operating
lever by pushing it up. Do not close the
hinged cover at this time.
Step 13. The dry pilot pressure relief
valve (Item Y - Figure 8) provided with
the dry pilot actuation trim is factory
set to relieve at a pressure of approxi-
mately 45 psi (3,1 bar), which can typi-
cally be used for a maximum dry pilot
actuation system pressure of 40 psi
(2,8 bar). The pressure relief valve may
be reset; however, it must be reset to
relieve at a pressure which is in accor-
dance with the requirements of the
authority having jurisdiction.
To reset the dry pilot pressure relief
valve, first loosen the jam nut and then
adjust the cap accordingly, clockwise
for a higher pressure setting or counter
clockwise for a lower pressure setting.
After verifying the desired pressure
setting, tighten the jam nut.
Step 14. A suitable automatic supervi-
sory air (nitrogen) supply, as described
in the Technical Data section, is to be
installed in accordance with the appli-
cable technical data sheet and set for
10 ± 2 psi (0,69 ± 0,14 bar).
Step 15. A desiccant dryer, when
required for the supervisory air supply,
is to be installed between a drip leg
and the Model AMD-1 air mainte-
nance device or between the Model
G16AC812 automatic supervisory air
supply and the preaction trim.
Step 16. The supervisory low pressure
switch is to be wired to the supervisory
alarm initiating circuit of an alarm panel.
Step 17. Conduit and electrical con-
nections are to be made in accordance
with the applicable standards of the
approval agency.
Step 18. Before a system hydrostatic
test is performed, the DV-5Adiaphragm
chamber is to be depressurized, the
automatic drain valve is to be tem-
porarily replaced with a plug, and the
diaphragm cover bolts must be uni-
formly and securely tightened using
a cross-draw sequence.After tight-
ening, double-check to make certain
that all of the diaphragm cover bolts
are securely tightened. See Table B in
the Care and Maintenance section for
torque specifications.
Note: When installing dry pilot actuation,
the system will require two automatic air
supplies as described in Steps 9 and 14.

TFP1416
Page 13 of 18
Note:
Port Connections P1 through P7 are described in Figure 2.
External Trim Connections
C1
C2
C3
C4
C5
C6
C7
C8
C9
Diaphragm Supply Connection
Water Motor Alarm Connection
Dry Pilot Line Connection
Dry Pilot Air Supply Connection
Supervisory Air Supply Connection
Waterow Pressure Alarm Switch
Connection
Low Air Pressure Alarm Switch
Connection
Main Drain Connection
Drip Funnel Connection
Item Description
A
B
C
D
E
F
G
H
J
K
L
M
DV-5aValve
System Main Control Valve
Waterow Pressure Switch
Main Drain Valve
System Drain Valve
Automatic Drain Valve
Alarm Test Valve
Alarm Control Valve (Optional)
Water Supply Gauge
Diaphragm Gauge
System Gauge
Manual Control Station
Item Description
N
P
Q
R
S
T
U
V
W
X
Y
Z
Manual Reset Actuator
Diaphragm Supply Valve
Diaphragm Supply Strainer
Inverted Flare Shut-Off Valve
Supervisory Air Supply Valve
Supervisory Air Pressure Relief Valve
Supervisory Low Pressure Switch
Dry Pilot Actuator
Dry Pilot Low Pressure Switch
Dry Pilot Air Supply Valve
Dry Pilot Line Gauge
Dry Pilot Air Pressure Relief Valve
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
C8
C9
C4
C7
C3
C7
C5
C2 C6
C1
A
B
JK
D
E
F
G
M
N
P
Q
U
V
W
X
Y
Z
S
L
T
C
H
R
P1
P6
P7
P2
P3
P4
P5
FIGURE 8
DV-5AVALVE - SINGLE INTERLOCK PREACTION DRY PILOT ACTUATION
(See Figure 6 for specific Bills of Materials)

TFP1416
Page 14 of 18
Step 14. Close the hinged cover of the
manual control station (M) and insert a
new break rod in the small hole through
the top of the enclosing box.
Step 15. Fully open the system main
control valve (B).
Step 16. After setting a fire protec-
tion system, notify the proper authori-
ties and advise those responsible for
monitoring proprietary and/or central
station alarms.
Care and
Maintenance
The following procedures and inspec-
tions must be performed as indicated,
in addition to any specific require-
ments of the NFPA and any applicable
standards recognized by the Approval
agency. Any impairment must be imme-
diately corrected. See Figure 8.
NOTICE
If the water supply needs to be shut off
to the DV-5Avalve and trim and cannot
be shut off upstream of the system,
close the system main control valve (B),
the diaphragm supply valve (P), and the
inverted flare shut-off valve (R). This will
allow any trim above the system main
control valve (B) to be taken apart for
service if necessary.
The frequency at which the following
procedures and inspections are to be
performed are to be in accordance with
the NFPA and any applicable specific
requirements of the standards recog-
nized by the Approval agency.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must first be obtained from the proper
authorities and all personnel who may
be affected by this action must be
notified.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this docu-
ment, as well as with the NFPA and any
applicable standards recognized by the
Approval agency. Contact the install-
ing contractor or product manufacturer
with any questions.
Some procedures in this section result
in the operation of the associated
alarms. Notify the owner and the fire
department, central station, or other
signal station to which the alarms are
connected before performing the tests.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with the
NFPA and any applicable standards
recognized by the Approval agency.
Drop in Water Supply Pressure
Below Normal Range
NOTICE
If the water supply pressure is signif-
icantly reduced below the normally
expected static pressure range (as
could occur in the case of a water main
break or repair), and there is a subse-
quent drop in the diaphragm chamber
water pressure below its normal range
(for example, due to a leak in a piping
connection to or from the diaphragm
chamber or, a leak in the diaphragm
chamber check valve caused by dirt or
debris in the check valve seal area), a
deluge valve such as the DV-5Acould
inadvertently trip, if its water supply
pressure is quickly restored.
A drop in the water supply pressure
to below its normal range (as in the
case of an interrupted water supply
condition) constitutes an emergency
impairment.
Should this condition occur, immedi-
ately close the system main control
valve (B) and use the following proce-
dure to reset the system:
Step 1. Prior to the water supply pres-
sure being restored to the closed
system main control valve (B), note the
pressure indicated by the diaphragm
gauge (K) and determine if the pressure
is within the normally expected range.
Step 2. If the diaphragm chamber pres-
sure is below the normal range, check
for and correct any source of leakage
from the diaphragm chamber prior to
resetting the system.
Step 3. After the water supply pres-
sure is restored to the system main
control valve (B), reset the DV-5Avalve
in accordance with the Valve Setting
Procedure section.
NOTICE
For fire protection systems subject to
an emergency impairment caused by
an interrupted water supply condition,
it is recommended that consideration
be given to installing a low water supply
pressure switch with the appropriate
alarm/indications to monitor the water
supply pressure.
Waterflow Alarm Test Procedure
To test the waterflow alarm, open the
alarm test valve (G), which will allow a
flow of water to the waterflow pressure
switch (C) and/or water motor alarm.
Upon satisfactory completion of the
test, close the alarm test valve (G).
To ensure drainage of the alarm line,
depress the plunger on the automatic
drain valve (F).
Supervisory Low Pressure Alarm
Test Procedure
Proper operation of the supervisory low
pressure switch (U) must be performed
as follows:
Step 1. Open the system drain valve
(E) just enough to slowly relieve super-
visory air pressure from the system.
Verify that the supervisory low pressure
switch (U) is operational and that the
low pressure set point is approximately
5 psi (0,34 bar).
Step 2. Close the system drain valve
(E) and allow the system supervisory
pressure of 10 ± 2 psi (0,69 ± 0,14 bar)
to be automatically re-established. The
supervisory low pressure switch (U)
should return to its normal condition.
Pressure Relief Valve Maintenance
Over pressurization of the system
piping with air will result in the opening
of the supervisory air pressure relief
valve (T). If the supervisory air pres-
sure relief valve (T) continues to bleed
air after the system pressure has
been reduced to its normal super-
visory pressure range of 10 ± 2 psi
(0,69 ± 0,14 bar), most likely debris
became lodged in the seating area. To
help clean the seating area, slowly pull
up on the ring at the top of the supervi-
sory air pressure relief valve (T) to allow
a full flow of air through the supervisory
air pressure relief valve (T), and then
release the ring to allow the supervi-
sory air pressure relief valve (T) to snap
closed. Repeat the cleaning procedure
as necessary.

TFP1416
Page 15 of 18
Dry Pilot Actuation
Operation Test Procedure
Proper operation of the DV-5Avalve,
such as opening of the DV-5Avalve as
during a fire condition, must be verified
as follows:
Step 1. If water must be prevented
from flowing beyond the riser, perform
the following steps:
• Close system main control valve (B).
Open main drain valve (D).
• Open system main control valve (B)
one turn beyond position at which
water just begins to flow from main
drain valve (D).
• Slowly close the main drain valve (D).
Step 2. Open the inspector’s test
connection.
Note: Be prepared to quickly perform Steps
3, 4, and 5 if water must be prevented from
flowing beyond the riser.
Step 3. Verify that the DV-5Avalve has
tripped, as indicated by the flow of
water into the system.
Step 4. Close the system main control
valve (B).
Step 5. Close the diaphragm supply
valve (P).
Step 6. Reset the DV-5Avalve in accor-
dance with the Valve Setting Procedure.
Dry Pilot Actuator Test Procedure
Proper operation of the dry pilot actua-
tor for dry pilot actuation must be veri-
fied as follows:
Step 1. Close the system main control
valve (B).
Step 2. Open the main drain valve (D).
Step 3. Open the inspector’s test con-
nection on the dry pilot line.
Step 4. Verify that there is a flow of
water from the dry pilot actuator (U)
drain connection.
Step 5. Verify that the diaphragm
chamber pressure has decreased
to below 25% of the water supply
pressure.
Step 6. Close the inspector’s test con-
nection and allow the dry pilot line
pressure to re-establish, and proceed
as follows:
• Water should cease draining from
the dry pilot actuator (U) but remain
draining from the manual reset actu-
ator (N).
• Press the reset knob on the manual
reset actuator (N) and hold it a few
seconds until water stops flowing
from its drain valve.
• Pressure will then build up in the
DV-5Adiaphragm chamber.
• After system pressure is restored
in the DV-5Adiaphragm chamber,
inspect the Dry pilot actuator (U) and
manual reset actuator (N) for leaks at
the drain tubes. Any leaks must be
corrected before proceeding to the
next step.
Step 7. Partially open the system main
control valve (B). Slowly close the main
drain valve (D) as soon as water dis-
charges from the main drain valve (D)
and then close the main drain valve
(D). Observe the automatic drain valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem. If there are no leaks, the
DV-5Avalve is ready to be placed in
service and the system main control
valve (B) must then be fully opened.
Low Pressure Alarm and
Condensate Drain for Dry Pilot
Actuation Test Procedures
Testing of the dry pilot low pressure
switch (W) and drainage of the pilot
line condensate must be performed as
follows:
Step 1. Close the system main control
valve (B).
Step 2. Close the diaphragm supply
valve (P).
Step 3. Open the main drain valve (D).
Step 4. Open the inspector’s test con-
nection, and slowly relieve pneumatic
pressure. Verify that the dry pilot low
pressure switch (W) is operational and
that the low pressure set points are as
follows:
• Low pressure alarm setting at
approximately 6 psi (0,4 bar) below
the minimum pilot line service pres-
sure requirement shown in Graph B
• Fire alarm setting at approximately
14.5 psi (1,0 bar) below the minimum
pilot line service pressure require-
ment shown in Graph B.
Step 5. Close the inspector’s test con-
nection and allow the dry pilot line to
automatically repressurize.
Step 6. Individually open each low
point drain and then close after dis-
charge of any trapped condensate.
The gauge test valve to which the dry
pilot line gauge (Y) is connected must
be used as a low point drain. Close the
gauge test valve, remove the plug, and
partially open the gauge test valve (as
necessary, collect water in a cup). After
condensate water ceases to drain,
close the gauge test valve, replace the
plug, and then completely open the
gauge test valve.
Step 7. Allow the dry pilot line to auto-
matically repressurize.
Step 8. Open the diaphragm supply
valve (P).
Step 9. Partially open the system main
control valve (B). Slowly close the main
drain valve (D) as soon as water dis-
charges from the main drain valve (D).
Observe the automatic drain valve
(F) for leaks. If there are leaks, deter-
mine/correct the cause of the leakage
problem. If there are no leaks, the
DV-5Avalve is ready to be placed in
service and the system main control
valve (B) must then be fully opened.

TFP1416
Page 16 of 18
Internal Valve Inspection
Once every five years during the annual
operational test procedure and prior
to the DV-5Avalve being reset and
with the DV-5Avalve de-pressurized,
the interior of the DV-5Avalve must
be cleaned and inspected for wear
and damage. Damaged or worn parts
must be replaced. Replacement of the
Diaphragm every ten years is recom-
mended, or more frequently if inspec-
tions and/or wear and tear warrant
more frequent replacement.
NOTICE
The diaphragm cover may be removed
between Steps 4 and 5 of the reset-
ting instructions, since at that point the
DV-5avalve should be de-pressurized
as evident by a zero gauge reading on
the diaphragm gauge (K) and water
supply gauge (J), as well as no water
discharging from the automatic drain
valve (F).
To perform internal valve inspection
between Steps 4 and 5 of the Valve
Setting Procedure remove the dia-
phragm cover as follows:
Step 1. Close the inverted flare shut-
off valve (R).
Step 2. Remove the copper tube fitting
between the diaphragm supply valve
(P) and the inverted flare shut-off valve
(R).
Step 3. Loosen the union securing the
dry pilot actuation trim, and remove the
dry pilot actuation trim.
Step 4. Loosen and remove the union
between the diaphragm cover and the
MRA-1 manual reset actuator (N) and
remove the MRA-1 manual reset actua-
tor (N) subassembly.
Step 5. Remove the diaphragm valve
cover hardware, then slowly remove the
diaphragm cover and perform internal
valve inspection. Clean the valve inte-
rior and replace parts as necessary.
After cleaning and inspecting valve
interior, and replacing parts as nec-
essary, reinstall the diaphragm cover
by completing the following steps to
assure the diaphragm cover fasteners
are uniformly and securely tightened.
Step 1. With reference to Figure 1,
ensure that the diaphragm is properly
oriented and that the proper hardware
arrangement is utilized when assem-
bling the diaphragm covers. The hard-
ware arrangements differ depending on
the size of the DV-5Avalve.
Step 2. By first using the long hex bolts,
support of the diaphragm cover will be
provided before installing the short hex
bolts. Align diaphragm in proper orien-
tation with valve body, and then align
diaphragm cover in proper orienta-
tion with valve body. Hand-tighten all
fasteners.
Step 3. Using crossdraw sequence to
assure uniformity, wrench-tighten long
hex Bolts and short hex bolts to appro-
priate torque values. Repeat crossdraw
sequence two to three times at incre-
mental torque valves until reaching the
torque valves found in Table B.
Step 4. Inspect to assure all hex bolts
are securely tightened.
Step 5. Using the union, secure the
MRA-1 manual reset actuator (N) to the
diaphragm cover.
Step 6. Using the union, secure the dry
pilot actuation trim.
Step 7. Replace the copper tube fitting
between the diaphragm supply valve
(P) and the inverted flare shut-off valve
(R).
Step 8. Ensure that the unions and flare
fittings are securely tightened.
Step 9. With the diaphragm supply
valve (P) closed, fully open the inverted
flare shut-off valve (R) stainless steel
screw (approximately ½ in.) until resis-
tance is met so as not to break the
internal roll-pin. The internal roll-pin
stops the removal of the inverted flare
shut-off valve (R) stainless steel screw.
Step 10. Proceed with Step 5 of the
Valve Setting Procedures section in this
data sheet.
NOTICE
If the water supply contains chemicals
which tend to attack a polyester fab-
ric-reinforced, EPDM rubber or the five
year inspection indicates a build-up of
debris within the DV-5Avalve that could
affect its proper operation, then the
frequency of the internal valve inspec-
tion procedure must be appropriately
increased.
With reference to Figure 1, make
certain that the diaphragm is correctly
oriented; otherwise, the DV-5Avalve
cannot be properly set.
Under-tightening the diaphragm cover
bolts can result in internal and external
leakage.
Use only TYCO replacement fasteners
as specified in Figure 1.
Do not apply adhesives, lubricants,
or other substances to the diaphragm
valve body.
Nominal
Valve Sizes
ANSI
Inches
(DN)
Torque
lb-ft
(N∙m)
Nuts Short
Hex
Bolts
1 1/2
(40) 44
(59,7) 35
(47, 5 )
2
(50) 44
(59,7) 35
(47, 5 )
3
(80) 125
(169,5) 125
(169,5)
4
(100) 150
(203,4) 150
(203,4)
61
(150) 150
(203,4) 150
(203,4)
8
(200) 188
(254,9) 188
(254,9)
NOTES
1. Also applicable to metric 165,1 mm size.
TABLE B
DIAPHRAGM COVER BOLTS
MINIMUM TORQUE

TFP1416
Page 17 of 18
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
The TYCO DV-5AAutomatic Water
Control Single Interlock Preaction Dry
Pilot Actuation Valve may be ordered
as follows:
Pre-Assembled Valves
with Trim
DV-5AValves with Galvanized Trim
and Butterfly Valve
Specify: Size (specify), DV-5AAuto-
matic Water Control Valve, G x G con-
nections with assembled galvanized
Americas Single Interlock Preaction
Dry Pilot Actuation Trim, complete with
assembled Model BFV-300 Butterfly
Valve, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 551011215
2 in. (DN50) .................... 551011220
3 in. (DN80) .................... 551011230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 551011240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 551011260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 551011280
Note: Americas pressure switches and psi/
kPa water pressure gauges are provided
This arrangement is available for EMEA
and APAC upon request. Contact your lo-
cal distributor.
AMERICAS
DV-5AValves with Galvanized Trim
Specify: Size (specify), DV-5AAuto-
matic Water Control Valve, (specify)
end connection with assembled gal-
vanized Americas Single Interlock Pre-
action Dry Pilot Actuation Trim, P/N
(specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 55 0011215
2 in. (DN50) ....................550 011220
3 in. (DN80) ....................55 0011230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 55 0011240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 55 0011260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 5 50011280
Flange x Flange ANSI
3 in. (DN80) ....................550021230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550021240
6 in. (DN150)....................550021260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550021280
Flange x Groove ANSI
3 in. (DN80) ....................550031230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550031240
6 in. (DN150)....................550031260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550031280
Thread x Thread NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550061215
2 in. (DN50) ....................550061220
Note: Pressure switches and psi/kPa water
pressure gauges are provided.
Separate DV-5AValves without Trim
See Table A for flange drilling
specifications.
Specify: Size (specify), DV-5AAuto-
matic Water Control Valve, (specify)
end connection, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530010015
2 in. (DN50) ....................530010020
3 in. (DN80) ....................530010030
4 in. (DN100)....................530010040
6 in. (DN150)....................530010060
8 in. (DN200) ...................530010080
Flange x Flange ANSI
3 in. (DN80) ....................530020030
4 in. (DN100)....................530020040
6 in. (DN150)....................530020060
8 in. (DN200) ...................530020080
Flange x Groove ANSI
3 in. (DN80) ....................530030030
4 in. (DN100)....................530030040
6 in. (DN150)....................530030060
8 in. (DN200) ...................530030080
Thread x Thread NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530060015
2 in. (DN50) ....................530060020
Note: Valves are typically provided with
flange drilling per ANSI B16.1 (Class 125) or
ISO (7005-2 PN16).
Upon request, valves can be provided with
flange drilling per JIS B 2210 or AS 2129. In
which case part numbers are not assigned.
DV-5AValve Trim Semi-Assembled
Specify: Size (specify), finish (specify),
Dry Pilot Actuation Trim for DV-5AAuto-
matic Water Control Valves used in
Single Interlock Preaction Fire Protec-
tion System, P/N (specify):
Galvanized
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 540001220
2 in. (DN50) ....................540001220
3 in. (DN80) ....................540001230
4 in. (DN100)....................540001240
6 in. (DN150)....................540001260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 540001280
Black
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 542001220
2 in. (DN50) ....................542001220
3 in. (DN80) ....................542001230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 542001240
6 in. (DN150)....................542001260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 542001280
Note: Pressure switches are separately
ordered.
EMEA
DV-5AValves with Galvanized Trim
Specify: Size (specify), DV-5AAuto-
matic Water Control Valve, (specify)
end connection with assembled galva-
nized EMEA Single Interlock Preaction
Dry Pilot Actuation Trim, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550111215
2 in. (DN50) .................... 55 0111220
3 in. (DN80) .................... 550111230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550111240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550111260
165,1 mm ......................550111266
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550111280
Flange x Flange ANSI
3 in. (DN80) ....................550121230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550121240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550121260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550121280
Flange x Groove ANSI
3 in. (DN80) ....................550131230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550131240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550131260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550131280
Flange x Flange ISO
3 in. (DN80) ....................550141230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550141240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550141260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550141280
Flange x Groove ISO
3 in. (DN80) ....................550151230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550151240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550151260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550151280
Thread x Thread ISO
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550171215
2 in. (DN50) ....................550171220
Note: Pressure switches, bar/psi water
pressure gauges, and NPT to ISO threaded
trim adaptors for external connections are
provided.
Separate DV-5AValves without Trim
See Table A for flange drilling
specifications.
Specify: Size (specify), DV-5AAuto-
matic Water Control Valve, (specify)
end connection, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530010015
2 in. (DN50) ....................530010020
3 in. (DN80) ....................530010030
4 in. (DN100)....................530010040
6 in. (DN150)....................530010060
165,1 mm ......................530010066
8 in. (DN200) ...................530010080
Flange x Flange ANSI
3 in. (DN80) ....................530020030
4 in. (DN100)....................530020040
6 in. (DN150)....................530020060
8 in. (DN200) ...................530020080
Flange x Groove ANSI
3 in. (DN80) ....................530030030
4 in. (DN100)....................530030040
6 in. (DN150)....................530030060
8 in. (DN200) ...................530030080
Thread x Thread NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530060015
2 in. (DN50) ....................530060020
Flange x Flange ISO
3 in. (DN80) ....................530040030
4 in. (DN100)....................530040040
6 in. (DN150)....................530040060
8 in. (DN200) ...................530040080
Flange x Groove ISO
3 in. (DN80) ....................530050030
4 in. (DN100)....................530050040
6 in. (DN150)....................530050060
8 in. (DN200) ...................530050080
Thread x Thread ISO
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530070015
2 in. (DN50) ....................530070020
Note: Valves are typically provided with
flange drilling per ANSI B16.1 (Class 125) or
ISO (7005-2 PN16).
Upon request, valves can be provided with
flange drilling per JIS B 2210 or AS 2129. In
which case part numbers are not assigned.

TFP1416
Page 18 of 18
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2023 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
DV-5AValve Trim
Specify: Size (specify), finish (specify),
Dry Pilot Actuation Trim for DV-5AAuto-
matic Water Control Valves used in
Single Interlock Preaction Fire Protec-
tion System, P/N (specify):
Galvanized
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 540101220
2 in. (DN50) ....................540101220
3 in. (DN80) ....................540101230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 540101240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 540101260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 540101280
Black
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 542101220
2 in. (DN50) ....................542101220
3 in. (DN80) ....................542101230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 542101240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 542101260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 542101280
Note: Pressure switches, water pressure
gauges, and BFV-300 Butterfly Valve are
separately ordered. NPT to ISO threaded
adaptors are provided for External Trim Con-
nections (drains, pressure switches, water
motor alarms, etc.).
APAC
DV-5AValves with Galvanized Trim
Specify: Size (specify), DV-5AAuto-
matic Water Control Valve, (specify)
end connection with assembled galva-
nized APAC Single Interlock Preaction
Dry Pilot Actuation Trim, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 55 0011215
2 in. (DN50) ....................550 011220
3 in. (DN80) ....................55 0011230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 55 0011240
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 55 0011260
165,1 mm ......................550 01126 6
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 5 50011280
Flange x Flange ANSI
3 in. (DN80) ....................550021230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550021240
6 in. (DN150)....................550021260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550021280
Flange x Groove ANSI
3 in. (DN80) ....................550031230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550031240
6 in. (DN150)....................550031260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550031280
Thread x Thread NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550061215
2 in. (DN50) ....................550061220
Flange x Flange ISO
3 in. (DN80) ....................550041230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550041240
6 in. (DN150)....................550041260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550041280
Flange x Groove ISO
3 in. (DN80) ....................550051230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550051240
6 in. (DN150)....................550051260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550051280
Note: Pressure switches and psi/kPa water
pressure gauges are provided.
Separate DV-5AValves without Trim
See Table A for flange drilling
specifications.
Specify: Size (specify), DV-5AAuto-
matic Water Control Valve, (specify)
end connection, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530010015
2 in. (DN50) ....................530010020
3 in. (DN80) ....................530010030
4 in. (DN100)....................530010040
6 in. (DN150)....................530010060
165,1 mm ......................530010066
8 in. (DN200) ...................530010080
Flange x Flange ANSI
3 in. (DN80) ....................530020030
4 in. (DN100)....................530020040
6 in. (DN150)....................530020060
8 in. (DN200) ...................530020080
Flange x Groove ANSI
3 in. (DN80) ....................530030030
4 in. (DN100)....................530030040
6 in. (DN150)....................530030060
8 in. (DN200) ...................530030080
Thread x Thread NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530060015
2 in. (DN50) ....................530060020
Flange x Flange ISO
3 in. (DN80) ....................530040030
4 in. (DN100)....................530040040
6 in. (DN150)....................530040060
8 in. (DN200) ...................530040080
Flange x Groove ISO
3 in. (DN80) ....................530050030
4 in. (DN100)....................530050040
6 in. (DN150)....................530050060
8 in. (DN200) ...................530050080
Thread x Thread ISO
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530070015
2 in. (DN50) ....................530070020
Note: Valves are typically provided with
flange drilling per ANSI B16.1 (Class 125) or
ISO (7005-2 PN16).
Upon request, valves can be provided with
flange drilling per JIS B 2210 or AS 2129. In
which case part numbers are not assigned.
DV-5AValve Trim
Specify: Size (specify), finish (specify),
Dry Pilot Actuation Trim for DV-5AAuto-
matic Water Control Valves used in
Single Interlock Preaction Fire Protec-
tion System, P/N (specify):
Galvanized
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 540001220
2 in. (DN50) ....................540001220
3 in. (DN80) ....................540001230
4 in. (DN100)....................540001240
6 in. (DN150)....................540001260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 540001280
Black
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 542001220
2 in. (DN50) ....................542001220
3 in. (DN80) ....................542001230
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 542001240
6 in. (DN150)....................542001260
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 542001280
Note: Pressure switches are separately
ordered.
DV-5AValve Trim Accessories
(for separately ordered valve trim)
Specify: (specify accessory descrip-
tion), P/N (specify):
Waterflow Pressure Alarm Switch
PS10-2 (America) . . . . . . . . . . . . . . . . . . . . 25720
Waterflow Pressure Alarm Switch
PS10-2 (APAC) .............25710 OR 100102
Waterflow Pressure Alarm Switch
PS10-1 (EMEA). . . . . . . . . . . . . . . . . . . . . . . 0260
Supervisory Air Pressure Alarm Switch, Potter
PS40-2 (America/APAC) . . . . . . . . . . . . . . 25710
Supervisory Air Pressure Alarm Switch
PS40-1 (EMEA) . . . . . . . . . . . . . . . . . . . . . . 0262
Model WMA-1 Water Motor Alarm
(America/APAC) . . . . . . . . . . . . . . . . 526301001P
Model WMA-1 Water Motor Alarm
(EMEA) . . . . . . . . . . . . . . . . . . . . . . . 526301021R
Model AMD-1 Air Maintenance Device,
Dry Pilot . . . . . . . . . . . . . . . . . . . . . . . 523242002
Model AMD-2 Air Maintenance Device,
Dry Pilot . . . . . . . . . . . . . . . . . . . . . . . 523262001
Model AMD-3 Nitrogen Maintenance Device,
Dry Pilot . . . . . . . . . . . . . . . . . . . . . . . 523282001
Model G16AC812 Automatic Supervisory
Air Supply......................521201001
Model AMD-1 Air Maintenance Device
Supervisory Air Supply . . . . . . . . . . . 523242002
Model AMD-3 Nitrogen Maintenance Device
Supervisory Air Supply . . . . . . . . . . . 523282001
Model MC-1
Manual Control Stations . . . . . . . . . . 522892001
Water Gauges
with bar/psi ....................025500013
600 psi Water Gauge psi/kPa
(service pressure over 300 psi) . . . . . 923431004
DV-5AValve Replacement Parts
Specify: (Description) for use with
(specify size) DV-5aAutomatic Water
Control Valve, P/N (See Figure 1)
DV-5AValve Trim Replacement
Parts
Specify: (Description) for use with
DV-5AValve Trim, P/N (See Figure 6)

TFP1416
Change History Appendix
Worldwide
Contacts
www.tyco-fire.com
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2023 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
ISSUE DATE NOTES
05-23
Page 10, Figure 6 (2 of 2), Item A2, Waterow Pressure Alarm Switch, Single Contacts (EMEA), added
alternate P/N 100101, Item A3, Low Air Pressure Alarm Switch, Single Contacts (EMEA), added alter-
nate P/N 100401.
01-23
Page 1, updated QR code and URL; Page 10, Figure 6 (2 of 2), Items A2 and A3, updated Waterow
and Low Air Pressure Alarm Switch part numbers and regional applicability; Page 11, Figure 7, updated
dimensions; Page 18, changed corporate address and telephone number to 1467 Elmwood Avenue,
Cranston, RI 02910 | Telephone +1-401-781-8220, formerly 1400 Pennbrook Parkway, Lansdale, PA 19446
| Telephone +1-215-362-0700; Incorporated Appendix A into document, including print instructions.
06-22
Page 1, added QR code and URL to allow convenient access to electronic version from printed docu-
ment; Page 16, Table B, updated Diaphragm Chamber Cover Bolt minimum torque specications for all
valve sizes. Separate document Appendix A is also updated to reect new edition TFP1416 issue date.
06-21 Added metric 165,1 mm size. Separate Appendix A also updated to reect TFP1416 issue date.
04-21 Removed unnecessary solenoid valves statements from Ordering Procedure. Separate Appendix A is
also updated to reect TFP1416 issue date.
03-21 Update dimension H values (inlet of buttery valve or welded tee to DV-5A valve inlet). Separate Appen-
dix A is also updated to reect TFP1416 issue date.
12-20 Corrected Valve Setting Procedure, Supervisory Air Supply Valve item reference letter changed from R
to S to correspond with Figure 8. Separate Appendix A is also updated to reect TFP1416 issue date.
05-20
New Technical Data Sheet TFP1416 describes DV-5A Automatic Water Control Valve with Preaction
Fire Protection System Single-Interlock Dry Pilot Actuation Trim, formerly described in now-obsolete
technical data sheet TFP1425. Separate Appendix A operation and setting procedure poster issued in
conjunction with TFP1416.

APPENDIX A INSTRUCTIONS TFP1416
Worldwide
Contacts
www.tyco-fire.com
DV-5AAppendix
Poster Printing
Instructions
General
Description
The appendix found at the end of this
document provides valve setting and
testing/inspection procedures summa-
rized from the Care and Maintenance
section.
Some jurisdictions require a copy of the
Summary Instructions appendix to be
displayed in proximity to a DV-5AAuto-
matic Control Valve riser supplying a
fire protection system.
Reproduce as an individual poster by
printing on appropriate media.
A form of protection is recommended
to prevent damage which could render
the poster illegible. Conditions to avoid
include moisture infiltration, fading,
mutilation, etc.. Protective measures
may include lamination, placement
within an impact- and water-resistant
frame, etc.
The format shown in this document is
landscape orientation on US Tabloid
size, also known as ANSI B drawing
format, both roughly comparable to
ISO A3 size format.
To avoid potential cropping of content
when printing to A3 format, select
options such as print to fit or scale
to fit. Depending on printer capabil-
ity content will be slightly reduced but
should remain readable.
See Print Format Dimensions Table for
details.
Format
Imperial
in. Metric
mm
WHWH
US Tabloid 17 11 — —
ANSI B
ISO A3 — — 420 297
PRINT FORMAT DIMENSIONS
TFP1485 APPENDIX A
AUGUST 2022
1467 Elmwoo d Avenue, Cran ston, RI 02910 | Tele phone +1-401-781-82 20
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision d ate and are sub ject to chang e without not ice.
Worldwide
Contacts
www.tyco-fire.com
Summary Instructions
DV-5AAutomatic Water Control Valve
Preaction Type A Systems
(EN12845 Compliance)
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date elec tronic version of this
document. Data rates may apply.
docs.jci.com/tycore/tfp1485
NOTICE
The procedu res provided are s ummary instructions of the c omplete procedures appe aring in
Technical Data Sheet TFP1485. If problems occur, consult full document.
Valve Setting Procedure
1. Close System Main Control Valve (B), Diaphragm Supply Valve (P), and Air Supply Control
Valves (X) and ( Y).
2. Open Main Drain Valve (D), System D rain Valve (E), and all auxiliar y drains in system. Also,
remove plug from Air Supply Strainer (W ) to drain any water and ensure i t is clean and free
of debris. Close aux iliary drain valves, System Drain Valve (E), and reassemble Air Supply
Strainer (W ) after water stops disc harging. Leave Main Drain Valve (D) open.
3. Ensure Pressure Gauge Valves and Alarm Control Valve (H), as applicable, are open.
4. Depress plunge r of Automatic Drain Valve (F) to verify it is open.
5. Clean Diaphragm Supply Strainer (Q). Flush s trainer by opening the Di aphragm Supply
Valve ( P).
6. Replace operated automatic sprinkler s on system piping.
7. Reset DV-5AValve Releasing Panel in accordance with manufacturer instructions.
8. Re-establish system air pressure to reset Model DP-1 Dry Pilot Actuator ( T) by opening Air
Supply Control Valve (X ). Do not open Air Supply Control Valve (Y) at this time. Observe Dr y
Pilot Actuator (T ) air pressure on Dry Pilot Gauge (Z).
9. Open Manual Control Station (M), then open Diaphragm Supply Valve (P). After aerated
water stops discharging f rom Manual Control Station (M) drain tube, slowly clo se operating
lever. Do not close hinged cover at this time.
10. After aerated water stops discharging, re set Manual Reset Actuator (N) until water stops
owing from its drain tube and pressure reaches approximately 15 psi (1,0 bar) on Diaphragm
Gauge (K).
11. With diaphragm chamber pressurized, temporarily close Diaphragm Supply Valve (P), and
observe Diaphragm Gauge (K) for a drop in pressure. If pre ssure drop is noted, replace DV-5A
Diaphragm and co rrect any leaks before p roceeding.
12. If Diaph ragm Gauge (K) indicates no drop in pressu re, re-open Diaphragm Supply Valve
(P) and procee d.
13. Open Air S upply Control Valve (Y ) to pressurize system piping.
14. Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from M ain Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, correct the leakage problem.
15. Close hinge d cover of Manual Control Station (M) and insert new break rod in small hole
through the top of the enclosing box.
16. Open System Main Control Valve (B).
17. After setting re protection system, notify proper authorities and advise those responsible
for monitoring proprietary and/or central station alarms.
Waterflow Alarm Test Procedure
1. Open Alarm Test Valve (G), allowing water to ow to Waterow Pressure Switch (C) and/or
Water Motor Alarm. Close Alarm Test Valve (G) when test is completed.
2. Depress plunge r on the Automatic Drain Valve (F ) to drain alarm line.
Solenoid Valve Test Procedure For Electric Actuation
1. Close System Main Control Valve (B) and open Main Drain Valve (D).
2. Test deluge releasing panel in accordance with manufacturer’s instructions to energize
the Solenoid Valve (R).
3. Verify that water is owing fro m Solenoid Valve (R) drain conne ction.
4. Verify Diaphrag m Chamber pressure has decrea sed to below 25% of water supply press ure.
5. Reset electric detection system in accorda nce with manufacturer’s instructions to de-ener-
gize Solenoid Valve (R). Water should top draining from Solenoid Valve (R) but remain draining
from Manual Reset Actuator (N).
6. Press Reset Knob o n Manual Reset Actuator ( N) and hold a few seconds until water stops
owing.
7. After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator
(N) for leaks. Correct any leaks before proc eeding.
8. Partially open S ystem Main Control Valve (B). Slowly close M ain Drain Valve (D) as water
discharges from M ain Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, corre ct the leakage proble m. If there are no leaks, place DV-5AValve in service a nd
open System Main Control Valve (B).
Solenoid Valve and Dry Pilot Actuator Test Procedure
1. Close System Main Control Valve (B) and open Main Drain Valve (D).
2. Simulate power failure by disconnecting main power to releasing panel, and disconnecting
battery back-up. Refer to releasing panel manufacturer’s instructions for specic details. This
step allows Solenoid Valve (S) to open.
3. Open system’s Inspector’s Test Connection to relieve system air pressure.
4. Verify water ow from Dr y Pilot Actuator (T ) drain connection.
5. Verify Diaphragm Chamber pressure decreased to below 25% of water supply pressure.
6. Close Inspector’s Test Connectio n and allow the system air pressure to re-establish. Water
stops draining from Dry Pilot Actuator (T ) but continues to drain from Manual Reset Ac tua-
tor (N). Press Reset Knob on Manual Reset Actuator (N) and hold a few seconds until water
stops owing from drain tub e.
7. Pressure will then build up in DV-5ADiaphragm Chamber.
8. After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator
(N) for leaks. Any leaks must be corrected before proceeding.
9. Reestablish bat tery and main power to releasing panel in accordance with manufacturer’s
instructions.
10. Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from M ain Drain Valve (D), then close Main Drain Valve (D). Observe Automatic
Drain Valve (F) for leaks a nd correct the leak age problem. If there are no l eaks, place DV-5A
Valve in service and open System Main Control Valve (B).
Supervisory Low Pressure Alarm Test Procedure and Validation of Normally Closed
Solenoid Valve (S)
1. Close System Main Control Valve (B), and open Main Drain Valve (D).
2. Crack open system’s Inspector’s Test Connection to relieve air pressure from system.
Verify Supervisory Low Pressure Alarm Switch (V ) is operational a nd low pressure set point
is approximately 0,4 bar under minimum system air pressure.
3. Allow system air pressure to decay to 0 psig. Verify no water draining from Dry Pilot Ac tu-
ator (T ).
4. Close system’s Inspector’s Test Connection and allow system supervisor y pressure to auto-
matically re-established. As necessary, open, then close quick ll air supply control valve in
automatic air maintena nce device. Supervisory Low Pressure Alarm Switch (V ) should return
to “normal” condition.
5. Verify system air pres sure is normal and DV-5ADiaphragm Chamber remains pressurized.
6. Partially open S ystem Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from M ain Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, corre ct the leakage proble m. If there are no leaks, place DV-5AValve in service a nd
open System Main Control Valve (B).
Operation Test Procedure
1. To prevent water from owing beyond riser, close System Main Control Valve (B). Open
Main Drain Valve(D).
2. Open System Main Control Valve (B) one turn beyond which water begins to ow from Main
Drain Valve (D). Slowly close Main D rain Valve (D).
3. Test deluge releasing panel in accordance with manufacturer’s instructions to ene rgize
Solenoid Valve (R).
4. Veri fy DV- 5AValve has tripped, as indicated by water ow into system.
5. Close System Main Control Valve (B).
6. Close Diaphragm S upply Valve (P) and Air Supply Control Valves (X) and ( Y).
7. Reset DV-5AValve with Preaction Type A Trim in accordance with Valve Setting Proce dure.
Internal Valve Inspection
1. Ensure that Steps 1 to 4 of the Valve Setting Procedure are completed prior to proceeding
with the Internal Valve Inspec tion.
2. Ensure Diaphragm Supply Valve (P) is closed. If provided as part of the valve trim, close
Inverted Flare Shut-Off Valve (AA).
3. Remove the Supply Line bet ween the Diaphragm S upply Valve (P) and the System Main
Control Valve (B). If provided as par t of the valve trim, remove the Supply L ine between the
Diaphragm Supply Valve (P) and Inverted Flare Shut-O ff Valve (AA).
4. Loosen union securing Actuation Trim and remove Actuation Trim.
5. Remove union between D iaphragm Cover and MRA-1 Manual Reset Actuator (N). Remove
MRA-1 Manual Reset Actuator ( N) subassembly.
6. Remove Diaphragm Valve Cover hardware, slowly remove Diaphragm Cover and perform
internal valve inspec tion. Clean valve interior and replace parts as necessary.
7. Ensure Diaphragm is properly oriented and proper hardware arrangement is utilized.
8. Insert Long Hex Bolts. Align Diaphragm with Valve Body, and then align Diaphragm Cover
with Valve Body. Insert Shor t Hex Bolts. Hand-tighten all fasteners.
9. Using crossdraw se quence, wrench-tighten Long Hex Bolts and Shor t Hex Bolts. Repeat
crossdraw seque nce two to three times at incremental torque valves.
10. Inspect to assure all Hex Bolts are securely tightened.
11. Using the union, secure the MRA-1 Manual Reset Ac tuator (N) to the Diaphragm Cover.
12. Using union, secure Actuation Trim.
13. Replace the S upply Line between the D iaphragm Supply Valve and the System Main
Control Valve (B). If provided as par t of the valve trim, replace Supply Line betwee n Diaphragm
Supply Valve (P) and Inverted Flare Shut-Off Valve (A A).
14. Ensure unio ns and are ttings are securely tightened.
15. If provided with the valve trim, and with Diaphra gm Supply Valve (P) closed, fully open
Inverted Flare Shut-Off Valve (AA) stainless steel screw (approximately 1/2 in.) until resis-
tance is met.
16. Proceed with Step 5 of the Valve Setting Procedures.
Item Description
P
Q
R
S
T
U
V
W
X
Y
Z
AA
Diaphragm Supply Valve
Diaphragm Supply Strainer
Solenoid Valve (NC) D e-Energized #1
Solenoid Valve (NC) En ergized #2
Dry Pilot Actu ator
Pressure Relief Valve
Supervis ory Low Pressure Alarm Swi tch
Air Supply Strainer
Air Supply Con trol Valve "A"
Air Supply Con trol Valve "B"
Dry Pilot Gau ge
Inverted Fl are Shut-Of f Valve
Item Description
A
B
C
D
E
F
G
H
J
K
L
M
N
DV-5aVal ve
System Main Con trol Valve
Waterow Press ure Switch
Main Drain Valve
System Drain Valve
Automatic Drain Valve
Alarm Test Valve
Alarm Contro l Valve (Optional)
Water Supply Gauge
Diaphragm Gauge
System Gauge
Manual Control Station
Manual Reset Actuator
A
B
C
JK
D
E
F
G
N
P
Q
V
X
Y
M
W
S
T
R
L
Z
U
H
AA
W
H
Other manuals for DV-5A
13
Table of contents
Other Tyco Control Unit manuals